EDR-3000
IM02602003E
Parameter
Description
Setting range
Default
Menu path
Angle IB Fund.
Start Position respectively Start Angle of the Current
Phasor during Fault Phase:Phase B
-360 - 360°
240°
[Service
/Test Mode (Prot
inhibit)
/WARNING! Cont?
/Sgen
/Configuration
/FaultSimulation
/CT]
Angle IC Fund.
Start Position respectively Start Angle of the Current
Phasor during Fault Phase:Phase C
-360 - 360°
120°
[Service
/Test Mode (Prot
inhibit)
/WARNING! Cont?
/Sgen
/Configuration
/FaultSimulation
/CT]
Angle IX meas
Fund.
Start Position respectively Start Angle of the Current
Phasor during Fault Phase: IX
-360 - 360°
0°
[Service
/Test Mode (Prot
inhibit)
/WARNING! Cont?
/Sgen
/Configuration
/FaultSimulation
/CT]
IA Fund.
Current Fundamental Magnitude during Post phase:
Phase A
0.00 - 40.00In
0.0In
[Service
/Test Mode (Prot
inhibit)
/WARNING! Cont?
/Sgen
/Configuration
/PostFault
/CT]
www.eaton.com
636