123
Hardware specifi cation
POWERXL SERIES VFD
MN040010EN—June 2018 www.eaton.com
DeviceNet board LED status
Table 146. DeviceNet power LED (D1)
Illumination
Pattern Meaning
OFF
Power to controller of Option board is not activated
ON
Power to controller of Option board is activated
Table 147. DeviceNet Board status LED (D10)
Illumination
Pattern Meaning
OFF
Option board not activated
ON
Option board in Normal condition i.e. no fault is
occurred
Blinking at 40 Hz
DCOM communication fault occurs
Blinking at 20 Hz
Option card Hardware fault occurs
Blinking at 10 Hz
DeviceNet communication fault occurs
Table 148. The MS and NS LED (D2)
For this state …
LED is …
To indicate …
Device not powered/
not on–line
Off
Device is not on–line.
• The device has not completed the Dup_MAC_ID test yet.
• The device may not be powered.
Device operational
AND On–line,
connected
Green
The device is operating in a normal condition and the device is on–line with connections in the established state.
• For a Group 2 Only device it means that the device is allocated to a Master.
• For a UCMM capable device it means that the device has one or more established connections.
Device operational
AND On–line, not
connected
or
Device On–line
AND Device needs
commissioning
Flashing
Green
The device is operating in a normal condition and the device is on–line with no connections in the established
state.
• The device has passed the Dup_MAC_ID test, is on–line, but has no established connections to other nodes.
• For a Group 2 Only device it means that this device is not allocated to a master.
• For a UCMM capable device it means that the device has no established connections.
• Configuration missing, incomplete or incorrect.
Minor Fault and/or
Connection Time–Out
and/or No Network
Power
Flashing Red
Any one or more of the following conditions:
• Recoverable fault
• One or more I/O Connections are in the Timed-Out state
• No network power present
Critical Fault or
Critical Link Failure
Red
The device has an unrecoverable fault; may need replacing.
Failed communication device. The device has detected an error that has rendered it incapable of communicating
on the network (Duplicate MAC ID, or Bus–off).
Communication Faulted
and Received an
Identify Comm Fault
Request—Long
Protocol
Flashing Red
and Green
A specific Communication Faulted device. The device has detected a Network Access error and is in the
Communication Faulted state. The device has subsequently received and accepted an Identify Communication
Faulted Request—Long Protocol message.
Содержание PowerXL Series
Страница 1: ...Effective June 2018 Supersedes October 2017 Communication manual PowerXL Series VFD...
Страница 24: ...xxiv S curit du moteur et de l quipement POWERXL SERIES VFD MN040010EN June 2018 www eaton com...
Страница 149: ...125 Hardware speci cation POWERXL SERIES VFD MN040010EN June 2018 www eaton com Figure 53 DeviceNet parameters...
Страница 202: ...178 Commissioning POWERXL SERIES VFD MN040010EN June 2018 www eaton com Fault tracing Figure 74 Fault tracing...
Страница 253: ...229 Appendix D PowerXL Recommended Secure Hardening Guidelines POWERXL SERIES VFD MN040010EN June 2018 www eaton com...
Страница 254: ...230 Hardware speci cation POWERXL SERIES VFD MN040010EN June 2018 www eaton com...
Страница 255: ...231 Hardware speci cation POWERXL SERIES VFD MN040010EN June 2018 www eaton com...