background image

EDR-3000

IM02602003E

www.eaton.com

19

Access Level

Read Only-Lv0

Prot-Lv1

Prot-Lv2

Supervisor-Lv3

Control-Lv1

Control-Lv2

Parameters can only be read within this level.

This level enables to execute Resets and Acknowledgements

This level enables to modify protection settings

This level provides full access (not limited) to all settings

This level enables to control switchtgears

This level enables to modify the settings of switchgears

(Please refer to chapter  [Parameter\Access Level])

Содержание EDR 3000

Страница 1: ...nual General Order MRM0007157 Volume 3 of 6 Equipment Medium Voltage Switchgear Assembly Pentagon MCM7571 Date 2016 04 08 WESCO MIDLOTHIAN VA 7582 PO 7582 785492 YORK RIVER ELECTRIC 2015 Eaton Corpora...

Страница 2: ......

Страница 3: ...Switchgear Assembly Vol 1 1 1 Drawings 1 2 Instruction Data Vol 2 1 3 Component Data Vol 3 5 2 0 Medium Voltage Switches Vol 6 2 1 Drawings 2 2 Instruction Data 2 3 Component Data 3 0 Panelboards Vol...

Страница 4: ......

Страница 5: ...line catalog pricing document support distribution directory news and events For warranty support 877 ETNCARE For a general directory of Eaton Electrical products 800 525 2000 For on site field servi...

Страница 6: ......

Страница 7: ...Medium Voltage Switchgear Assembly...

Страница 8: ......

Страница 9: ...Medium Voltage Switchgear Assembly Section Table of Contents 1 0 Medium Voltage Switchgear Assembly Vol 3 Section Table of Contents 1 1 Component Data 1 1 1 IM02602003E EDR 3000 RevD Manual...

Страница 10: ......

Страница 11: ...Component Data...

Страница 12: ......

Страница 13: ...EDR 3000 DISTRIBUTION RELAY Installation Operation and Maintenance Software Version 2 5 b IM02602003E Revision D English...

Страница 14: ...50X 51X CTS 79 74 TC Option Fundamental and RMS Max Min Avg Currents THD current Current phasors Sequence Currents Metering SOTF CLPU Trend recorder Event recorder Fault recorder Waveform recorder Zon...

Страница 15: ...Slot X103 Data Communication 55 Slot X120 PC Interface 60 Control Wiring Diagram 61 Input Output and LED Settings 63 Digital Input Configuration 63 DI 8P X 64 DI 4P X Settings 68 Wired Inputs Aliases...

Страница 16: ...utputs 191 Global Protection Parameter of the Demand Management 191 States of the Inputs of the Demand Management 193 Resets 194 Manual Acknowledgment 196 Manual Acknowledgment Via PowerPort E 196 Ext...

Страница 17: ...ten 320 Parameter Setting at the HMI 321 Parameter Setting via Power Port E 325 Setting Groups 328 Comparing Parameter Files Via PowerPort E 341 Converting Parameter Files Via PowerPort E 342 Program...

Страница 18: ...Circuit Monitoring 576 Self Supervision 584 Programmable Logic 587 General Description 587 Programmable Logic at the Panel 593 Programmable Logic Via PowerPort E 593 Commissioning 615 Commissioning P...

Страница 19: ...cifications of the Real Time Clock 660 Time Synchronization Tolerances 660 Specifications of the Measured Value Acquisition 661 Protection Elements Accuracy 662 Appendix 665 Instantaneous Current Curv...

Страница 20: ...nging this manual and without previous notice Therefore no claim can be brought based on the information and descriptions included in this manual Text graphics and formulas do not always apply to the...

Страница 21: ...orized modifications 1 constitute misuse and or negligence within the meaning of the product warranty thereby excluding warranty coverage for any resulting damage and 2 invalidate product certificatio...

Страница 22: ...signed for any usage beyond these applications This applies also to the use as a partly completed machinery The manufacturer cannot be held liable for any resulting damage The User alone bears the ris...

Страница 23: ...oduced To verify that you have the latest revision be sure to check the Eaton Corporation website http www eaton com The latest versions of most publications are available at this site If the User s p...

Страница 24: ...s cigarette packages cellophane wrappers vinyl books or folders plastic bottles and plastic ash trays away from the device the modules and the work area as much as possible 4 Do not remove any printed...

Страница 25: ...mplates The device templates MUST BE installed to allow PowerPort E to configure a device off line Please make sure the product label wiring diagram type code and materials and description pertain to...

Страница 26: ...ned value can be selected 1 n Assignment List Name 1 n VeEnable No assignment 1 n No a ssignment 1 Name 1 n Assignment List Parameter of a Module Input with special values An 1 n output from the list...

Страница 27: ...is expired the output becomes 1 too The time stage will be reset by 0 at the input Thus the output will be set to 0 at the same time Time stage minimum pulse width The pulse width name t will be start...

Страница 28: ...ction module will lead to a general trip Each trip of an active trip authorized protection module will lead to a general trip Each trip of an active trip authorized protection module will lead to a ge...

Страница 29: ...the device type will lead to a phase selective general pickup collective pickup Each phase selective pickup of a module I IG V VX depending on the device type will lead to a phase selective general p...

Страница 30: ...ease Refer to Diagram Q V Decoupling Distributed Generator Q V Decoupling Distributed Generator 40 Please Refer to Diagram CTS Pickup CTS Pickup 44 45 Please Refer to Diagram Analog Values Please Refe...

Страница 31: ...be read within this level This level enables to execute Resets and Acknowledgements This level enables to modify protection settings This level provides full access not limited to all settings This l...

Страница 32: ...SIGNALS are indicated by right and left double arrow heads and small caps Paths are indicated by brackets Software and Device names are written in italic Module and Instance Element names are display...

Страница 33: ...IM02602003E Load Reference Arrow System Within the E Series the Load Reference Arrow System is used in principal Generator protection relays are working based on the Generator Reference System www eat...

Страница 34: ...s the directional feature of the over current protections then the device no longer trips in a directional way but merely in a non directional way The manufacturer does not accept liability for any pe...

Страница 35: ...dbus RTU Modbus TCP I RS 485 Ethernet Modbus RTU Modbus TCP EDR 3000 Printed Circuit Board Printed Circuit Board A Standard B Conformal Coating A Standard EDR 3000 There are two mounts available for t...

Страница 36: ...n method of the Communication system used the needed space depth differs If for instance a D Sub Plug is used it has to be added to the depth dimension Even when the auxiliary voltage is switched off...

Страница 37: ...ground symbol at the rear side of the device The power supply card needs a separate ground connection 2 5 mm2 AWG 14 0 56 0 79 Nm 5 7 In lb at terminal X1 DO NOT over tighten the mounting nuts of the...

Страница 38: ...nded Connect a ground cable 4 to 6 mm2 AWG 12 10 1 7 Nm 15 In lb to the housing using the screw that is marked with the ground symbol at the rear side of the device The power supply card needs a separ...

Страница 39: ...ation placement of the individual modules can be determined from the connection diagram attached to the top of your device Overview of Slots Housing B1 Schematic Diagram The housing must be carefully...

Страница 40: ...12 10 1 7 Nm 15 In lb to the housing using the screw that is marked with the ground symbol at the rear side of the device The power supply card needs a separate ground connection 2 5 mm2 AWG 14 0 56 0...

Страница 41: ...ants have a different scope of functions Available assembly groups in this slot DI8 X1 This assembly group comprises a wide range power supply unit and two non grouped digital inputs and six 6 digital...

Страница 42: ...ut range has to be parameterized Wrong switching thresholds can result in malfunctions wrong signal transfer times The digital inputs are provided with different switching thresholds can be parameteri...

Страница 43: ...1 DI2 DI3 DI4 COM1 DI 4P X COM2 N C 1 3 2 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 Power Supply N C N C N C N C N C N C Donot use Donot use 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 V Power Supply N...

