33
EtherNet/IP On-Board Communications
POWERXL SERIES VFD
MN040010EN—June 2018 www.eaton.com
Figure 21. Module and network status
Module Status
Network Status
Module status indications
Represents the state of the drive.
Table 58. Module status LED description
Indicator state
Summary
Meaning
Steady off
No power
No power is supplied to the PowerXL.
Steady green
Device operational
Drive is operating correctly.
Flashing green
Standby
Drive has not been configured.
Flashing red
Minor fault
Drive has detected a recoverable minor fault.
Note. An incorrect or inconsistent configuration would be considered a minor fault.
Also check that on clearing the fault, it turns off.
Steady red
Major fault
Drive has detected a non-recoverable major fault.
Flashing green/red
Self-test
Drive is performing its power on self test.
Network status indications
Represents the state of the Ethernet port network interface.
Table 59. Network status LED description
Indicator State
Summary
Meaning
Steady off
Not powered, no IP address
Drive is powered off, or is powered on but with no IP address configured (Interface
Configuration attribute of the TCP/IP Interface Object).
Flashing green
No connections
An IP address is configured, but no CIP connections are established, and an Exclusive Owner
connection has not timed out.
Steady green
Connected
At least one CIP connection (any transport class) is established, and an
Exclusive Owner connection has not timed out.
Flashing red
Connection timeout
Drive is powered on and an exclusive Owner connection has timed out. It returns to steady
green only when all timed out Exclusive Owner connections are established.
Steady red
Duplicate IP address
Drive has detected a Duplicate IP.
Flashing green/red
Self-test
Drive is performing its power on self test.
Flash rate is 1 flash per second.
Содержание PowerXL Series
Страница 1: ...Effective June 2018 Supersedes October 2017 Communication manual PowerXL Series VFD...
Страница 24: ...xxiv S curit du moteur et de l quipement POWERXL SERIES VFD MN040010EN June 2018 www eaton com...
Страница 149: ...125 Hardware speci cation POWERXL SERIES VFD MN040010EN June 2018 www eaton com Figure 53 DeviceNet parameters...
Страница 202: ...178 Commissioning POWERXL SERIES VFD MN040010EN June 2018 www eaton com Fault tracing Figure 74 Fault tracing...
Страница 253: ...229 Appendix D PowerXL Recommended Secure Hardening Guidelines POWERXL SERIES VFD MN040010EN June 2018 www eaton com...
Страница 254: ...230 Hardware speci cation POWERXL SERIES VFD MN040010EN June 2018 www eaton com...
Страница 255: ...231 Hardware speci cation POWERXL SERIES VFD MN040010EN June 2018 www eaton com...