Setup and Configuration
Copyright © 2004-2009 Eaton Corporation. All Rights Reserved.
IPN 997-00012-35E December 2009
27
Notes:
1
The format is: (SM65 S3P Address : CBC RCP Address). Change the CBC RCP address as
required (150 - 153). Refer to Steps 2-3 for further information.
2
DCTools can not connect to multiple CBCs simultaneously. To connect to a second CBC,
close the connection to the first and create a new connection to the second CBC.
Interfacing the SM65 with SiteSure
SiteSure
is a suite of add-on modules to provide control and monitoring of a wide range of
external devices. It uses the communications capability of an Eaton DC power system to
monitor and control security, air conditioning, engine alternators and other building services,
or sense DC currents for load metering.
SiteSure
modules can be added as required to
provide the number of inputs and outputs needed for a particular application.
Four
SiteSure
modules are available:
•
SiteSureGP
– collects site-specific status information via configurable analog and digital
inputs
•
SiteSureDI
– provides additional configurable digital inputs
•
SiteSureDO
– provides configurable relay outputs for local control or alarm indication
•
Current Input Module (IOM-CS)
– provides configurable current sensor inputs
►
To interface SiteSure modules to an SM65:
1
Connect the
SiteSure
master modules (SiteSureGP and IOM-CS) as shown in the
following diagram.
2
Use
DCTools
(Configuration > External I/O) to check the
SiteSure
master module
addresses.
3
If more than one SiteSure master module is to be connected then change the addresses as
follows:
•
Connect one module at a time to the SM65.
•
Double-click in the
Change module number to:
column to set the new module
number.
4
Configure the external analog inputs, digital inputs and digital outputs.
For SiteSure installation and configuration details refer to the SiteSure Installation and
Configuration Guide. See Related Information on page
.
Содержание SM65