![Eaton Magnefix MD4 Скачать руководство пользователя страница 52](http://html1.mh-extra.com/html/eaton/magnefix-md4/magnefix-md4_user-manual_4122434052.webp)
Magnefix MD4
52
991.184 G01 03
5. Secure the filling device by firmly tightening the screw
in the top plate.
6. Using the hose clip, firmly attach the hose to the filling
tube of the filling device.
7. Remove the nylon locking pin and the rubber sealing
from the cable box.
8. Connect the filling hose to the cable box:
insert the nipple as far as possible into the filling hole
and give it a quarter turn. Check that the nipple snaps
into the filling hole interlock.
9. Place the hand-operated pump on the valve and fill the
cable box by pumping steadily (to prevent air bubbles
from developing). The cable box has to be completely
filled.
10. When the grease in the cable box touches the cast
resin insulation, continue pumping steadily until the
cable box has expanded by approximately 2 cm.
N
OTE
Maximum working pressure is 0,5-0,8 bar.
Maximum pumping pressure is 1 bar is not to be
exceeded.
5.. 9
11. Wait for the grease to come out of one of the spigots
and then pull away the nylon thread. Repeat this for
the other spigots.
12. Fit the protection covers on the left-hand side and
secure them. Make sure that the clamping edge of the
cable box adequately rests on the bearing face of the
protection cover.
13. Remove the pump from the valve.
14. Now depressurise the cable box, using the valve, until
the box remains about 1 cm thicker. The excess filling
is necessary to compensate for shrinkage and any
grease absorption by the cable.
11