Страница 44: ...s to be configured Wrong switching thresholds can result in malfunctions wrong signal transfer times The digital inputs are provided with different switching thresholds that are configurable two AC an...

Страница 45: ...DI1 COM2 DI2 DI3 DI4 DI5 DI6 DI7 DI8 COM3 Donot use DI 8P X COM3 N C Donot use 1 3 2 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 Power Supply 1 2 3 4 5 6 7 8 9 10 11 12 COM1 13 14 15 16 17 18 V Power Supp...

Страница 46: ...sembly Group with 3 Relay Outputs 1 Supervision Contact All Relay Outputs are Form C contacts RO 5 X2 Assembly Group with 5 Relay Outputs 1 Supervision Contact All Relay Outputs are Form C contacts RO...

Страница 47: ...fully consider the current carrying capacity of the Relay Outputs Please refer to the Technical Data The System OK contact SC relay cannot be configured The system contact is a Form C contact that pic...

Страница 48: ...com 36 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 RO1 RO2 RO3 X SC N C N C N C N C N C N C RO1 CMN RO1 N O RO1 N C RO2 CMN RO2 N O RO2 N C RO3 CMN RO3 N O RO3 N C 1 3 2 4 5 6 7 8 9 10 11 12 13 14 1...

Страница 49: ...sider the current carrying capacity of the Relay Outputs Please refer to the Technical Data The System OK contact SC relay cannot be configured The system contact is a Form C contact that picks up whe...

Страница 50: ...38 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 RO3 RO1 RO2 RO4 RO5 X SC RO1 CMN RO1 N O RO1 N C RO2 CMN RO2 N O RO2 N C RO3 CMN RO3 N O RO3 N C RO4 CMN RO4 N O RO4 N C RO5 CMN RO5 N O RO5 N C 1 3 2...

Страница 51: ...carefully consider the current carrying capacity of the Relay Outputs Please refer to the Technical Data The System OK contact SC relay cannot be configured The system contact is a Form C contact tha...

Страница 52: ...nt www eaton com 40 RO3CMN RO3N O RO3N C 1 3 2 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 IRIG B IRIG B RO1N O RO2 N O SC N C SC N O SC CMN COM OUT IN COM RO 3ZI X 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 1...

Страница 53: ...t TI 4 X3 Standard ground current measuring card TIS 4 X3 Sensitive Ground current measuring card The Technical data of the sensitive ground measuring input deviate are different to the Technical Data...

Страница 54: ...hort circuited before the current circuit to the device is opened The current measuring inputs may exclusively be connected to current measuring transformers with galvanic separation Do not mix the in...

Страница 55: ...E Terminal Markings Pin Assignment www eaton com 43 IA 1A IA N IA 5A IB 1A IB N IC 1A IC N IC 5A IX 1A IX N IX 5A IB 5A 1 2 3 4 5 6 7 8 10 11 9 12 1 2 3 4 5 6 7 8 9 10 11 12 IA 1A 5A N IB 1A 5A N IC 1...

Страница 56: ...transformers have to be short circuited before the current circuit to the device is opened The current measuring inputs may exclusively be connected to current measuring transformers with galvanic se...

Страница 57: ...E Terminal Markings Pin Assignment www eaton com 45 IA 1A IA N IA 5A IB 1A IB N IC 1A IC N IC 5A IX 1A IX N IX 5A IB 5A 1 2 3 4 5 6 7 8 10 11 9 12 1 2 3 4 5 6 7 8 9 10 11 12 IA 1A 5A N IB 1A 5A N IC 1...

Страница 58: ...ive current measuring inputs is the measurement of small currents like they could occur in isolated and high resistance grounded networks Due to the sensitiveness of these measuring inputs don t use t...

Страница 59: ...03E 3 phase 3 wire IG Calculated www eaton com 47 A B C IA IB IC 1 X 2 3 4 5 6 7 8 9 10 11 12 Three phase Current Measurement Inom Secondary 5 A IA 1A 5A N IB 1A 5A N IC 1A 5A N IX 1A 5A N IB IC IA IR...

Страница 60: ...IB 1A 5A N IC 1A 5A N IX 1A 5A N Warning The shielding at the dismantled end of the line has to be put through the zero sequence current transformer and has to be grounded at the cable side ZeroSequen...

Страница 61: ...m 4th CT on Neutral www eaton com 49 A B C IA IB IC 1 X 2 3 4 5 6 7 8 9 10 11 12 4 wire system 4th CT on Neutral In secondary 5 A IA 1A 5A N IB 1A 5A N IC 1A 5A N IX 1A 5A N IB IC IA N IN IN IX meas I...

Страница 62: ...g Neutral www eaton com 50 A B C IA IB IC 1 X 2 3 4 5 6 7 8 9 10 11 12 4 wire system with ground current CT Toroidal involving Neutral In secondary 5 A IA 1A 5A N IB 1A 5A N IC 1A 5A N IX 1A 5A N IB I...

Страница 63: ...Interface Rear side of the device Slots An Ethernet interface may be available depending on the device type ordered The available combinations can be gathered from the ordering code www eaton com 51 X...

Страница 64: ...EDR 3000 IM02602003E Ethernet RJ45 Terminal Marking www eaton com 52 1 8 TxD TxD RxD N C N C RxD N C N C...

Страница 65: ...side of the device Slots If the device is equipped with an IRIG B00X interface is dependent on the ordered device type The available combinations can be gathered from the ordering code www eaton com...

Страница 66: ...EDR 3000 IM02602003E IRIG B00X Make sure that the tightening torque is 5 7 In lb 0 56 0 79 Nm Terminal Markings Pin Assignment for Device www eaton com 54 1 X101 2 IRIG B IRIG B 1 2 IRIG B IRIG B...

Страница 67: ...slot is dependent on the ordered device type The scope of functions is dependent on the type of data communication interface Available assembly groups in this slot RS485 Terminals for Modbus and IEC...

Страница 68: ...bus connection cable must be shielded The shielding has to be fixed at the screw that is marked with the ground symbol at the rear side of the device The communication is Half Duplex www eaton com 56...

Страница 69: ...the Bus Wiring Example Device at the End of the BUS Using the Integrated Terminal Resistor www eaton com 57 6 4 5 3 2 1 5V GND R1 560 R2 120 Protective Relay B B A A R1 R2 R1 HF Shield 6 4 5 3 2 1 5V...

Страница 70: ...rth termination resistors used Shield at bus master side connected to earth termination resistors not used Shield at bus device side connected to earth termination resistors not used 1 3 2 4 5 6 TR P...

Страница 71: ...d at bus device side connected to earth termination resistors used Shield at bus master side connected to earth termination resistors not used Shield at bus device side connected to earth termination...

Страница 72: ...ment of the fully wired null modem cable Dsub 9 Female Signal Dsub 9 Female Signal 2 RxD 3 TxD 3 TxD 2 RxD 4 DTR 6 1 DSR DCD 6 1 DSR DCD 4 DTR 7 RTS 8 CTS 8 CTS 7 RTS 5 GND Ground 5 GND Ground 9 Ring...

Страница 73: ...EDR 3000 IM02602003E Control Wiring Diagram Below is the recommended control wiring schematic for the EDR 3000 www eaton com 61...

Страница 74: ...EDR 3000 IM02602003E Wiring Diagrams Please refer to the file edr 3000_wiring_diagrams pdf on your manual CD www eaton com 62...

Страница 75: ...meters for each of the digital inputs Nominal voltage Debouncing time A state change will only be adopted by the digital input after the debouncing time has expired and Inverting where necessary The d...

Страница 76: ...e Para Digital Inputs DI 8P X1 Group 1 Debouncing Time 1 A change of the state of a digital input will only be recognized after the debouncing time has expired become effective Thus transient signals...

