96
PROFIBUS-DP External Communication Cards
POWERXL SERIES VFD
MN040010EN—June 2018 www.eaton.com
DPV1 acyclic communication
Base model parameter access, whose structure is
defined in the PROFIdrive profile 4.2, is always used
for communicating the writing/reading parameters for
PROFIdrive drives.
Under this arrangement, parameters access always consists
of two elements. Under this arrangement, parameter
access always consists of two elements.
Write request (“Write data set “)
Read request (“Read data set”)
Write request or Request can be send via DPV1 master
class 1 or master class 2.
The DP V1 command/response part is used for the standard
DP V1 read/Write on the Slot 0, Index47 data block.
Parameter requests and parameter responses
A parameter consists of three segments.
Request header
ID for the request and number of parameters which are
accessed. Multi-Axis and Modular drives, Addressing of
one DO.
Parameter address
Addressing of a parameter. If parameters are accessed,
there are correspondingly many parameter addresses but
can only be accessed on a single case. The parameter
address appears only in the request, not in the response.
Parameter value. Per addressed parameter, there is a
segment for the parameter values. Depending on the
request ID, parameter values appear only either in the
request or in the reply.
Words and double words
The following telegram contents are displayed in words (a
word or 2 bytes per line). Words or double words will have
the most significant byte being transmitted first (big endian).
Table 114. Words and Double Words
Word
Byte 1
Byte 2
Double Word
Byte 1
Byte 2
Byte 3
Byte 4
According to the Base Model Parameter access the structure of the parameter
request and parameter response as shown in
Table 116
and
Table 117
.
Table 115. Base mode parameter request
Block definition
Byte n
Byte n +1
n
Request Header
Request reference
Request ID 0
0
Axis-No. / DO-ID
No. of parameters = i
2
1st Parameter address
Attribute
No. of elements
4
Parameter number (PNU)
Subindex
ith Parameter address
...
4 + 6 × (i-1)
1st Parameter value(s)
(only for requst
“change parameter”)
Format
No. of values
4 + 6 × i
Value
...
ith Parameter value
...
4 + 6 × i + ... +
(Format_n x Qty_n)
Table 116. Base model response
Block definition
Byte n
Byte n +1
n
Response header
Request Ref. mirrored
Response ID
0
Axis-No. / DO-ID mirrored
No. of parameters = i
2
1st Parameter Value (s) (only after
request “Request”)
Format
No.of values
4
Values or error values
...
ith Parameter values
...
4 +... + (Format_n × Qty_n)
Содержание PowerXL Series
Страница 1: ...Effective June 2018 Supersedes October 2017 Communication manual PowerXL Series VFD...
Страница 24: ...xxiv S curit du moteur et de l quipement POWERXL SERIES VFD MN040010EN June 2018 www eaton com...
Страница 149: ...125 Hardware speci cation POWERXL SERIES VFD MN040010EN June 2018 www eaton com Figure 53 DeviceNet parameters...
Страница 202: ...178 Commissioning POWERXL SERIES VFD MN040010EN June 2018 www eaton com Fault tracing Figure 74 Fault tracing...
Страница 253: ...229 Appendix D PowerXL Recommended Secure Hardening Guidelines POWERXL SERIES VFD MN040010EN June 2018 www eaton com...
Страница 254: ...230 Hardware speci cation POWERXL SERIES VFD MN040010EN June 2018 www eaton com...
Страница 255: ...231 Hardware speci cation POWERXL SERIES VFD MN040010EN June 2018 www eaton com...