![Eaton Magnefix MD4 Скачать руководство пользователя страница 26](http://html1.mh-extra.com/html/eaton/magnefix-md4/magnefix-md4_user-manual_4122434026.webp)
Magnefix MD4
26
991.184 G01 03
3.3.13 Fit the C-section to the front of the
frame (systems with Protected panel
only)
1.
Fit the C-section to the front of the frame after
connecting the cables (Chapter 3.9).
2.
Fit the cable support section (r) to the underside of the
C-section (p).
3.
Fit the cable clamps (s) to the cable support section.
4.
Secure the cables in the clamps and tighten the
clamps firmly.
1 .. 4
3.3.14 Checks
1. Check the connections made. This is to ensure a
perfect earth connection.
3.3.15 Spare panels
If the switchgear contains spare panels, fit them with
covers and unfilled cable boxes.
R
EMARK
The cable boxes must not be sealed airtight at the
bottom.