Страница 77: ...tal Inputs DI 8P X1 Group 3 Debouncing Time 3 A change of the state of a digital input will only be recognized after the debouncing time has expired become effective Thus transient signals will not be...

Страница 78: ...Time 20 ms 50 ms 100 ms 20 ms Device Para Digital Inputs DI 8P X1 Group 3 Inverting 7 Inverting the input signals Inactive Active Inactive Device Para Digital Inputs DI 8P X1 Group 3 Debouncing Time 7...

Страница 79: ...DI 8P X Signal Description DI 1 Signal Digital Input DI 2 Signal Digital Input DI 3 Signal Digital Input DI 4 Signal Digital Input DI 5 Signal Digital Input DI 6 Signal Digital Input DI 7 Signal Digi...

Страница 80: ...al input will only be recognized after the debouncing time has expired become effective Thus transient signals will not be misinterpreted No Debouncing Time 20 ms 50 ms 100 ms 20 ms Device Para Digita...

Страница 81: ...o Debouncing Time 20 ms 50 ms 100 ms 20 ms Device Para Digital Inputs DI 4P X1 Inverting 4 Inverting the input signals Inactive Active Inactive Device Para Digital Inputs DI 4P X1 Debouncing Time 4 A...

Страница 82: ...DR 3000 IM02602003E Digital Inputs Output Signals on DI 4P X Signal Description DI 1 Signal Digital Input DI 2 Signal Digital Input DI 3 Signal Digital Input DI 4 Signal Digital Input www eaton com 70...

Страница 83: ...ific functions on digital inputs Alias Example The 52a contact will be assigned connected to Digital input1 DI1 Once the 52a is aliased linked on the DI1 the signal WiredInput 52A can be used instead...

Страница 84: ...uts TOCa M1 Main 1 Breaker Connected 1 n Dig Inputs Device Para Wired Inputs 43 10 M1 Main 1 Breaker Selected To Trip 1 n Dig Inputs Device Para Wired Inputs 52a M2 Main 2 Breaker Closed 1 n Dig Input...

Страница 85: ...nputs Device Para Wired Inputs 43 10 T Tie Breaker Selected To Trip 1 n Dig Inputs Device Para Wired Inputs 43 M System In Manual 1 n Dig Inputs Device Para Wired Inputs 43 A System in Auto 1 n Dig In...

Страница 86: ...ara Wired Inputs TOCa M2 I State of the module input Main 2 Breaker Connected Device Para Wired Inputs 43 10 M2 I State of the module input Main 2 Breaker Selected To Trip Device Para Wired Inputs 52a...

Страница 87: ...will keep it s position as long as it has not been reset and as long as the power supply feeds the protective relay In the case of a loss of power to the protective device the relays will return to th...

Страница 88: ...verting 4 Assignment 5 Inverting 5 OR Inactive Active Latched Assignment 6 Inverting 6 Assignment 7 Inverting 7 OR OR AND State of the Relay Output Acknowledge HMI Acknowledge 1 n Assignment List Ackn...

Страница 89: ...d Acknowledgment Options Relay output contacts can be acknowledged Via the push button C at the operating panel If Latched is active each relay output contact can be acknowledged by a signal for examp...

Страница 90: ...outputs of an entire assembly group has precedence to forcing a single relay output Normal De Energized Energized Normal Service Test Mode Prot inhibit WARNING Cont Force RO RO 3 X2 Force RO1 By means...

Страница 91: ...t acknowledges the corresponding Relay Output can be assigned to each Relay Output The acknowledgement signal is only effective if the parameter Latched is set to active Only available if Latched Acti...

Страница 92: ...of the assigned signal Inactive Active Inactive Device Para Relay Outputs RO 3 X2 RO 1 Assignment 5 Assignment 1 n Assignment List Device Para Relay Outputs RO 3 X2 RO 1 Inverting 5 Inverting of the...

Страница 93: ...ive Device Para Relay Outputs RO 3 X2 RO 2 Acknowledgment Acknowledgment Signal An acknowledgment signal that acknowledges the corresponding Relay Output can be assigned to each Relay Output The ackno...

Страница 94: ...signment 1 n Assignment List Device Para Relay Outputs RO 3 X2 RO 2 Inverting 4 Inverting of the state of the assigned signal Inactive Active Inactive Device Para Relay Outputs RO 3 X2 RO 2 Assignment...

Страница 95: ...fines whether the Relay Output will be latched when it picks up Inactive Active Inactive Device Para Relay Outputs RO 3 X2 RO 3 Acknowledgment Acknowledgment Signal An acknowledgment signal that ackno...

Страница 96: ...of the assigned signal Inactive Active Inactive Device Para Relay Outputs RO 3 X2 RO 3 Assignment 4 Assignment 1 n Assignment List Device Para Relay Outputs RO 3 X2 RO 3 Inverting 4 Inverting of the...

Страница 97: ...DISARMED in order to safely perform maintenance while eliminating the risk of taking an entire process off line Note Zone Interlocking and Supervision Contact cannot be disarmed YOU MUST ENSURE that t...

Страница 98: ...will be set by force for the duration of this time That means for the duration of this time the Relay Output does not show the state of the signals that are assigned on it Only available if Mode Time...

Страница 99: ...a Relay Outputs RO 3 X2 RO 1 RO1 5 Module Input State Assignment Device Para Relay Outputs RO 3 X2 RO 1 RO1 6 Module Input State Assignment Device Para Relay Outputs RO 3 X2 RO 1 RO1 7 Module Input St...

Страница 100: ...tate Assignment Device Para Relay Outputs RO 3 X2 RO 2 RO2 6 Module Input State Assignment Device Para Relay Outputs RO 3 X2 RO 2 RO2 7 Module Input State Assignment Device Para Relay Outputs RO 3 X2...

Страница 101: ...tate Assignment Device Para Relay Outputs RO 3 X2 RO 3 RO3 6 Module Input State Assignment Device Para Relay Outputs RO 3 X2 RO 3 RO3 7 Module Input State Assignment Device Para Relay Outputs RO 3 X2...

Страница 102: ...e while eliminating the risk of taking an entire process off line Note Zone Interlocking and Supervision Contact cannot be disarmed YOU MUST ENSURE that the relays are ARMED AGAIN after maintenance Ou...

Страница 103: ...outputs of an entire assembly group has precedence to forcing a single relay output Normal De Energized Energized Normal Service Test Mode Prot inhibit WARNING Cont Force RO RO 5 X2 Force RO1 By means...

Страница 104: ...ed or force de energized state Normal De Energized Energized Normal Service Test Mode Prot inhibit WARNING Cont Force RO RO 5 X2 Force RO5 By means of this function the normal Relay Output State can b...

Страница 105: ...t acknowledges the corresponding Relay Output can be assigned to each Relay Output The acknowledgement signal is only effective if the parameter Latched is set to active Only available if Latched Acti...

Страница 106: ...of the assigned signal Inactive Active Inactive Device Para Relay Outputs RO 5 X2 RO 1 Assignment 5 Assignment 1 n Assignment List Device Para Relay Outputs RO 5 X2 RO 1 Inverting 5 Inverting of the...

Страница 107: ...ive Device Para Relay Outputs RO 5 X2 RO 2 Acknowledgment Acknowledgment Signal An acknowledgment signal that acknowledges the corresponding Relay Output can be assigned to each Relay Output The ackno...

Страница 108: ...signment 1 n Assignment List Device Para Relay Outputs RO 5 X2 RO 2 Inverting 4 Inverting of the state of the assigned signal Inactive Active Inactive Device Para Relay Outputs RO 5 X2 RO 2 Assignment...

Страница 109: ...fines whether the Relay Output will be latched when it picks up Inactive Active Inactive Device Para Relay Outputs RO 5 X2 RO 3 Acknowledgment Acknowledgment Signal An acknowledgment signal that ackno...

