![Eaton Magnefix MD4 Скачать руководство пользователя страница 17](http://html1.mh-extra.com/html/eaton/magnefix-md4/magnefix-md4_user-manual_4122434017.webp)
Magnefix MD4
991.184 G01 03
17
Dimensions
– wall-mounted version
Panel name
widths
weight
Cable panel (including switch caps)
91 mm
15 kg
Busbar connection
91 mm
7.5 kg
Connecting panel
91 mm
4.5 kg
Busbar connecting panel (sectional panel including switch caps)
182 mm
19.5 kg
Protected panel with current transformers (including branch-circuit panel and switch caps) 230 mm
61.5 kg
Fuse panel with branch-circuit panel (including switch caps and fuse holders, excluding fuses)
230 mm
37.5 kg
Busbar connecting panel with SVS or HC switchgear
91 mm
9 kg
Height (overall height)
1487 mm
Depth with fuse panel
517 mm
Depth without fuse panel
(measured with a switch cap having an electromechanical indicator)
465 mm
Depth with protected panel (including earthing interlock)
605 mm (+ 27)
Calculation of width (example):
B= (K x 91) + (T x 230) + 72 where:
K: number of cable panels
T: number of protected branches
Total switchgear width (B): number of panels (panel width) + 2 side plates.
Maximum switchgear width (B): 1404 mm (including 3
rd