18
Modbus TCP On-Board communications
POWERXL SERIES VFD
MN040010EN—June 2018 www.eaton.com
Commissioning
Connections and wiring
The Ethernet port supports 10/100 Mb speeds in both
full and half-duplex modes. The boards must be connected to
the Ethernet network with a shielded CAT-5e cable.
A crossover cable (at least CAT-5e cable with STP, shielded
twisted pair) may be needed if you want to connect the
EtherNet/IP board directly to the master appliance.
Use only industrial standard components in the network and
avoid complex structures to minimize the length of response
time and the amount of incorrect dispatches.
It is often a good practice to use a subnet that is different
from other devices not related to the drive control.
Figure 14. CAT-5e cable
Figure 15. DG1 keypad navigation to ethernet comm settings