Step 2 – Setup first (or only) CBC
1
Connect a null modem cable from the RS232 port of the CBC to the serial
port of the PC.
2
From the
DCTools
CellSure Battery Monitoring System Summary (Home)
screen, go to
Configuration
>
Communications
and check the following
settings:
•
RCP address:
150 (default)
•
Baud Rate Port RS485: B 19200 Baud
•
Protocol Port RS485:
Rcp
Step 3 – Setup additional CBCs (if fitted)
As required, repeat the previous step for the second, third and fourth CBCs,
except set the RCP addresses to 151, 152 and 153 respectively.
Step 4 – Configure the SM65 to operate with CellSure
1
From the
DCTools
System Summary (Home) screen, go
Configuration
>
External I/O
to display the External Input/Output Communications
view.
2
Scroll down to CellSure Battery Controller (CBC) and set
Fitted
to
True
.
3
From the
DCTools
System Summary (Home) screen, go to
CBC
to display
the CellSure Battery Controller (CBC) Summary view.
4
Set
Number of CBCs
as appropriate.
5
To allow the SM65 to use the average string temperature from the
CellSure
battery temperature sensor (instead of its own battery
temperature input) click
D
next to
Batt Temp Source
and select
CBC
Average
from the list.
Step 5 – Configure the DCTools / PowerManagerII communications settings
Create a new connection for CellSure in DCTools and/or PowerManagerII
with the following settings. Then check that DCTools or PowerManagerII
communicates correctly.
Comms
Enabled :
True
Protocol
:
S3P
Passthrough
Connect Using
:
Local Network
S3P Address
:
1:150 (Note 1)
Server IP Address
:
Enter the SM65 IP Address
Server
Port
:
14000
Telnet
:
Cleared