Alarms and Messages of UA 300 D
No.
Message
Cause
Correction
Hardware faults
4
EEPROM Fault
Component for saving configuration defective or confi-
guration data in EEPROM implausible.
Save parameters in LDSWin software,
perform first start if necessary and load
parameters from LDSWin.
Contact Service Organization if fault re-
curs
6
Flash Fault
Flash memory module defective.
Please contact Service Organization −
Replace device
8
RTC Fault
Real−time clock defective.
Please contact Service Organization −
Replace device
10
Battery Voltage
Real−time clock and RAM backup battery dead
Replace battery (see Section 4 − Installa-
tion and Startup)
Messages
50
First Start
Controller performed first start (basic settings loaded).
−
51
Power Failure
Controller performed restart after power outage.
−
120
Low Temp. Zone 1
Temperature below lower limit on monitored control
sensors of Zone 1.
Check parameter setting, sensors, sy-
stem
121
Low Temp. Zone 2
Temperature below lower limit on monitored control
sensors of Zone 2.
Check parameter setting, sensors, sy-
stem
122
High Temp. Zone 1
Temperature above upper limit on monitored control
sensors of Zone 1.
Check parameter setting, sensors, sy-
stem
123
High Temp. Zone 2
Temperature above upper limit on monitored control
sensors of Zone 2.
Check parameter setting, sensors, sy-
stem
124
Door1 Open
Coldroom door 1 open beyond alarm interval 1; col-
droom controller UR 141 only.
Close door, check door switch or connec-
ting cable
125
No Defrost
Defrosting not performed within alarm interval.
Check parameter settings: Internal/exter-
nal defrost timer, defrost times, alarm de-
lay
126
Timer−Term. Defrost
Defrosting terminated by safe defrost time. Heater
defective, contactor defective, evaporator iced.
Defrosting is always terminated by safe de-
frost time on controllers working with off−
cycle defrosting. Alarm may be displayed at
intervals on these controllers without an ac-
tual fault occurring.
Check parameter settings: Defrost termi-
nation temperature too low,
check evaporator for icing, check location
of defrost sensor,
set defrost termination temperature
to −−"
127
Manual Shutoff
Manual Shutdown
digital input actuated.
−
137
Door2 Open
Coldroom door 2 open beyond alarm interval; col-
droom controller UR 141 only.
Close door, check door switch or connec-
ting cable
Содержание UA 300 D
Страница 2: ......
Страница 6: ...Table of contents iv Version 2 03 27 Juni 2008 Notice ...
Страница 8: ...System Design of UA 300 D 2 Version 2 03 27 Juni 2008 Notice ...
Страница 40: ...Installation and Startup of UA 300 D 34 Version 2 03 27 Juni 2008 Notice ...
Страница 54: ...Operation of UA 300 D 48 Version 2 03 27 Juni 2008 Notice ...
Страница 100: ...Menu structure UA 300 D Controller type UR 141 94 Version 2 03 27 Juni 2008 Notice ...
Страница 108: ...Specifications of UA 300 D 102 Version 2 03 27 Juni 2008 Notice ...