Страница 110: ...of the assigned signal Inactive Active Inactive Device Para Relay Outputs RO 5 X2 RO 3 Assignment 4 Assignment 1 n Assignment List Device Para Relay Outputs RO 5 X2 RO 3 Inverting 4 Inverting of the...

Страница 111: ...ra Relay Outputs RO 5 X2 RO 4 t Off Delay Switch Off Delay 0 00 300 00s 0 2s Device Para Relay Outputs RO 5 X2 RO 4 Latched Defines whether the Relay Output will be latched when it picks up Inactive A...

Страница 112: ...signment 1 n Assignment List Device Para Relay Outputs RO 5 X2 RO 4 Inverting 3 Inverting of the state of the assigned signal Inactive Active Inactive Device Para Relay Outputs RO 5 X2 RO 4 Assignment...

Страница 113: ...O 4 Operating Mode Operating Mode Norm De energ Norm Energ Norm De energ Device Para Relay Outputs RO 5 X2 RO 5 t Off Delay Switch Off Delay 0 00 300 00s 0 2s Device Para Relay Outputs RO 5 X2 RO 5 La...

Страница 114: ...of the assigned signal Inactive Active Inactive Device Para Relay Outputs RO 5 X2 RO 5 Assignment 3 Assignment 1 n Assignment List Device Para Relay Outputs RO 5 X2 RO 5 Inverting 3 Inverting of the s...

Страница 115: ...gnal Inactive Active Inactive Device Para Relay Outputs RO 5 X2 RO 5 DISARMED Ctrl Enables and disables the disarming of the relay outputs This is the first step of a two step process to inhibit the o...

Страница 116: ...is not in a disarmed state The relays can be set from normal operation relay works according to the assigned signals to force energized or force de energized state Permanent Timeout Permanent Service...

Страница 117: ...Relay Outputs RO 5 X2 RO 1 RO1 5 Module Input State Assignment Device Para Relay Outputs RO 5 X2 RO 1 RO1 6 Module Input State Assignment Device Para Relay Outputs RO 5 X2 RO 1 RO1 7 Module Input Sta...

Страница 118: ...ate Assignment Device Para Relay Outputs RO 5 X2 RO 2 RO2 6 Module Input State Assignment Device Para Relay Outputs RO 5 X2 RO 2 RO2 7 Module Input State Assignment Device Para Relay Outputs RO 5 X2 R...

Страница 119: ...ate Assignment Device Para Relay Outputs RO 5 X2 RO 3 RO3 7 Module Input State Assignment Device Para Relay Outputs RO 5 X2 RO 3 Ack signal RO 3 Module Input State Acknowledgment signal for the Relay...

Страница 120: ...ate Assignment Device Para Relay Outputs RO 5 X2 RO 4 Ack signal RO 4 Module Input State Acknowledgment signal for the Relay Output If latching is set to active the Relay Output can only be acknowledg...

Страница 121: ...ate Assignment Device Para Relay Outputs RO 5 X2 RO 5 RO5 7 Module Input State Assignment Device Para Relay Outputs RO 5 X2 RO 5 Ack signal RO 5 Module Input State Acknowledgment signal for the Relay...

Страница 122: ...afely perform maintenance while eliminating the risk of taking an entire process off line Note Zone Interlocking and Supervision Contact cannot be disarmed YOU MUST ENSURE that the relays are ARMED AG...

Страница 123: ...X2 Force all Outs By means of this function the normal Relay Output State can be overwritten forced The relay can be set from normal operation relay works according to the assigned signals to force en...

Страница 124: ...or force de energized state Normal De Energized Energized Normal Service Test Mode Prot inhibit WARNING Cont Force RO RO 3ZI X2 Force RO3 By means of this function the normal Relay Output State can b...

Страница 125: ...that acknowledges the corresponding Relay Output can be assigned to each Relay Output The acknowledgement signal is only effective if the parameter Latched is set to active Only available if Latched...

Страница 126: ...the assigned signal Inactive Active Inactive Device Para Relay Outputs RO 3ZI X2 RO 1 Assignment 5 Assignment 1 n Assignment List Device Para Relay Outputs RO 3ZI X2 RO 1 Inverting 5 Inverting of the...

Страница 127: ...Device Para Relay Outputs RO 3ZI X2 RO 2 Acknowledgment Acknowledgment Signal An acknowledgment signal that acknowledges the corresponding Relay Output can be assigned to each Relay Output The acknow...

Страница 128: ...nment 1 n Assignment List Device Para Relay Outputs RO 3ZI X2 RO 2 Inverting 4 Inverting of the state of the assigned signal Inactive Active Inactive Device Para Relay Outputs RO 3ZI X2 RO 2 Assignmen...

Страница 129: ...ines whether the Relay Output will be latched when it picks up Inactive Active Inactive Device Para Relay Outputs RO 3ZI X2 RO 3 Acknowledgment Acknowledgment Signal An acknowledgment signal that ackn...

Страница 130: ...the assigned signal Inactive Active Inactive Device Para Relay Outputs RO 3ZI X2 RO 3 Assignment 4 Assignment 1 n Assignment List Device Para Relay Outputs RO 3ZI X2 RO 3 Inverting 4 Inverting of the...

Страница 131: ...DISARMED in order to safely perform maintenance while eliminating the risk of taking an entire process off line Note Zone Interlocking and Supervision Contact cannot be disarmed YOU MUST ENSURE that...

Страница 132: ...ill be set by force for the duration of this time That means for the duration of this time the Relay Output does not show the state of the signals that are assigned on it Only available if Mode Timeou...

Страница 133: ...Relay Outputs RO 3ZI X2 RO 1 RO1 5 Module Input State Assignment Device Para Relay Outputs RO 3ZI X2 RO 1 RO1 6 Module Input State Assignment Device Para Relay Outputs RO 3ZI X2 RO 1 RO1 7 Module Inpu...

Страница 134: ...te Assignment Device Para Relay Outputs RO 3ZI X2 RO 2 RO2 6 Module Input State Assignment Device Para Relay Outputs RO 3ZI X2 RO 2 RO2 7 Module Input State Assignment Device Para Relay Outputs RO 3ZI...

Страница 135: ...te Assignment Device Para Relay Outputs RO 3ZI X2 RO 3 RO3 6 Module Input State Assignment Device Para Relay Outputs RO 3ZI X2 RO 3 RO3 7 Module Input State Assignment Device Para Relay Outputs RO 3ZI...

Страница 136: ...perform maintenance while eliminating the risk of taking an entire process off line Note Zone Interlocking and Supervision Contact cannot be disarmed YOU MUST ENSURE that the relays are ARMED AGAIN af...

Страница 137: ...chapter is valid The only difference between Group A and Group B is within the menu paths Via the INFO push button it is always possible to display the current pickups and alarm texts that are assign...

Страница 138: ...nal from the LED Reset list e g digital inputs or communication signals If Latched active The Ex Acknowledge module all LEDs can be acknowledged at once if the signal for external acknowledgment becom...

Страница 139: ...signment 1 Inverting 1 Assignment 2 Inverting 2 Assignment 3 Inverting 3 Assignment 4 Inverting 4 Assignment 5 Inverting 5 LE D Active Color LED Inactive Color OR OR AND Acknowledge HMI Acknowledge 1...

Страница 140: ...tection function is activated If however in spite of successful booting or after the third unsuccessful reboot caused by the self supervision module the Operational LED System OK flashes in red or is...

Страница 141: ...evice Para LEDs LEDs group A LED 1 LED Active Color The LED lights up in this color if the state of the OR assignment of the signals is true Green Red Red flash Green flash Red Device Para LEDs LEDs g...

Страница 142: ...e state of the assigned signal Inactive Active Inactive Device Para LEDs LEDs group A LED 1 Assignment 5 Assignment 1 n Assignment List Device Para LEDs LEDs group A LED 1 Inverting 5 Inverting of the...

