Function of UA 300 D
7
E
2007 − ECKELMANN | BERLINER STRASSE 161 | 65205 WIESBADEN | FON +49(0)611 7103-0 | FAX 49(0)611 7103-133 | eckelmann.de
Version 2.03 27. Juni 2008
3.2.1
Cooling (solenoid valve)
Twin control by majority (UA 111 X Zone 1 only)
With the UA 111 X controller, the compressors are controlled as a function of the supply air sensors for the first
temperature zone (see description below, Section 3.2.2.1). The cooling relay energizes as a function of the com-
pressors whenever a minimum of one compressor is started.
Majority explained (varying with version):
Version 1.09 and lower
Above Version 1.09
Even number of supply air sensors
1): Half supply air s 1
2): Half supply air sensors
Odd number of supply air sensors
3): Half supply air sensors rounded up
Example:
1):
Total 6 supply air sensors:
4 or more sensors = Majority
2):
Total 6 supply air sensors:
3 or more sensors = Majority
3):
Total 5 supply air sensors:
3 or more sensors = Majority
On−off control by all connected supply air sensors (UA 111 XP Zone 1 only)
Control is made by all supply air sensors of the first zone. The cooling relay de−energizes when temperature re-
aches the setpoint (switch−off value) on all connected supply air sensors or the setpoint for antifreeze protection
on one supply air sensor. The cooling relay re−energizes when temperature has passed the switching differential
on the majority of the connected supply air sensors (e.g. 3 out of 5).
On−off control (UA 111 X Zone 2, UA 111 XP Zone 2 and UR 141 only)
Control is made by one temperature sensor (supply air for UA 111, room air for UR 141). The cooling relay de−
energizes when temperature reaches the setpoint (switch−off value) on the respective temperature sensor. The
cooling relay re−energizes with the set hysteresis.
Cooling relay operation
Operation of the cooling relay takes place according to the cooling safety requirements and is governed by the
controller type selected:
UA 111 X, UA 111 XP, UR 141 Zone 2 (NT): N.O. control, i.e. cooling is OFF when case controller is
de−energized.
UR 141 Zone 1 (LT): N.C. control, i.e. cooling is ON when case controller is de−energized.
Содержание UA 300 D
Страница 2: ......
Страница 6: ...Table of contents iv Version 2 03 27 Juni 2008 Notice ...
Страница 8: ...System Design of UA 300 D 2 Version 2 03 27 Juni 2008 Notice ...
Страница 40: ...Installation and Startup of UA 300 D 34 Version 2 03 27 Juni 2008 Notice ...
Страница 54: ...Operation of UA 300 D 48 Version 2 03 27 Juni 2008 Notice ...
Страница 100: ...Menu structure UA 300 D Controller type UR 141 94 Version 2 03 27 Juni 2008 Notice ...
Страница 108: ...Specifications of UA 300 D 102 Version 2 03 27 Juni 2008 Notice ...