SM65 Supervisory Module Handbook
12
Copyright © 2004-2009 Eaton Corporation. All Rights Reserved.
IPN 997-00012-35E December 2009
Viewing Alarms and System Status Messages (Status View Mode)
Status View Mode displays alarm and status messages.
<
indicates an Urgent/Critical alarm
=
indicates a Non-urgent alarm
Refer to SM65 Keypad and Display on page
for details about the other display indicators.
Rules for displaying alarms and system status
•
Active alarms are always displayed before status messages.
•
Urgent/Critical alarms are always displayed before Non-urgent alarms.
•
Alarms with their severity set to
None
are not displayed.
Important note about Rectifier (Rect) Comms Lost alarm
If a rectifier is removed, a
Rect Comms Lost
alarm is displayed after 10 seconds. If this alarm is
cleared within the configurable
Alarm Recognition Time
(default is 10 seconds) an external
alarm will not be generated.
Rects Comms Lost is remotely displayed as Multiple Rectifier Comms Lost.
►
To view and clear alarms
1
From Main Display Mode, press
:
to enter Status View Mode.
2
Press
6
to scroll through the list of alarms.
3
Press
8
to clear the alarms. (Only three alarms can be cleared – Rect Comms Lost, Rects
Comms Lost and Battery Test Fail.)
4
Press
9
to return to Main Display Mode.
See Alarm Descriptions on page
for a comprehensive list of alarms (that can be displayed in
Status View Mode).
►
To view alarm additional text (Requires SM65 v4 or later)
1
From Main Display Mode, press
:
to enter Status View Mode.
2
Press
:
to view additional text for the first alarm.
Press
6
or
7
to scroll the text if it is too large to fit on one screen.
3
Press
:
to view additional text for the next alarm(s).
4
Press
9
to return to Status View Mode.
5
Press
9
to return to Main Display Mode.