Proceed as follows:
1. Pull up the cable and fix it in the cable clamps. Firmly
tighten the clamps.
2. Terminate the cable in accordance with the
instructions of the cable supplier.
1
3. Cut off the cable cores 2 to 3 mm below the cast resin
insulation.
4. Remove the insulation from the cable cores over a
distance of 30 mm.
3, 5
5. Insert the greased rubber sleeves (b) into the feed
opening of the insulating conduits (a) at the top.
N
OTE
These rubber sleeves are not resistant to cable
grease..
5
6. Turn the sealing plugs inside out.
a
b