121
DeviceNet External Communication Cards
POWERXL SERIES VFD
MN040010EN—June 2018 www.eaton.com
DeviceNet External Communication Cards
DeviceNet is an open protocol network based on the
CAN stack protocol. It is designed to connect industrial
control devices to a network without expensive hardwiring.
With direct connectivity, DeviceNet provides improved
communications between devices as well as important
device diagnostic information that is typically not as easily
accessed with hardwired I/O interfaces.
The DeviceNet model is referred to as an application
independent. It provides communication services needed by
various types of applications. It uses a predefined Master/
Slave connection set that is used between the devices on
the network with the master controller. This being said it is
based on the CIP (Common Industrial Protocol).
DeviceNet technical data
Table 143. DeviceNet connection
Item
Value
Interface
Open style connector (Pluggable connector)
Data Transfer method
CAN
Transfer Cable
2 wire Twisted shielded cable with 2 wire but power
cable and drain
Electrical Isolation
500 Vdc
Table 144. Communications
Item
Value
ODVA CT26 Compliant
Baud rate
500 kBaud
250 kBaud
125 kBaud
Addresses
0-63
Product Code
0x3019
Product Type
0x02
Vendor ID
68
DeviceNet
Network supply voltage: 11 to 25 Vdc network input
current: 28 mA typical, 125 mA inrush (24 Vdc)
Table 145. Environment
Description Specification
Ambient Operation
Temperature
–10 °C to +55 °C
Storing Temperature
–40 °C to +60 °C
Humidity
<95%, no condensation allowed
Altitude
Max. 1000 M
Vibration
0.5G at 9–200 Hz
Safety
Fulfills EN 50178 standard
Baud Rate
125 Kbps, 250 Kbps and 500 Kbps
Network Size
Up to 64 nodes including master
Network Length
Selectable end to end distance varies with speed
Baud rate
Distance
125 Kbps
500 m
250 Kbps
250 m
500 Kbps
100 m
Содержание PowerXL Series
Страница 1: ...Effective June 2018 Supersedes October 2017 Communication manual PowerXL Series VFD...
Страница 24: ...xxiv S curit du moteur et de l quipement POWERXL SERIES VFD MN040010EN June 2018 www eaton com...
Страница 149: ...125 Hardware speci cation POWERXL SERIES VFD MN040010EN June 2018 www eaton com Figure 53 DeviceNet parameters...
Страница 202: ...178 Commissioning POWERXL SERIES VFD MN040010EN June 2018 www eaton com Fault tracing Figure 74 Fault tracing...
Страница 253: ...229 Appendix D PowerXL Recommended Secure Hardening Guidelines POWERXL SERIES VFD MN040010EN June 2018 www eaton com...
Страница 254: ...230 Hardware speci cation POWERXL SERIES VFD MN040010EN June 2018 www eaton com...
Страница 255: ...231 Hardware speci cation POWERXL SERIES VFD MN040010EN June 2018 www eaton com...