EPX400-A20CU – Manual
Page 34 / 62
Response type
8.4.1.1.
Instant
— violating the input will result in an immediate alarm if the system is
armed.
Delayed
— delayed input switches on associated output, ie. generates alarm,
after expiry of Entry time, but only when partition to which input belongs will not
be disarmed before Entry time period.
Mode
8.4.1.2.
The parameter describes input configuration and stable state of input. Any change of
that state causes alarm message to be sent. The following configuration types are
available: NO / NC / EOL-NO / EOL-NC / DEOL-NO / DEOL-NC. NC type input must
be closed for the whole time. Line interruption causes its induction. NO type input
remains open. It activates when closed. EOL and DEOL (single end-of-line resistor
and double end-of-line resistor) differ with 1 or 2 resistors allowing distinguishing
alarm from sabotage. Electric diagrams for all configuration types were described in
chapter 3.4. Input configuration.
Sensitivity
8.4.1.3.
This parameter means minimum time for change maintenance at input so that it
would be detected by communicator. Default setting is 400ms.
Interlocking – After number of violations
8.4.1.4.
With this option you can lock any input of connector, and as a result condition
changes on this input will be ignored and will not be reported to monitoring station.
Selecting this option will result in displaying an additional items
Violations
with a
slider for setting a lock for input after a specific number of violations (input state
change) from 1 to 100,
and
Duration
where you have to set duration time for lock of
the input.