EDR-3000
IM02602003E
Set-up a Connection Via Modbus Tunnel
Establishing a connection via a Gateway (TCP/IP)/Modbus RTU to the device is
only possible if your device is equipped with an Ethernet Interface (RJ45).
Contact your IT administrator in order to establish the network connection.
Part 1: If you don´t know the Slave ID of the device that should be connected via Modbus Tunnel, it can be read out at
the device.
Call up the menu
»Device parameter/Modbus« at the HMI (panel) and read out the Slave ID:
Part 2: Setting the IP address of the gateway and the Slave ID of the device that is to be connected via Modbus tunnel
using PowerPort-E
Call up the menu Settings/Device Connection within PowerPort-E.
Select »Modbus TCP/IP Gateway«
Enter the IP-Address of the device that should be connected.
Enter the Slave ID of the device.
www.eaton.com
161