Analog value object instance summary
The following table summarizes the Analog Value Objects supported.
Table 93. Analog value object instance summary
Instance ID
Object name
Description
Units
Preset value access
AV0
Speed Reference
Motor speed reference from network
Percent
C
AV1
Current Limit
Current Limit
Amps
W
AV2
Min Frequency
Minimum Frequency
Hz
W
AV3
Maximum Frequency
Maximum Frequency
Hz
W
AV4
Accel Time 1
Acceleration Time
seconds
W
AV5
Decel Time 1
Deceleration Time
seconds
W
AV6
AnyParam ID
Parameter ID number to be accessed
No Units
W
AV7
AnyParam Value
Value of parameter defined by AV6
No Units
W
AV8
Process Data In 1
Fieldbus Process Data In 1
NA
C
AV9
Process Data In 2
Fieldbus Process Data In 2
NA
C
AV10
Process Data In 3
Fieldbus Process Data In 3
NA
C
AV11
Process Data In 4
Fieldbus Process Data In 4
NA
C
AV12
Process Data In 5
Fieldbus Process Data In 5
NA
C
AV13
Process Data In 6
Fieldbus Process Data In 6
NA
C
AV14
Process Data In 7
Fieldbus Process Data In 7
NA
C
AV15
Process Data In 8
Fieldbus Process Data In 8
NA
C
ote:
N
For Present Value Access Types, R = Read-only, W = Writeable, C = Commandable.
Commandable values support priority arrays and relinquish defaults.
Table 94. Analog Input object instance summary
Instance ID
Object name
Description
Units
Preset value access
AI0
Frequency Setpoint
Frequency Setpoint
Hz
R
AI1
Output Frequency
Output Frequency
Hz
R
AI2
Motor Speed
Motor Speed
Rpm
R
AI3
Motor Load
Motor Load
Percent
R
AI4
Kilowatt Hours total
Kilowatt Hour Counter (Total) scaled by 1000
KWh
R
AI5
Motor Current
Motor Current
Amps
R
AI6
DC link Voltage
DC link Voltage
Volts
R
AI7
Motor Voltage
Motor Voltage
Volts
R
AI8
Unit Temperature
Heatsink Temperature
°C
R
AI9
Motor Torque
In % of motor nominal Torque
Percent
R
AI10
Operating Days
Operating Days (resettable)
Day
R
AI11
Operating Hours
Operating Hours (resettable)
Hour
R
AI12
Motor Temperature
Motor Temperature
Percent
R
AI13
Analog Input 1
Analog Input 1
Volts
R
AI14
Analog Input 2
Analog Input 2
Volts
R
AI15
Analog Output 1
Analog Output 1
Volts
R
AI16
Analog Output 2
Analog Output 2
Volts
R
AI17
Kilowatt Instantaneous
Kilowatt Instantaneous
KW
R
ote:
N
For Present Value Access Types, R = Read-only.
Содержание PowerXL Series
Страница 1: ...Effective June 2018 Supersedes October 2017 Communication manual PowerXL Series VFD...
Страница 24: ...xxiv S curit du moteur et de l quipement POWERXL SERIES VFD MN040010EN June 2018 www eaton com...
Страница 149: ...125 Hardware speci cation POWERXL SERIES VFD MN040010EN June 2018 www eaton com Figure 53 DeviceNet parameters...
Страница 202: ...178 Commissioning POWERXL SERIES VFD MN040010EN June 2018 www eaton com Fault tracing Figure 74 Fault tracing...
Страница 253: ...229 Appendix D PowerXL Recommended Secure Hardening Guidelines POWERXL SERIES VFD MN040010EN June 2018 www eaton com...
Страница 254: ...230 Hardware speci cation POWERXL SERIES VFD MN040010EN June 2018 www eaton com...
Страница 255: ...231 Hardware speci cation POWERXL SERIES VFD MN040010EN June 2018 www eaton com...