4.2.2
Switching off
Switching off the cable panel and branch-circuit
panel
W
ARNING
Refer to the safety instructions in paragraph 4.1.2.
Procedure for switch caps
1. Place the springing handle on the switch cap.
2. Pull the handle firmly.
The switch cap disengages from the fixed part.
1, 2
3.
Place a clean, dry cover on the open cast resin
insulated member of the switch.
4
If (maintenance) work is scheduled to be performed,
the installation must have protective earthing.
Switching off a protected panel
3 Cover for cast resin insulated member of switch
Procedure for protected panel
1
If the relay has switched off the protected panel:
the electronic trip indicator (9) will show a red field;
the mechanical position indicator (5) will show a
white field.
Verify this.
2
If the position indicator (5) shows a black field, press
the button (6) The vacuum circuit-breaker will then
switch off.
3
Remove the corresponding switch caps (12) one by
one in line with the above procedure.
4
If (maintenance) work is scheduled to be performed,
the installation must have protective earthing.
5
If you are about to carry out measurements, switch on
the vacuum circuit-breaker in line with the above
procedure “Switching on for maintenance work” and
then lock it to prevent switching off, using the relevant
key-operated earthing interlock locking knob.