Alarm Descriptions
AC Fail
All rectifiers are reporting loss of AC power.
AC Frequency*
The frequency of the AC supply is outside the configurable AC frequency band,
defined as: Nominal AC Frequency ± AC Frequency Threshold
AC Phase1 (or 2 or 3)*
The AC voltage of Phase 1, 2 or 3 is outside the configurable AC phase voltage
band, defined as: Nominal AC Voltage (V) ± AC Fail Urgent Threshold (%)
AC Phase1 (or 2 or 3)
Volt*
The AC voltage of Phase 1, 2 or 3 is outside the configurable AC phase voltage
band, defined as: Nominal AC Voltage (V) ± AC Fail Non Urgent Threshold (%)
ACD Fan Fail
The AC Distribution cooling system or fan controller has failed.
Aux Temp Fail
The auxiliary temperature sensor is incorrectly configured, disconnected, not
fitted or faulty.
Batt Current Limit**
Battery Current Limit (BCL) is active.
Batt Fuse Fail
A battery fuse has blown or a battery MCB has operated.
Battery Test Active**
A Battery Test is active.
Batt Test Fail**
The batteries do not have the required capacity or are not fully charged.
Cabinet Fan Failed
A cabinet fan (connected to XS3 pin 2, when XS3 pin 2 function is set to Cabinet
Fan Fail) has failed.
CBC Comms Failed
The
CellSure Fitted
configuration file item is enabled but the CellSure Battery
Controller (CBC) is not fitted or not registered by the SM65.
CBC Fail
A CBC connected to the SM65 has failed.
CBC Non Urgent
Non-urgent CellSure alarm(s) active. Only occurs if CellSure is fitted. See
Interfacing the SM65 with CellSure on page
for details.
CBC Urgent
Urgent CellSure alarm(s) active. Only occurs if CellSure is fitted. See Interfacing
the SM65 with CellSure on page
for details.
Config Error
Configuration file is missing or invalid, installed rectifiers have different
nominal output voltages, or the number of cells in a battery string entered in the
configuration file does not match the nominal rectifier output voltage. Refer to
Troubleshooting on page
for more information.
Equalize Active**
The Equalize function is active.
Fast Charge Active**
The Fast Charge function is active.
Generator Fail
The Generator Start Alarm has been active for the Generator Start Alarm
Recognition Period but the AC supply is still not present.
Generator Start
Uses the Fast Charge and/or Equalize control function to start a generator. The
generator is started with the batteries partially discharged and switched off
when the batteries are fully recharged.
High Aux Temp
The auxiliary temperature sensor is at a temperature above the high temperature
set point.
High Batt Temp
The battery temperature sensor is at a temperature above the high temperature
set point. This alarm indicates either thermal runaway of the batteries or that the
batteries are operating at a temperature that may cause reduced battery life.
High Float
The float voltage is above its normal range.