![Eaton Magnefix MD4 Скачать руководство пользователя страница 46](http://html1.mh-extra.com/html/eaton/magnefix-md4/magnefix-md4_user-manual_4122434046.webp)
Magnefix MD4
46
991.184 G01 03
8. Slide the cable box on to the cast resin insulation of
the panel.
9. Draw the cable beside the cable box (g) such that the
bottom of the O ring (f) is about 25 mm higher than the
bottom of the cable box.
10. Mark the cable with a line (M) immediately above the
cable clamp (a).
11. Remove the cable box from the cast resin insulation.
12. Insert the cable into the cable box from below and
lower the cable box on to the cable as far as possible.
13. Fix the cable in the cable clamp (c) at position (M)
previously marked.
Move the distance plates (b) until the centre of the
cable is exactly in line with the centre of the cable box.
Firmly tighten the cable clamp.
14. For copper-cored cables, depending on the core
diameter, refer to the procedure described in:
(3 x 70 mm
2
) Chapter 3.6.1, 13 to 23
(3 x 95 mm
2
) Chapter 3.6.2, 13 to 25
15. For cables with an aluminium core:
Once the crimp cable clamps have been placed, fix
them in accordance with the instructions. In this case,
skip step 14.
13
R
EMARK
Fit the hose clip at the level of the O ring to ensure
proper sealing.
16. Fit the hose clip to the gland bush, at the level of the O
ring.
17. Fill the cable box with grease (see Chapter 3.7).
16
M