Страница 143: ...ignment 1 Assignment 1 n Assignment List 51X 1 Trip Device Para LEDs LEDs group A LED 2 Inverting 1 Inverting of the state of the assigned signal Inactive Active Inactive Device Para LEDs LEDs group A...

Страница 144: ...ed when it picks up Inactive Active Active Device Para LEDs LEDs group A LED 3 Ack signal Acknowledgment signal for the LED If latching is set to active the LED can only be acknowledged if all signals...

Страница 145: ...the state of the assigned signal Inactive Active Inactive Device Para LEDs LEDs group A LED 3 Assignment 3 Assignment 1 n Assignment List Device Para LEDs LEDs group A LED 3 Inverting 3 Inverting of t...

Страница 146: ...ive 1 n LEDAcknList Device Para LEDs LEDs group A LED 4 LED Active Color The LED lights up in this color if the state of the OR assignment of the signals is true Green Red Red flash Green flash Red De...

Страница 147: ...state of the assigned signal Inactive Active Inactive Device Para LEDs LEDs group A LED 4 Assignment 5 Assignment 1 n Assignment List Device Para LEDs LEDs group A LED 4 Inverting 5 Inverting of the...

Страница 148: ...ED 5 Assignment 1 Assignment 1 n Assignment List Prot Pickup Device Para LEDs LEDs group A LED 5 Inverting 1 Inverting of the state of the assigned signal Inactive Active Inactive Device Para LEDs LED...

Страница 149: ...ed when it picks up Inactive Active Active Device Para LEDs LEDs group A LED 6 Ack signal Acknowledgment signal for the LED If latching is set to active the LED can only be acknowledged if all signals...

Страница 150: ...he state of the assigned signal Inactive Active Inactive Device Para LEDs LEDs group A LED 6 Assignment 3 Assignment 1 n Assignment List Device Para LEDs LEDs group A LED 6 Inverting 3 Inverting of th...

Страница 151: ...1 n LEDAcknList Device Para LEDs LEDs group A LED 7 LED Active Color The LED lights up in this color if the state of the OR assignment of the signals is true Green Red Red flash Green flash Green fla...

Страница 152: ...tate of the assigned signal Inactive Active Inactive Device Para LEDs LEDs group A LED 7 Assignment 4 Assignment 1 n Assignment List Device Para LEDs LEDs group A LED 7 Inverting 4 Inverting of the st...

Страница 153: ...e Para LEDs LEDs group A LED 1 LED1 4 Module Input State LED Device Para LEDs LEDs group A LED 1 LED1 5 Module Input State LED Device Para LEDs LEDs group A LED 1 Acknow Sig 1 Module Input State Ackno...

Страница 154: ...2 Module Input State Acknowledgment Signal only for automatic acknowledgment Device Para LEDs LEDs group A LED 2 LED3 1 Module Input State LED Device Para LEDs LEDs group A LED 3 LED3 2 Module Input...

Страница 155: ...LEDs group A LED 4 LED4 3 Module Input State LED Device Para LEDs LEDs group A LED 4 LED4 4 Module Input State LED Device Para LEDs LEDs group A LED 4 LED4 5 Module Input State LED Device Para LEDs LE...

Страница 156: ...5 Module Input State Acknowledgment Signal only for automatic acknowledgment Device Para LEDs LEDs group A LED 5 LED6 1 Module Input State LED Device Para LEDs LEDs group A LED 6 LED6 2 Module Input...

Страница 157: ...LEDs group A LED 7 LED7 2 Module Input State LED Device Para LEDs LEDs group A LED 7 LED7 3 Module Input State LED Device Para LEDs LEDs group A LED 7 LED7 4 Module Input State LED Device Para LEDs LE...

Страница 158: ...02003E Front Panel www eaton com 146 1 2 3 5 7 6 9 10 RS232 Interface PowerPort E Connection ACK RST key INFO Key Signals Messages Control Softkeys Display LED System OK Programmable LEDs Protective D...

Страница 159: ...ion activated Based on the application need up to 7 but not necessary programmable LEDs can be activated By properly configuring some or all 7 LEDs user will be able to view the relay overall operatio...

Страница 160: ...KEYS are contextual On the bottom line of the display the present function is displayed symbolized Possible functions are Navigation Parameter decrement increment Scrolling up down a menu page Moving...

Страница 161: ...e seconds the SOFTKEYs will be shown flashing If there is more than one signal assigned to an LED indicated by three dots the User can check the state of the multiple assignments by proceeding as foll...

Страница 162: ...The User can exit the reset menu by pressing the Softkey Arrow left 8 RS232 Interface PowerPort E Connection Connection to the software PowerPort E is done via the RS232 interface 9 OK Key When using...

Страница 163: ...enu Via SOFTKEY Top of List the User will be taken directly to the top of a list Via SOFTKEY Bottom of List the User will be taken directly to the end of a list Via SOFTKEY the related digit will be i...

Страница 164: ...ves to the top of the active window End Moves to the bottom of the active window Ctrl O Opens the file opening dialog Browsing through the file system for an existing device file Ctrl N Creates a new...

Страница 165: ...of all relay types Reading and evaluation of statistical data and measuring values Commissioning Support Forcing Relays Disarming Relays Display of the device status and Fault analysis via event and f...

Страница 166: ...e button in the INFO frame Select an installation path or confirm the standard installation path by mouse click on the Continue button Confirm the entry for the suggested installation folder by mouse...

Страница 167: ...SB to serial adapter If the USB to serial adapter is correctly installed communication with the device can be established using the CD provided see the next section Setting Up Configuring the Connecti...

Страница 168: ...EDR 3000 IM02602003E www eaton com 156 RS232 Parameter Setting and Evaluation via Serial RS232 PowerPort E Protective Relay Device Example...

Страница 169: ...roved by Eaton Corporation may be used First install the adapter with the related driver that you can find on the CD and then establish the connection PowerPort E Device The adapters must support very...

Страница 170: ...er MUST first read out the IP address at the HMI of the device within menu Device para TCP IP then compare the IP address with the list If the addresses are identical establish the connection If they...

Страница 171: ...EDR 3000 IM02602003E www eaton com 159 TCP IP Parameter Setting and Evaluation via TCP IP PowerPort E IP Address Device Example...

Страница 172: ...www eaton com 160 Protective Relay Protective Relay TCP IP TCP IP TCP IP Parameter Setting and Evaluation via TCP IP PowerPort E IP Address IP Address IP Address TCP IP Ethernet Device Example Device...

Страница 173: ...ID of the device that should be connected via Modbus Tunnel it can be read out at the device Call up the menu Device parameter Modbus at the HMI panel and read out the Slave ID Part 2 Setting the IP...

Страница 174: ...tective Relay Protective Relay TCP IP Modbus RTU Modbus RTU Parameter Setting and Evaluation via Modbus Tunnel PowerPort E Power Xpert Gateway SLAVE ID 2 SLAVE ID 3 SLAVE ID n IP Address Modbus RTU De...

Страница 175: ...d with the proxy settings Example Internet Explorer For each connection the proxy settings have to be set manually Please proceed as follows Start your Internet Explorer Call up the Tools menu Call up...

Страница 176: ...tarted For establishing the connection the User needs to have sufficient rights administration rights If a firewall is installed on your computer TCP IP port 52152 must have been released If your comp...

Страница 177: ...rk Close PowerPort E Call up the Control Panel Choose Network Internet On the left side click on Manage Network Connections Right click on Eaton Relays Direct Connection Choose Delete from the shortcu...

Страница 178: ...into the device button the User can transmit all parameters that are marked by this symbol If a parameter file is saved on the local hard drive these parameters are no longer classified to be modifie...

Страница 179: ...changed parameter data are now saved in the chosen folder Backup and Documentation When Using PowerPort E How to Save Device Data on a PC Click on Save as in the File menu Specify a name choose a fold...

