CellSure Status Messages
Battery Cap Low
(Battery Capacity Low)
The battery capacity is below the set threshold limit.
Bat Res Chge Low
(Battery Reserve Charge
Low Discharge)
Only a limited amount of backup capacity remains for the entire battery
system. A warning to find an alternative power source if required.
Bat Res Time Low
(Battery Reserve Time Low
Discharge)
Only a limited amount of backup time remains for the entire battery system.
A warning to find an alternative power source if required.
Battery SOH Fail
(Battery State of Health
Fail)
The battery may need to be replaced.
Battery SOH Low
(Battery State of Health
Low)
The condition of the battery is poor and requires either a boost recharge or
replacing.
Battery SOH Poor
(Battery State of Health
Poor)
A battery string is in poor condition and may need replacing soon.
Bloc Cap Low
(Bloc Capacity Low)
The capacity of an individual monobloc is below the set threshold limit.
Capacity alarms are generated after completing a valid discharge. A valid
discharge is defined as a completed discharge within a specific discharge rate
and temperature range down to or beyond a partial discharge depth (full
discharge or partial discharge depth). The capacity is calculated according to
the built-in algorithm. By detecting low capacity in blocs, these poor-
performing blocs can be removed before healthy blocs are affected.
Bloc Disch End V
(Bloc End Voltage
Discharge)
A full discharge (down to the specified end voltage) has been completed.
Charge Volt Div
(Bloc Voltage Divergence
Charge)
The voltage of an individual monobloc differs significantly from the average
monobloc voltage of that string for the alarm time limit set. Used to identify
blocs that do not regain their expected charge. These blocs may not be
healthy and may fail soon.
Dischge Volt Div
(Bloc Voltage Divergence
Discharge)
The voltage of an individual monobloc is significantly below the maximum
monobloc voltage of that string. Used to identify blocs that drop away
during a discharge, indicating reduced capacity of that monobloc and the
need for replacement. Several of these alarms generated during a discharge
may indicate replacement of the whole string.
Bloc Float V Div
(Bloc Voltage Divergence
Float)
The voltage of an individual monobloc differs significantly from the average
monobloc voltage of that string for the alarm time limit set. Used to identify
blocs that do not regain their expected charge while on float. After further
discharges, this information is useful to determine which blocs need to be
replaced.
Bloc V Failure
(Bloc Voltage Failure)
A monobloc in a string has failed. Provides a warning before imminent loss
of string communication occurs in C2M sensor modules.