BACnet/IP parameters
Table 199. BACnet/IP parameter descriptions
ID
Name
Description
P12.4.1.9
Enable BACnet/IP
This parameter enables BACnet IP communications. When this parameter is enabled, other parameters in
menu becomes visible, else they are hidden.
P12.4.3.1
BACnet/IP UDP port number
The UDP port for the BACnet IP communication.
P12.4.3.2
BACnet/IP Foreign Device
The foreign device feature is used when the device is located in a different network than the BBMD.
A normal router does not send broadcast messages between different networks. The ‘Foreign device’
feature solves this problem by establishing a connection to the BBMD with unicast messages. All
broadcast messages are forwarded to a BBMD device that takes care of receiving and transmitting
broadcast messages in both directions for all foreign devices.
P12.4.3.3
BACnet/IP BBMD IP
The IP address of the BACnet IP Broadcast Management Device.
P12.4.3.4
BACnet/IP BBMD Port
The BBMD Port number.
P12.4.3.5
BACnet/IP Registration Interval
The registration interval to keep a live connection to the BBMD. Unit is seconds.
P12.4.3.6
BACnet/IP Comm Timeout
Defines the number of seconds after a timeout is indicated after a communication break or disconnected
EtherNet link. Value 0 disables communication link supervision.
P12.4.3.7
BACnet/IP Protocol Status
Fieldbus Protocol Status tells the status of the protocol.
P12.4.3.8
BACnet/IP Fault Behavior
Defines when Fieldbus fault to be raise if fault condition is detected.
P12.4.3.9
BACnet/IP Instance Number
The Device Object’s Instance number is used in conjunction with the MAC address to assign the devices
on the network. The instance number can have up to 127 nodes on it before a different instance number is
required.
BACnet overview
BACnet technical data
Protocol Implementation Conformance Statement (PICS)
Controller Profile
•
B—ASC
Segmentation Capability
•
Not supported
Data Link Layer and Routing Options
•
10/100 MBit/s, Autosensing
Character Sets Supported
•
UTF8
BIBBS Supported
•
Data Sharing
•
ReadProperty—B
•
WriteProperty—B
•
Device Management
•
Dynamic Device Binding—B
•
Dynamic Object Binding—B
•
DeviceCommunicationControl—B
•
ReinitializeDevice—B
•
Alarms and Events: Not supported
•
Schedules: Not supported
•
Trends: Not supported
•
Network Management: Not supported
Содержание PowerXL Series
Страница 1: ...Effective June 2018 Supersedes October 2017 Communication manual PowerXL Series VFD...
Страница 24: ...xxiv S curit du moteur et de l quipement POWERXL SERIES VFD MN040010EN June 2018 www eaton com...
Страница 149: ...125 Hardware speci cation POWERXL SERIES VFD MN040010EN June 2018 www eaton com Figure 53 DeviceNet parameters...
Страница 202: ...178 Commissioning POWERXL SERIES VFD MN040010EN June 2018 www eaton com Fault tracing Figure 74 Fault tracing...
Страница 253: ...229 Appendix D PowerXL Recommended Secure Hardening Guidelines POWERXL SERIES VFD MN040010EN June 2018 www eaton com...
Страница 254: ...230 Hardware speci cation POWERXL SERIES VFD MN040010EN June 2018 www eaton com...
Страница 255: ...231 Hardware speci cation POWERXL SERIES VFD MN040010EN June 2018 www eaton com...