Menu structure UA 300 D
Controller type UA 111 XP
77
E
2007 − ECKELMANN | BERLINER STRASSE 161 | 65205 WIESBADEN | FON +49(0)611 7103-0 | FAX 49(0)611 7103-133 | eckelmann.de
Version 2.03 27. Juni 2008
S
Screen 6−2−2 Temp. Display
DISPLAY
POS: XXXXX
Entry
Default
Offset
XX K
Offset for temperature display
−10..10
0K
S
Screen 6−2−3 Alarm Delay
ALARMDELAY
POS: XXXXX
Entry
Default
Sensor Fault
XX m
Sensor break alarm delay
0..30
15 min
High/Low Temp.
XX m
High/low temperature alarm delay
0..120
60 min
No Defrost
XX h
No defrost alarm delay
−−, 2..168
24 h
Selfholding
X
Alarm self−hold with manual alarm cancellation (YES) or
automatic cancellation on send (NO)
↑
,
↓
,
(Y/N)
N
S
Screen 6−2−4 230V Inputs
Only trained personnel should be allowed to change inputs, as changes may affect other functions.
230V INPUT
POS: XXXXX
Entry
Default
Input1:Comp.ON
Function of Digital Input 1 D11/D12 −
Load compressor (ON)
−
Comp.ON
Input2:SETP.TOG.
Function of Digital Input 2 D21/D22 −
Setpoint toggle
−
SETP.TOG.
Input3:Comp.OFF
Function of Digital Input 3 D31/D32 −
Unload compressor (OFF)
−
Comp.OFF
S
Screen 6−2−5 Sensor Type
Entry chooses between values. Checkmark indicates current setting.
SENSORS
POS: XXXXX
Entry
Default
L243
√
Temperature range −50 .. 50°C
Sensor type L243 is identical with K243
↵
√
K277
Temperature range −50 .. 50°C
↵
5K3A1
Temperature range 0 .. 100°C
↵
S
Screen 6−3 Cooling
COOLING
POS: XXXXX
Entry
Default
Cont Cool Mon.
XX m
Duration of forced interruption of cooling in continuous
running
−−, 0..15
0 min
Emergency Op.
XX %
In failure of required sensors, the solenoid is actuated
to adjust to the set opening in %
0..100
40%
Содержание UA 300 D
Страница 2: ......
Страница 6: ...Table of contents iv Version 2 03 27 Juni 2008 Notice ...
Страница 8: ...System Design of UA 300 D 2 Version 2 03 27 Juni 2008 Notice ...
Страница 40: ...Installation and Startup of UA 300 D 34 Version 2 03 27 Juni 2008 Notice ...
Страница 54: ...Operation of UA 300 D 48 Version 2 03 27 Juni 2008 Notice ...
Страница 100: ...Menu structure UA 300 D Controller type UR 141 94 Version 2 03 27 Juni 2008 Notice ...
Страница 108: ...Specifications of UA 300 D 102 Version 2 03 27 Juni 2008 Notice ...