CANopen External Communication Cards
POWERXL SERIES VFD
MN040010EN—June 2018 www.eaton.com
Process data (PDO)
The real time data transfer is performed by means of using the “Process Data Objects.” The transfer of PDOs is performed
with no protocol overhead. The Process Data is time-critical data used for control of the drive and monitor status.
Table 137. Process data (PDO)
RxPDO1
Header
Data
ID
RTR
LEN
1
2
3
4
5
6
7
8
0x201
0
4
Control Word
Target Velocity
TxPDO1
Header
Data
ID
RTR
LEN
1
2
3
4
5
6
7
8
0x181
0
4
Status Word
Control effort
RxPDO2
Header
Data
ID
RTR
LEN
1
2
3
4
5
6
7
8
0x301
0
8
Motor Nominal Percentage
Velocity deceleration delta speed
Velocity deceleration delta time
TxPDO2
Header
Data
ID
RTR
LEN
1
2
3
4
5
6
7
8
0x281
0
8
Motor Actual Percentage
Torque %
Current %
Fault Code
RxPDO3
Header
Data
ID
RTR
LEN
1
2
3
4
5
6
7
8
0x401
0
8
Fixed control word
Speed reference Percentage
FB_Process_data_in1
FB_Process_data_in2
TxPDO3
Header
Data
ID
RTR
LEN
1
2
3
4
5
6
7
8
0x381
0
8
Fixed status word
Actual speed Percentage
FB_Process_data_out1
FB_Process_data_out2
RxPDO4
Header
Data
ID
RTR
LEN
1
2
3
4
5
6
7
8
0x501
0
8
FB_Process_data_in3
FB_Process_data_in4
FB_Process_data_in5
FB_Process_data_in6
TxPDO4
Header
Data
ID
RTR
LEN
1
2
3
4
5
6
7
8
0x481
0
8
FB_Process_data_out3
FB_Process_data_out4
FB_Process_data_out5
FB_Process_data_out6
Some drive actual values can be monitored by using a Process Data Object 2 (rx).
Addressing of the data in these addresses is based off the following scheme this is in a hex:
RxPDO1 = 0x200 + node ID(hex)
RxPDO2 = 0x300 + node ID(hex)
RxPDO3 = 0x400 + node ID(hex)
RxPDO4 = 0x500 + node ID(hex)
TxPDO1 = 0x180 + node ID(hex)
TxPDO2 = 0x280 + node ID(hex)
TxPDO3 = 0x380 + node ID(hex)
TxPDO4 = 0x480 + node ID(hex)
ote:
N
PDO1 and PDO2 should be used when in “Drive Mode” and PDO3 and PDO4 used in “Bypass Mode”.
vl_actual percentage
Motor Speed. Scaled with percentage function
_torque_percentage
Calculated torque. Scaled in 0.0%–100% (0–1000)
_current_percentage
Measured motor current. (1 = 0.01 A)
fault_code
Shows the drive fault code (= 0, if no fault active)
Содержание PowerXL Series
Страница 1: ...Effective June 2018 Supersedes October 2017 Communication manual PowerXL Series VFD...
Страница 24: ...xxiv S curit du moteur et de l quipement POWERXL SERIES VFD MN040010EN June 2018 www eaton com...
Страница 149: ...125 Hardware speci cation POWERXL SERIES VFD MN040010EN June 2018 www eaton com Figure 53 DeviceNet parameters...
Страница 202: ...178 Commissioning POWERXL SERIES VFD MN040010EN June 2018 www eaton com Fault tracing Figure 74 Fault tracing...
Страница 253: ...229 Appendix D PowerXL Recommended Secure Hardening Guidelines POWERXL SERIES VFD MN040010EN June 2018 www eaton com...
Страница 254: ...230 Hardware speci cation POWERXL SERIES VFD MN040010EN June 2018 www eaton com...
Страница 255: ...231 Hardware speci cation POWERXL SERIES VFD MN040010EN June 2018 www eaton com...