Страница 180: ...se Export into File in order to export the device data into a txt file When exporting data only the actual selected printing range will be exported into a txt file That means that if the User has chos...

Страница 181: ...either Load an existing parameter file from a device please refer to the Section Loading Device Data When Using PowerPort E Create a new parameter file see below or Open a locally saved parameter file...

Страница 182: ...tree item Home Moves to the top of the active window End Moves to the bottom of the active window Ctrl O Opens the file opening dialog Browsing through the file system for an existing device file Ctr...

Страница 183: ...s or Special values within the Measured values tree The measured and calculated values are now shown in tabular form in the window To have the measuring data read in a cyclic manner select Auto refres...

Страница 184: ...EDR 3000 IM02602003E HMI and PowerPort E Power Auto Scaling kW kVAr or kVA MW MVAr or MVA GW GVAr or GVA www eaton com 172...

Страница 185: ...unter will start counting again at zero A corresponding signal will indicate the counter overflow Counter overflow at Energy Auto Scaling Depends on the settings for the current and voltage transforme...

Страница 186: ...ent Fund IX meas Fund Measured value measured IX Fundamental Operation Measured Values Current Fund IR calc Fund Measured value calculated IR Fundamental Operation Measured Values Current Fund I0 Fund...

Страница 187: ...of Positive Sequence System Operation Measured Values Current Fund Angle I2 Measured value calculated Angle of Negative Sequence System Operation Measured Values Current Fund IA RMS Measured value Ph...

Страница 188: ...RMS IA THD Measured Value Calculated IA Total Harmonic Current Operation Measured Values Current RMS IB THD Measured Value Calculated IB Total Harmonic Current Operation Measured Values Current RMS IC...

Страница 189: ...ion Minimum and Maximum Values Peak Values Pointers Time interval for the calculation of the minimum and maximum values Reset Configuration Options Where to configure Within menu Device Para Statistic...

Страница 190: ...calculation based on sliding period fixed fixed Average calculation is resetted by the end of the period that means with the next starting period duration fixed or sliding period Start Fct The average...

Страница 191: ...ion Statistics Vavg Configuration of the Power Based Average Value Calculation Availability depends on the ordered device code Power based Average Values Demand and Peak Values Time period for the cal...

Страница 192: ...ve Active Inactive Operation Reset Global Protection Parameters of the Statistics Module Parameter Description Setting range Default Menu path ResFc Max Resetting of all Maximum values 1 n Assignment...

Страница 193: ...tistics Demand Current Demand Duration I Demand Recording time Only available if Start I Demand via Duration 2 s 5 s 10 s 15 s 30 s 1 min 5 min 10 min 15 min 30 min 1 h 2 h 6 h 12 h 1 d 2 d 5 d 7 d 10...

Страница 194: ...mand Device Para Statistics Demand Current Demand ResFc I Demand I State of the module input Resetting of Statistics Current Demand avg peak avg Device Para Statistics Demand Current Demand ResFc Max...

Страница 195: ...all Minimum values Counters of the Module Statistics Value Description Menu path Res Cr I Demand Number of resets since last booting The timestamp shows date and time of the last reset Operation Stati...

Страница 196: ...s Min CT I2 max Fund Maximum value unbalanced load current Fundamental Operation Statistics Max CT I2 min Fund Minimum value unbalanced load current Fundamental Operation Statistics Min CT IA max RMS...

Страница 197: ...ue RMS Operation Statistics Demand Current Demand IC min RMS IC minimum value RMS Operation Statistics Min CT IX meas max RMS Measured value IX maximum value RMS Operation Statistics Max CT IX meas mi...

Страница 198: ...in Measured value calculated I2 I1 minimum value phase sequence will be taken into account automatically Operation Statistics Min CT IA Peak demand IA Peak value RMS value Operation Statistics Demand...

Страница 199: ...In order to reduce the demand charge respective to demand rate peak loads if possible should be diversified That means if possible avoiding large loads at the same time In order to assist the User in...

Страница 200: ...g window is selected and the interval is set to 15 minutes the protective device calculates and updates the average current or power continuously for the past 15 minutes the newest measuring value rep...

Страница 201: ...4 Window configuration Sliding Window configuration Fixed Sliding Sliding t Delay 0 Duration Average Calculation Pickup t Delay 0 Average Calculation Pickup t Delay 0 Average Calculation Pickup t Dela...

Страница 202: ...enu the minimum min and maximum max values can be seen Minimum values since last reset The minimum values are continuously compared to the last minimum value for that measuring value If the new value...

Страница 203: ...al Protection Parameter of the Demand Management Parameter Description Setting range Default Menu path Function Permanent activation or deactivation of module element Inactive Active Inactive SysA Gen...

Страница 204: ...path t Delay Tripping Delay 0 60min 0min SysA Demand Current Demand Alarm Alarm Inactive Active Inactive SysA THD I THD Threshold Threshold to be entered as primary value 1 500000A 500A SysA THD I TH...

Страница 205: ...EDR 3000 IM02602003E States of the Inputs of the Demand Management Name Description Assignment via ExBlo I Module Input State External Blocking SysA General Settings www eaton com 193...

Страница 206: ...nds at once Where Operation Acknowledge All at once Where Operation Acknowledge External Acknowledg ment Via a signal from the assignment list e g a digital Input all can be acknowledged All LEDs at o...

Страница 207: ...nu of this single LED Relay Output Where Within the Configuration menu of this single Relay Output Pending Trip Command Where Within the module TripControl If the User is within the parameter setting...

Страница 208: ...rd Manual Acknowledgment Via PowerPort E If PowerPort E is not running please start the application If device data have not been downloaded recently select Receive Data From The Device from the Device...

Страница 209: ...edge Via PowerPort E If PowerPort E is not running please start the application If device data have not been downloaded recently select Receive Data From The Device from the Device menu Double click o...

Страница 210: ...ommand Modbus Comm Cmd 2 Communication Command Modbus Comm Cmd 3 Communication Command Modbus Comm Cmd 4 Communication Command Modbus Comm Cmd 5 Communication Command Modbus Comm Cmd 6 Communication C...

Страница 211: ...te Out Signal Output of the logic gate Logic LE6 Timer Out Signal Timer Output Logic LE6 Out Signal Latched Output Q Logic LE6 Out inverted Signal Negated Latched Output Q NOT Logic LE7 Gate Out Signa...

Страница 212: ...LE15 Timer Out Signal Timer Output Logic LE15 Out Signal Latched Output Q Logic LE15 Out inverted Signal Negated Latched Output Q NOT Logic LE16 Gate Out Signal Output of the logic gate Logic LE16 Tim...

Страница 213: ...LE24 Out Signal Latched Output Q Logic LE24 Out inverted Signal Negated Latched Output Q NOT Logic LE25 Gate Out Signal Output of the logic gate Logic LE25 Timer Out Signal Timer Output Logic LE25 Ou...

Страница 214: ...nverted Signal Negated Latched Output Q NOT Logic LE34 Gate Out Signal Output of the logic gate Logic LE34 Timer Out Signal Timer Output Logic LE34 Out Signal Latched Output Q Logic LE34 Out inverted...

Страница 215: ...ate Out Signal Output of the logic gate Logic LE43 Timer Out Signal Timer Output Logic LE43 Out Signal Latched Output Q Logic LE43 Out inverted Signal Negated Latched Output Q NOT Logic LE44 Gate Out...

Страница 216: ...LE52 Timer Out Signal Timer Output Logic LE52 Out Signal Latched Output Q Logic LE52 Out inverted Signal Negated Latched Output Q NOT Logic LE53 Gate Out Signal Output of the logic gate Logic LE53 Tim...

Страница 217: ...LE61 Out Signal Latched Output Q Logic LE61 Out inverted Signal Negated Latched Output Q NOT Logic LE62 Gate Out Signal Output of the logic gate Logic LE62 Timer Out Signal Timer Output Logic LE62 Ou...

