991.184 G01 03
3. Saw off the cable box in accordance with the diameter
(d) measured across the lead sheath. Take into
account that several layers of polyethylene tape are to
be applied over the lead sheath.
4. Deburr sharp edges.
3, 4
5. Degrease the upper side of the lead sheath and sand
it lightly, for example, with a scouring pad.
6. Apply a couple of layers of polyethylene tape to the
lead sheath, so that the diameter measured across the
tape equals the inside diameter of the cable box.
Ensure that the upper side of the tape is flush with
that of the lead sheath
(see arrow).
Smooth out any wrinkles.
5, 6
R
EMARK
The filling opening is located at the front.
Make sure the paper insulation of the cores
does not become damaged (B).
7. Slide the cable box on to the cast resin insulation of
the panel.
8. Draw the cable beside the cable box until the
polyethylene tape protrudes about 10 mm below the
cable box.
9. Mark the cable with a line (M) immediately above the
cable clamp (A).
10. Remove the cable box from the cast resin insulation.
11. Insert the cable into the cable box from below and
lower the cable box on to the cable as far as possible.
7..10