Menu structure UA 300 D
Controller type UR 141
93
E
2007 − ECKELMANN | BERLINER STRASSE 161 | 65205 WIESBADEN | FON +49(0)611 7103-0 | FAX 49(0)611 7103-133 | eckelmann.de
Version 2.03 27. Juni 2008
S
Screen 6−2−4 230V Inputs
Only trained personnel should be allowed to change inputs, as changes may affect other functions.
230V INPUT
POS: XXXXX
Entry
Default
Input1:Door1
Function of Digital Input 1 D11/D12 −
Coldroom door 1 (closed/open)
−
Door1
Input2:SETP.TOG.
Function of Digital Input 2 D21/D22 −
Setpoint toggle
−
SETP.TOG.
Input3:Door2
Function of Digital Input 3 D31/D32 −
Coldroom door 2 (closed/open)
−
Door 2
S
Screen 6−2−5 Sensor Type
Entry chooses between values. Checkmark indicates current setting.
SENSORS
POS: XXXXX
Entry
Default
L243
√
Temperature range −50 .. 50°C
Sensor type L243 is identical with K243
↵
√
K277
Temperature range −50 .. 50°C
↵
5K3A1
Temperature range 0 .. 100°C
↵
S
Screen 6−3 Cooling
COOLING
POS: XXXXX
Entry
Default
Cont Cool Mon.
XX m
Duration of forced interruption of cooling in continuous
running
−−, 0..15
0 min
Emergency Op.
XX %
In failure of required sensors, the solenoid is actuated
to adjust to the set opening in %
0..100
10%
S
Screen 6−4 Language
LANGUAGE
POS: XXXXX
Entry
Default
Deutsch D
√
↵
√
English GB
↵
Francais F
↵
Cesky CZ
↵
Содержание UA 300 D
Страница 2: ......
Страница 6: ...Table of contents iv Version 2 03 27 Juni 2008 Notice ...
Страница 8: ...System Design of UA 300 D 2 Version 2 03 27 Juni 2008 Notice ...
Страница 40: ...Installation and Startup of UA 300 D 34 Version 2 03 27 Juni 2008 Notice ...
Страница 54: ...Operation of UA 300 D 48 Version 2 03 27 Juni 2008 Notice ...
Страница 100: ...Menu structure UA 300 D Controller type UR 141 94 Version 2 03 27 Juni 2008 Notice ...
Страница 108: ...Specifications of UA 300 D 102 Version 2 03 27 Juni 2008 Notice ...