Страница 218: ...nverted Signal Negated Latched Output Q NOT Logic LE71 Gate Out Signal Output of the logic gate Logic LE71 Timer Out Signal Timer Output Logic LE71 Out Signal Latched Output Q Logic LE71 Out inverted...

Страница 219: ...Output Q NOT Logic LE78 Gate Out Signal Output of the logic gate Logic LE78 Timer Out Signal Timer Output Logic LE78 Out Signal Latched Output Q Logic LE78 Out inverted Signal Negated Latched Output...

Страница 220: ...tion tree Double click the Reset icon within the operation menu Double click the entry within the pop up that is to be reset or deleted The description of the reset commands can be found within the co...

Страница 221: ...If PowerPort E is not running please start the application If the device data have not been downloaded recently select Receive Data From The Device from Device menu Double click on the Operation icon...

Страница 222: ...ect Commands of the Panel Parameter Description Setting range Default Menu path Contrast Contrast 0 100 50 Device Para HMI Global Protection Parameters of the Panel Parameter Description Setting range...

Страница 223: ...form record is written a new waveform record cannot be triggered until all trigger signals which have triggered the previous waveform record are gone Recording is only done for the time the assigned e...

Страница 224: ...EDR 3000 IM02602003E www eaton com 212 Start 1 Trigger Start 2 Trigger Start 3 Trigger Start 4 Trigger Start 5 Trigger Start 6 Trigger Start 7 Trigger Start 8 Trigger Man Trigger Recording OR OR...

Страница 225: ...trigger time t 0 1 500 ms Post trigger time t 0 1 2000 ms t rec t 0 1 2000 ms Max file size Start 1 Prot Pickup Start 2 Start 3 Start 4 Start 5 Start 6 Start 7 Start 8 Post trigger time 25 Pre trigger...

Страница 226: ...trigger time t 0 1 500 ms Post trigger time t 0 1 1000 ms t rec t rec Max file size t 0 1 2000 ms Max file size Start 1 Prot Trip Start 2 Start 3 Start 4 Start 5 Start 6 Start 7 Start 8 Post trigger...

Страница 227: ...d click Receive Data From The Device in the Device menu Double click the Operation icon in the navigation tree Double click the Recorders icon in the navigation tree Double click the Waveform rec icon...

Страница 228: ...ll waveform records should be deleted and Confirm by pressing SOFTKEY OK Deleting Waveform Records Via PowerPort E If PowerPort E is not running please start the application If the device data have no...

Страница 229: ...n Assignment List Prot Pickup Device Para Recorders Waveform rec Start 2 Start recording if the assigned signal is true 1 n Assignment List Prot Trip Device Para Recorders Waveform rec Start 3 Start r...

Страница 230: ...m rec Post trigger time The post trigger time is settable up to a maximum of 50 of the Maximum file size setting The post trigger will be the remaining time of the Max file size but at maximum Post tr...

Страница 231: ...evice Para Recorders Waveform rec Start4 I State of the module input Trigger event start recording if Device Para Recorders Waveform rec Start5 I State of the module input Trigger event start recordin...

Страница 232: ...gnals Signal Description Recording Signal Recording Memory full Signal Memory Full Clear fail Signal Clear Failure in Memory Res all rec Signal All records deleted Res record Signal Delete Record Man...

Страница 233: ...enu path Rec state Recording state Ready Ready Recording Writing file Trigger Blo Operation Status display Recorders Waveform rec Error code Error code OK OK Write err Clear fail Calculation err File...

Страница 234: ...alysis already at the HMI After a fault a popup window will be sent onto the display in order to draw the users attention to the fault The Fault Recorder will provide information on the causes of the...

Страница 235: ...falling edge of the General Pickup Signal Please note that General Pickup is an or connection disjunction of all Pickup signals General Trip is an OR connection of all Trips www eaton com 223 Prot Pic...

Страница 236: ...en does the overlay popup appears on the display of the HMI A popup will appear on the HMI display when the General Pickup Prot Pickup disappears No time to trip will be shown if the pickup signal tha...

Страница 237: ...using Softkey OK How to find out fast if a fault has lead to a trip or not Faults that lead to a trip will be indicated by a flash icon right side within the overview menu of the fault recorder Which...

Страница 238: ...n that will be displayed depends on which protection module has tripped That means e g that the thresholds are shown In case that the trip was initiated by the MotorStart applies to motor protection r...

Страница 239: ...ext lower item within this fault record How to read Out the Fault Recorder In order to read out a fault record there are two options available Option 1 A Fault has popped up on the HMI because an trip...

Страница 240: ...e In the window the fault recordings are shown in tabular form In order to receive more detailed information on a fault double click the selected item in the list Via the print menu the User can expor...

Страница 241: ...e Fault Recorder Module Parameter Description Setting range Default Menu path Record Mode Recorder Mode Set the behaviour of the recorder Pickups and Trips Trips only Trips only Device Para Recorders...

Страница 242: ...This counter will be incremented by each General Pickup Prot Pickup A grid fault No can have several Fault Nos This counter will be incremented by each General Pickup Exception AR this applies only to...

Страница 243: ...k Receive Data From The Device in the Device menu Double click the Operation icon in the navigation tree Double click the Event Rec icon within the Operation Recorders menu In the window the events ar...

Страница 244: ...oceed as follows Call up the data as described above Call up the File Print menu Choose Print Actual Working Window within the pop up Press the Print button Press the Export to File button Enter a fil...

Страница 245: ...t Recorder Module Parameter Description Setting range Default Menu path Res all rec Reset all records Inactive Active Inactive Operation Reset Event Recorder Module Signals Signal Description Res all...

Страница 246: ...m the relay to the User s PC By selecting the Refresh Trend Recorder PowerPort E updates the list of the Trend Recorder The Delete Trend Recorder function will clear all trend data from the relay leav...

Страница 247: ...Measured value calculated Zero current Fundamental CT I1 Fund Measured value calculated Positive phase sequence current Fundamental CT I2 Fund Measured value calculated Unbalanced load current Fundame...

Страница 248: ...nd rec Observed Value3 Observed Value3 1 n TrendRecList CT IC RMS Device Para Recorders Trend rec Observed Value4 Observed Value4 1 n TrendRecList CT IX meas RMS Device Para Recorders Trend rec Observ...

Страница 249: ...EDR 3000 IM02602003E Parameter Description Setting range Default Menu path Observed Value10 Observed Value10 1 n TrendRecList Device Para Recorders Trend rec www eaton com 237...

Страница 250: ...Parameter Description Setting range Default Menu path Reset Delete all entries Inactive Active Inactive Operation Reset Counter Values of the Trend Recorder Value Description Default Size Menu path M...

Страница 251: ...nchronized via the following protocols IRIG B SNTP Communications Protocol Modbus RTU or TCP and or These protocols use different hardware interfaces and are different in accuracy Further information...

Страница 252: ...actors Accuracy of the connected time generator Synchronization protocol that is used and At Modbus TCP and SNTP Network load and data package transmission times Please consider the accuracy of the ti...

Страница 253: ...ezone menu 2 There also configure the switching of daylight savings time 3 Select the used time synchronisation protocol in the TimeSync menu e g IRIG B 4 Set the parameters of the synchronisation pro...

Страница 254: ...mertime Daylight Saving Time Only available if DST manual Active Inactive Active Inactive Device Para Time Timezone Summertime m Month of clock change summertime Only available if DST manual Active Ja...

Страница 255: ...ST manual Active 0 59min 0min Device Para Time Timezone Wintertime m Month of clock change wintertime Only available if DST manual Active January February March April May June July August September Oc...

Страница 256: ...enu path Wintertime h Hour of clock change wintertime Only available if DST manual Active 0 23h 3h Device Para Time Timezone Wintertime min Minute of clock change wintertime Only available if DST manu...

