Electrical data
UA 300 D xC
UA 300 D xS
Power supply
U
Nom
= 230 V AC, 200 − 265 V AC, 50/60 Hz
,
(+/− 3 Hz)
Rated power
10 VA
Leakage current over PE
max. 1 mA
Relay outputs
7 x 250 V AC, 6 A (4 N.O., 3 changeover), floating
Transverse voltage between outputs max. 400 V AC
Transistor outputs
2 x 24 V DC, pull down, switching transistor with internal current limiting to
50 mA for auxiliary alarm output
Lighting switch with external
connection option
−−−
1 double−pole, floating
Digital inputs
3 x 230 V AC, floating
Transverse voltage between inputs max. 400 V AC
Analog inputs
10 temperature sensors, two−wire type
for controller types K243/L243, K277, 5K3A1
(No shielding is required on sensor leads when installed exclusively inside the
refrigerated display case and when external interference (for example from paral-
lel power wires) is not to be expected)
Analog outputs
−−−
Fieldbus port
CAN bus, floating
Data ports
For BT 300 x Operator Interface
TTY (inverted)
Other ports
−−−
Archive memory
UA 300 D TC/AC: Archiving 1 year
UA 300 D TS/AS: Archiving 1 year
Monitoring function
Watchdog
Real−time clock
For UA 300 D TC/AC Battery−backed
Lithium cell CR 2450N 3 V
(shelf life 10 years)
Accuracy typically 8 min/yr at 25 °C
For UA 300 D TS/AS Battery−backed
Lithium cell CR 2450N 3 V
(shelf life 10 years)
Accuracy typically 8 min/yr at 25 °C
Temperature range
Transport: −20 °C ... +80 °C / Operation: 0 °C ... +50 °C
Temperature change
Transport: max. 20 K/h / Operation: max. 10 K/h
Relative humidity
(non−condensing)
Transport: 5 % ... 85 % / Operation: 5 % ... 85 %
Shock to DIN EN 60068−2−27
Transport and operation: 30 g
Vibration 10 − 150 Hz
to DIN EN 60068−2−6
Transport and operation: 2 g
Atmospheric pressure
Transport: 660 hPa ... 1060 hPa 7 Operation: 860 hPa ... 1060 hPa
Weight
ca. 750 g
ca. 950 g
Enclosure
IP20
CE conformity
Conforming to EU Directive
73/23/EEG (Low Voltage Directive)
89/336/EEG (EMC Directive)
Содержание UA 300 D
Страница 2: ......
Страница 6: ...Table of contents iv Version 2 03 27 Juni 2008 Notice ...
Страница 8: ...System Design of UA 300 D 2 Version 2 03 27 Juni 2008 Notice ...
Страница 40: ...Installation and Startup of UA 300 D 34 Version 2 03 27 Juni 2008 Notice ...
Страница 54: ...Operation of UA 300 D 48 Version 2 03 27 Juni 2008 Notice ...
Страница 100: ...Menu structure UA 300 D Controller type UR 141 94 Version 2 03 27 Juni 2008 Notice ...
Страница 108: ...Specifications of UA 300 D 102 Version 2 03 27 Juni 2008 Notice ...