87
PROFIBUS-DP External Communication Cards
POWERXL SERIES VFD
MN040010EN—June 2018 www.eaton.com
Table 104. Bypass mode process data modules
Module
Byte 0
Byte 1
Byte 2
Byte 3
Byte 4
Byte 5
Byte 6
Byte 7
Byte 8
Byte 9
Module 1
CW
REF
FBData_In_1
FBData_In_2
SW
ACT
FBData_Out_1 FBData_Out_2
Module 2
CW
REF
FBData_In_1
FBData_In_2
FBData_In_3
FBData_In_4
SW
ACT
FBData_Out_1 FBData_Out_2 FBData_Out_3 FBData_Out_4
Module 3
CW
REF
FBData_In_1
FBData_In_2
FBData_In_3
FBData_In_4
FBData_In_5
FBData_In_6
SW
ACT
FBData_Out_1 FBData_Out_2 FBData_Out_3 FBData_Out_4 FBData_Out_5 FBData_Out_6
Module 4
CW
REF
FBData_In_1
FBData_In_2
FBData_In_3
FBData_In_4
FBData_In_5
FBData_In_6
FBData_In_7
FBData_In_8
SW
ACT
FBData_Out_1 FBData_Out_2 FBData_Out_3 FBData_Out_4 FBData_Out_5 FBData_Out_6 FBData_Out_7 FBData_Out_8
Only available in bypass mode.
Process data out
This register range is normally used to fast monitoring of
the VFD. Process Data Out is located in range ID 2104–2111.
See table below.
Table 105. Fieldbus basic output table
ID
Modbus register
Group
Range/Type
2101
32101, 42101
FB Status Word
Binary coded
2102
32102, 42102
FB General Status Word
Binary coded
2103
32103, 42103
FB Actual Speed
%
2104
32104, 42104
FB Process Data Out 1
2105
32105, 42105
FB Process Data Out 2
2106
32106, 42106
FB Process Data Out 3
2107
32107, 42107
FB Process Data Out 4
2108
32108, 42108
FB Process Data Out 5
2109
32109, 42109
FB Process Data Out 6
2110
32110, 42110
FB Process Data Out 7
2111
32111, 42111
FB Process Data Out 8
ote:
N
FB Process data is defined in
Appendix B.
Status word
15 14 13 12 11 10
9
8
7
6
5
4
3
2
1
0
— — — — — — — — RUNEN BYS AREF WARN FLT DIR RUN RDY
Information about the status of the device and messages is
indicated in the Status Word. The Status Word is composed
of 16 bits that have the following meanings.
Table 106. Status word bit descriptions
Bit
Description
value = 0
Value = 1
0
Not Ready
Ready
1
STOP
RUN
2
Clockwise
Counterclockwise
3
—
Faulted
4
—
Warning
5
Ref. frequency not reached
Ref. frequency reached
6
Bypass not activated
Bypass activated
7
Run disable
Run Enable
8
Not in use
Not in use
9–15
Not in use
Not In use
Actual speed
15
14
13
12
11
10
9
8
7
6
5
4
3
2
1
0
MSB — — — — — — — — — — — — — — LSB
This is the Actual Speed of the motor.This value comes back
in the form of Hz.
Содержание PowerXL Series
Страница 1: ...Effective June 2018 Supersedes October 2017 Communication manual PowerXL Series VFD...
Страница 24: ...xxiv S curit du moteur et de l quipement POWERXL SERIES VFD MN040010EN June 2018 www eaton com...
Страница 149: ...125 Hardware speci cation POWERXL SERIES VFD MN040010EN June 2018 www eaton com Figure 53 DeviceNet parameters...
Страница 202: ...178 Commissioning POWERXL SERIES VFD MN040010EN June 2018 www eaton com Fault tracing Figure 74 Fault tracing...
Страница 253: ...229 Appendix D PowerXL Recommended Secure Hardening Guidelines POWERXL SERIES VFD MN040010EN June 2018 www eaton com...
Страница 254: ...230 Hardware speci cation POWERXL SERIES VFD MN040010EN June 2018 www eaton com...
Страница 255: ...231 Hardware speci cation POWERXL SERIES VFD MN040010EN June 2018 www eaton com...