EDR-3000
IM02602003E
Single Contact Indication – 52b only
If only the
52b signal is used for the monitoring of the “OPEN command”, the switch command will start the moving
timer. The Position Indication will indicate an INTERMEDIATE position. If the moving time elapsed before the
switchgear has reached the OPEN position, the switching operation was not successful and the Position Indication will
change to Pos DISTURB.
A CLOSE command also starts the moving time. Because the device does not receive a close signal by the breaker, it
assumes that the breaker is in close position after the moving time has elapsed.
The following table shows how breaker positions are validated based on 52b only:
States of the Digital Input
Validated Breaker Positions
CinBkr52a-I
CinBkr52b-I
Pos CLOSE
Pos OPEN Pos Indeterm Pos Disturb
Breaker
State
Not wired
0
0
0
1
(while t-Move
OPEN is
running)
0
(while t-Move
OPEN is
running)
0
Intermediate
Not wired
1
0
1
0
0
1
OFF
Not wired
0
1
0
0
0
2
ON
Not wired
1
0
0
0
(after t-Move
OPEN is
elapsed)
1
(after t-Move
OPEN is
elapsed)
3
Disturbed
www.eaton.com
367
Содержание EDR 3000
Страница 2: ......
Страница 4: ......
Страница 6: ......
Страница 7: ...Medium Voltage Switchgear Assembly...
Страница 8: ......
Страница 10: ......
Страница 11: ...Component Data...
Страница 12: ......
Страница 64: ...EDR 3000 IM02602003E Ethernet RJ45 Terminal Marking www eaton com 52 1 8 TxD TxD RxD N C N C RxD N C N C...
Страница 659: ...EDR 3000 IM02602003E Real Time Clock Running Reserve of the Real Time Clock 1 year min www eaton com 647...