EDR-3000
IM02602003E
Parameter
Description
Setting range
Default
Menu path
Curve Shape
Characteristic
IEC NINV,
IEC VINV,
IEC EINV,
IEC LINV,
ANSI MINV,
ANSI VINV,
ANSI EINV,
Therm Flat,
IT,
I2T,
I4T
ANSI MINV
[Protection Para
/<1..4>
/I-Prot
/51P[1]]
t-multiplier
Time multiplier/tripping characteristic factor. The setting
range depends on the selected tripping curve.
0.02 - 20.00
51P[1]: 1
51P[2]: 2
51P[3]: 3
[Protection Para
/<1..4>
/I-Prot
/51P[1]]
Reset Mode
Reset Mode
Instantaneous,
t-delay,
Calculated
Calculated
[Protection Para
/<1..4>
/I-Prot
/51P[1]]
t-reset
Reset time for intermittent phase failures (INV
characteristics only)
Available if:Reset Mode = t-delay
0.00 - 60.00s
0s
[Protection Para
/<1..4>
/I-Prot
/51P[1]]