Menu structure UA 300 D
Controller type UA 111 X
57
E
2007 − ECKELMANN | BERLINER STRASSE 161 | 65205 WIESBADEN | FON +49(0)611 7103-0 | FAX 49(0)611 7103-133 | eckelmann.de
Version 2.03 27. Juni 2008
S
Screen 2−4−4 Zone 2A Altern.
ALARM 2A
POS: XXXXX
Entry
Default
High Temp Setp
XX °C
High temperature setpoint at which
High Temperature
alarm is generated
−30..30
8 °C
Low Temp Setp.
XX K
Low temperature setpoint (difference below temperature
control setpoint) at which
Low Temperature
alarm is gene-
rated
−−, 0..6
2 K
S
Screen 2−5 Compressor
COMPRESSOR
POS: XXXXX
1 Setpoints
Continue to Screen 2−5−1, Setpoints
2 Setpoint toggle
Continue to Screen 2−5−2, Setpoint Toggle
S
Screen 2−5−1 Setpoints (Compressor)
COMPRESSOR
POS: XXXXX
Entry
Default
Enable C1
XXX
Enable Compressor 1
↑
,
↓
,
(ON/OFF)
ON
Enable C2
xxx
Enable Compressor 2
↑
,
↓
,
(ON/OFF)
ON
Delay C1 ON
xxx s
Start delay Compressor 1
0..250
60s
Delay C2 ON
xxx s
Start delay Compressor 2
0..250
180s
Delay C1 OFF
xxx s
Stop delay Compressor 1
0..250
60s
Delay C2 OFF
xxx s
Stop delay Compressor 2
0..250
15s
S
Screen 2−5−2 Setpoint toggle (Compressor)
Compr. alt.
POS: XXXXX
Entry
Default
Delay C1 ON
xxx s
Start delay Compressor 1
0..250
120s
Delay C2 ON
xxx s
Start delay Compressor 2
0..250
240s
Delay C1 OFF
xxx s
Stop delay Compressor 1
0..250
75s
Delay C2 OFF
xxx s
Stop delay Compressor 2
0..250
15s
Содержание UA 300 D
Страница 2: ......
Страница 6: ...Table of contents iv Version 2 03 27 Juni 2008 Notice ...
Страница 8: ...System Design of UA 300 D 2 Version 2 03 27 Juni 2008 Notice ...
Страница 40: ...Installation and Startup of UA 300 D 34 Version 2 03 27 Juni 2008 Notice ...
Страница 54: ...Operation of UA 300 D 48 Version 2 03 27 Juni 2008 Notice ...
Страница 100: ...Menu structure UA 300 D Controller type UR 141 94 Version 2 03 27 Juni 2008 Notice ...
Страница 108: ...Specifications of UA 300 D 102 Version 2 03 27 Juni 2008 Notice ...