Menu structure UA 300 D
Controller type UR 141
91
E
2007 − ECKELMANN | BERLINER STRASSE 161 | 65205 WIESBADEN | FON +49(0)611 7103-0 | FAX 49(0)611 7103-133 | eckelmann.de
Version 2.03 27. Juni 2008
*) Status abcdef covers following states of the refrigeration point. Display will be " − " if state is not
active.
Two−zone operation
Single−zone operation
a
O = Operating
O = Operating
b
R = Cooling
R = Cooling
c
R = Cooling
D = Defrost
d
D = Defrost
G = Door (coldroom ctrlr. only)
e
G = Door (coldroom ctrl. only)
A = Alarm
f
A = Alarm
7.3.7
Menu 6 Configuration
CONFIGURAT
POS: XXXXX
1 Refrger. Point
Continue to Screen 6−1
2 Controller
Continue to Screen 6−2
3 Cooling
Continue to Screen 6−3
4 Language
Continue to Screen 6−4
S
Screen 6−1 Refrger. Point
REFR. PT.
POS: XXXXX
Entry
Default
Refriger. Point Name:
Text only
xxxxxxxxxxxxxxx
Free text entry describing refrigeration point (see note follo-
wing table)
Coldroom
controller
Item ID:
XXXXX
Free text entry displayed in screens after ITEM ID (see
note following table)
UA300
Priority:
XX
Alarm priority in failure of refrigeration point or when global
controller priority is set (Screen 6−5)
↑
,
↓
,
or numbers
(0..99)
1
Refr. Sys. No.:
XX
No. of pack controller allocated to case/coldroom controller
↑
,
↓
,
or numbers
(−−, 1..9)
1
Refr. Sys. Type:
XXX
Associated compressor pack.
Parameter only required when linked to a VS 3000 BS
having several zones. If a different type of pack controller
is used, set this parameter blank (−−−)
↑
,
↓
,
or numbers
(−−−, Z1, Z2)
−−−
No. Sensors
XX
Number of temperature sensors connected. After entering
↵
sensor scan is performed to redetermine the number of
sensors.
↵
Temp. Zones
X
Number of temperature zones:
Single−zone operation/
Two−zone operation
↑
,
↓
,
or numbers
(1, 2)
2
Содержание UA 300 D
Страница 2: ......
Страница 6: ...Table of contents iv Version 2 03 27 Juni 2008 Notice ...
Страница 8: ...System Design of UA 300 D 2 Version 2 03 27 Juni 2008 Notice ...
Страница 40: ...Installation and Startup of UA 300 D 34 Version 2 03 27 Juni 2008 Notice ...
Страница 54: ...Operation of UA 300 D 48 Version 2 03 27 Juni 2008 Notice ...
Страница 100: ...Menu structure UA 300 D Controller type UR 141 94 Version 2 03 27 Juni 2008 Notice ...
Страница 108: ...Specifications of UA 300 D 102 Version 2 03 27 Juni 2008 Notice ...