Menu structure UA 300 D
Controller type UA 111 X
53
E
2007 − ECKELMANN | BERLINER STRASSE 161 | 65205 WIESBADEN | FON +49(0)611 7103-0 | FAX 49(0)611 7103-133 | eckelmann.de
Version 2.03 27. Juni 2008
S
Screen 1−5 Alarm
ALARM
POS:XXXXX
Alarm Relay
XXX
Current ON/OFF status of alarm output Terminal 15/16/18
Hi Temp Setp.1
XX °C
High temperature setpoint Zone 1
Lo Temp Setp.1
XX K
Low temperature setpoint Zone 1
Hi Temp Setp.2
XX °C
High temperature setpoint Zone 2; shown only when two−zone operation is set
(Screen 6−1)
Lo Temp Setp.2
XX K
Low temperature setpoint Zone 2; shown only when two−zone operation is set
(Screen 6−1)
S
Screen 1−6 Compressor
COMPRESSOR
POS:XXXXX
Compressor 1
XXX
Current ON/OFF status of Compressor 1 output Terminals 43/44
Compressor 2
XXX
Current ON/OFF status of Compressor 2 output Terminals 53/54
S
Screen 1−7 Cooling Zone 2
COOLING 2
POS:XXXXX
Cooling
XXX
Current ON/OFF status of cooling Zone 2 Terminals35/36/38
Run Time
XX %
Cooling relay on time during last day (00:00 − 24:00 hours)
Starts
X
Cooling relay actuations during last day
Setpoint R2.8
XXX °C
Supply air temperature setpoint for comparison
Hystersis R2.8
XXX K
Supply air temperature hysteresis setpoint
S
Screen 1−8 Defrost Zone 2
DEFROST 2
POS:XXXXX
Defrost 2
XXX
Current ON/OFF status of defrosting Zone 2
Def. End. Tmp.
XXX °C
Defrost termination temperature for comparison
Last DefrstWe
XX hh:mm
Day and time of last defrost cycle started
Содержание UA 300 D
Страница 2: ......
Страница 6: ...Table of contents iv Version 2 03 27 Juni 2008 Notice ...
Страница 8: ...System Design of UA 300 D 2 Version 2 03 27 Juni 2008 Notice ...
Страница 40: ...Installation and Startup of UA 300 D 34 Version 2 03 27 Juni 2008 Notice ...
Страница 54: ...Operation of UA 300 D 48 Version 2 03 27 Juni 2008 Notice ...
Страница 100: ...Menu structure UA 300 D Controller type UR 141 94 Version 2 03 27 Juni 2008 Notice ...
Страница 108: ...Specifications of UA 300 D 102 Version 2 03 27 Juni 2008 Notice ...