Menu structure UA 300 D
Controller type UR 141
89
E
2007 − ECKELMANN | BERLINER STRASSE 161 | 65205 WIESBADEN | FON +49(0)611 7103-0 | FAX 49(0)611 7103-133 | eckelmann.de
Version 2.03 27. Juni 2008
S
Screen 3−2 Defrost timer
DEFROST TIMER
POS: XXXXX
Entry
Default
Defrost timer
XXX
Defrost initiation via input D11/12 (EXT) or internal (INT)
↑
,
↓
,
(EXT, INT)
INT
Safe Defr Time
XXX m
Safe defrost time for maximum allowed duration of defro-
sting (used only for internal defrosting)
0..120
60 min
Defr. 1 xxxxx hh:mm
Defrost start time with internal defrosting; weekday, time;
shown only when internal defrosting is activated (Screen
3−2)
↑
,
↓
,
(Mo−Su etc.)
or numbers
(hh:mm)
Mo−Su
06:00
Defr. 2 xxxxx hh:mm
Defrost start time with internal defrosting; weekday, time;
shown only when internal defrosting is activated (Screen
3−2)
↑
,
↓
,
(Mo−Su etc.)
or numbers
(hh:mm)
Mo−Su
18:00
...
Defr. 14 xxxxx hh:mm
Manual Defrost
XXX
Status (OFF/ON) for supplementary manual defrosting *)
↑
,
↓
,
(ON/OFF)
OFF
*) Parameter automatically set to ON for safe defrost time at first start.
S
Screen 3−3 Toggle Setpoints
TOGGLE
POS: XXXXX
Entry
Default
Status
XXX
Setpoint toggle status (OFF/ON) of alternative set of setpo-
ints (setpoint toggle)
Toggle Setp.
XXX
Setpoint toggle via input D21/22 (EXT), internal (INT) or
disabled (−−)
↑
,
↓
,
(EXT, INT, −−)
EXT
Blind On Time
X s
Fan and cooling stop time after toggling to alternative set of
setpoints with external setpoint toggle (Screen 3−3)
0..250
55 sec
Alt ON: DD−DD hh:mm
Start time for toggle to alternative set of sepoints; weekday
from−to TT−TT, time hh:mm; shown only when internal set-
point toggle is activated (Screen 3−3)
↑
,
↓
,
(Mo−Su etc.)
or numbers
(hh:mm)
−−
Alt OFF: DD−DD hh:mm
End time for toggle to alternative set of sepoints; weekday
from−to TT−TT, time hh:mm; shown only when internal set-
point toggle is activated (Screen 3−3)
↑
,
↓
,
(Mo−Su etc.)
or numbers
(hh:mm)
−−
...
A total of 7 different ON and OFF toggle times can be defi-
ned. A toggle time will only be obeyed when a
matched
pair
of on and off times is set as a parameter.
Содержание UA 300 D
Страница 2: ......
Страница 6: ...Table of contents iv Version 2 03 27 Juni 2008 Notice ...
Страница 8: ...System Design of UA 300 D 2 Version 2 03 27 Juni 2008 Notice ...
Страница 40: ...Installation and Startup of UA 300 D 34 Version 2 03 27 Juni 2008 Notice ...
Страница 54: ...Operation of UA 300 D 48 Version 2 03 27 Juni 2008 Notice ...
Страница 100: ...Menu structure UA 300 D Controller type UR 141 94 Version 2 03 27 Juni 2008 Notice ...
Страница 108: ...Specifications of UA 300 D 102 Version 2 03 27 Juni 2008 Notice ...