Maintenance
Copyright © 2004-2009 Eaton Corporation. All Rights Reserved.
IPN 997-00012-35E December 2009
41
Step 6 - Power up the new SM65
1
Connect the power cable to the SM65 connector XS8.
2
Check that the green
B
Power On LED is on. If not, consult
Troubleshooting on page
Step 7 - Download the appropriate configuration file into the new SM65
1
Connect a null modem cable from the front RS232 serial port of the SM65 to
the serial port of the PC.
2
Start
DCTools
. If required, press F1 for
DCTools
online help.
3
On the
File
menu of
DCTools
, click
ICE Backup/Restore
. The Target
Configuration Database Backup Wizard dialog is then displayed.
4
Select
Restore
then click
Next
.
5
Browse to the configuration file and click
Next
. Once the restore operation
has been successfully completed, click
Finish
.
6
Check through the loaded configuration file in
DCTools
and make any
required changes.
7
If you make any changes, save the configuration file with a new file name.
Step 8 - Connect the remaining cables to the SM65
Step 9 - Check that the new SM65 operates as intended
1
Check all control functions, alarms and current measurement.
2
Check the power system identification parameters and communications
settings.
3
Change the configuration file as required to ensure that the SM65 operates
as intended.
4
Check that all rectifiers are communicating and that the SM65 has registered
all rectifiers. This can be checked from the LCD display by viewing the
individual rectifier currents in Main Display Mode. See supervisory module
menu structure on inside front cover or Viewing System Values on page
for details.