Страница 257: ...ong Kong UTC 7 Bangkok UTC 6 5 Rangoon UTC 6 Colombo UTC 5 75 Kathmandu UTC 5 5 New Delhi UTC 5 Islamabad UTC 4 5 Kabul UTC 4 Abu Dhabi UTC 3 5 Tehran UTC 3 Moscow UTC 2 Athens UTC 1 Berlin UTC 0 Lond...

Страница 258: ...EDR 3000 IM02602003E Parameter Description Setting range Default Menu path TimeSync Time synchronization IRIG B SNTP Modbus Device Para Time TimeSync TimeSync www eaton com 246...

Страница 259: ...or two connected SNTP servers The device s system time will be synchronized by the connected SNTP server 1 to 4 times per minute In turn the SNTP server synchronizes its time via NTP with other NTP s...

Страница 260: ...used because this could cause fluctuations of the time synchronization The network quality gives information about the network s load and data package transmission time The quality should be GOOD or...

Страница 261: ...ration Status Display Time Sync Sntp menu If the SNTP status is not active please proceed as follows Check if the wiring is correct Ethernet cable connected Check if a valid IP address is set in the d...

Страница 262: ...nter Reset all Counters Inactive Active Inactive Operation Reset Global Protection Parameters of the SNTP Parameter Description Setting range Default Menu path Server1 Server 1 Inactive Active Inactiv...

Страница 263: ...er2 Server 2 Inactive Active Inactive Device Para Time TimeSync SNTP IP Byte1 IP1 IP2 IP3 IP4 0 255 0 Device Para Time TimeSync SNTP IP Byte2 IP1 IP2 IP3 IP4 0 255 0 Device Para Time TimeSync SNTP IP...

Страница 264: ...SmallSyncs Service counter Total Number of very small Time Corrections 0 0 9999999999 Operation Count and RevData TimeSync SNTP NoOfNormSyncs Service counter Total Number of normal Time Corrections 0...

Страница 265: ...umServer2 Stratum of Server 2 0 0 9999999999 Operation Status display TimeSync SNTP SNTP Values Value Description Default Size Menu path Used Server Which Server is used for SNTP synchronization None...

Страница 266: ...EDR 3000 IM02602003E Value Description Default Size Menu path NetConn Quality of Network Connection GOOD SUFFICIENT BAD GOOD SUFFICENT BAD Operation Status display TimeSync SNTP www eaton com 254...

Страница 267: ...ion device supports IRIG B according to the IRIG STANDARD 200 04 This means that all time synchronization formats IRIG B00X IRIG B000 B001 B002 B003 B004 B005 B006 B007 are supported It is recommended...

Страница 268: ...as being active please proceed as follows To begin with check the IRIG B wiring Check if the correct IRIG B00X type is configured IRIG B Control Commands In addition to the date and time information...

Страница 269: ...eration Reset Global Protection Parameters of the IRIG B00X Parameter Description Setting range Default Menu path Function Permanent activation or deactivation of module element Inactive Active Inacti...

Страница 270: ...Signal10 Signal IRIG B Control Signal Control Signal11 Signal IRIG B Control Signal Control Signal12 Signal IRIG B Control Signal Control Signal13 Signal IRIG B Control Signal Control Signal14 Signal...

Страница 271: ...EDR 3000 IM02602003E Value Description Default Size Menu path Edges Edges 0 0 65535 Operation Count and RevData TimeSync IRIG B www eaton com 259...

Страница 272: ...ick the Date time icon within the operational data From the working window the User can now synchronize the date and time of the device with the PC i e that means that the device accepts the date and...

Страница 273: ...s to be established That means the User MUST first read out the IP address at the HMI of the device within menu Device para TCP IP then compare the IP address with the list If the addresses are identi...

Страница 274: ...on Reset Ack Comm Communication will be acknowledged Inactive Active Inactive Operation Reset Reboot Rebooting the device No Yes No Service General MaintMode Manually Arc Flash Reduction Maintenance S...

Страница 275: ...be executed In case all input functions are inactive the device will keep working with the Setting Group that was activated lastly Only available if PSet Switch PSS via Inp fct 1 n PSS Sys Maint Mode...

Страница 276: ...if the state of the assigned signal becomes true Only available if Remote Reset Active 1 n Assignment List Device Para Ex Acknowledge Scaling Display of the measured values as primary secondary or pe...

Страница 277: ...oup Protection Para PSet Switch Maint Mode I Module Input State Arc Flash Reduction Maintenance Switch Service Maint Mode System Module Signals Signal Description Reboot Signal Rebooting the device 1...

Страница 278: ...al Acknowledgment of the Relay Outputs Ack Counter Signal Reset of all Counters Ack Comm Signal Acknowledge Communication Ack TripCmd Signal Reset Trip Command Ack LED HMI Signal LEDs Acknowledgment H...

Страница 279: ...of the System Module Value Description Menu path Build Build Device Para Version Version Version Device Para Version Operating hours Cr Operating hours counter of the protective device Operation Coun...

Страница 280: ...atistical measured values Switch operating position in preparation State of device Time and date State of the device s digital inputs and Protection state pickups The master control system can give co...

Страница 281: ...e defining the period within which an inquiry from the master has to be answered Part 2 Hardware Connection For hardware connection to the control system there is an RS485 interface at the rear side o...

Страница 282: ...Setting a unit identifier is only necessary if a TCP network should be coupled to a RTU network If a different port than the default port 502 should be used please proceed as follows Choose Private wi...

Страница 283: ...Planning TCP 1 255 255 Device Para Modbus TCP Port Config TCP Port Configuration This parameter is to be set only if the default Modubs TCP Port should not be used Only available if Device Planning T...

Страница 284: ...call If there is no request message sent from Communication to the device after expiry of this time the device concludes a communication failure within the Communication system 1 3600s 10s Device Para...

Страница 285: ...ation Command Comm Cmd 3 Communication Command Comm Cmd 4 Communication Command Comm Cmd 5 Communication Command Comm Cmd 6 Communication Command Comm Cmd 7 Communication Command Comm Cmd 8 Communicat...

Страница 286: ...Number of Overrun Failures Physically corrupted Frame Only available if Device Planning RTU 0 0 9999999999 Operation Count and RevData Modbus NoOfParityErrors Total number of parity errors Physically...

Страница 287: ...out events is submitted between each IED Therefore each IED has to know about the functional capability of all other connected IEDs Each IEC 61850 capable device includes a description of its own func...

Страница 288: ...s and Wiring according to wiring scheme Commissioning steps for a substation with IEC 61850 environment 1 Parameter setting of the IEDs Ethernet installation TCP IP settings for the IEDs 2 IEC 61850 c...

Страница 289: ...1 Connect the device with your PC Notebook 2 Start Power Port E 3 Click on Receive data from Device in the menu Device 4 Click on IEC61850 in the menu Device Para 5 Click on the SCD icon in the IEC61...

Страница 290: ...IEC Communication and submit the changed parameter set into the device 10 Repeat Steps 1 through 9 for all devices connected to this IEC 61850 environment 11 If no error message occurs the configurati...

Страница 291: ...EDR 3000 IM02602003E Device Planning Parameters of the IEC 61850 Parameter Description Options Default Menu path Mode Mode Do not use Use Use Device Planning www eaton com 279...

Страница 292: ...or visualized via the SCD file to other devices within the IEC61850 substation 1 n Assignment List Device Para IEC61850 VirtualOutput3 Virtual Output This signal can be assigned or visualized via the...

Страница 293: ...signed or visualized via the SCD file to other devices within the IEC61850 substation 1 n Assignment List Device Para IEC61850 VirtualOutput12 Virtual Output This signal can be assigned or visualized...

Страница 294: ...assigned or visualized via the SCD file to other devices within the IEC61850 substation 1 n Assignment List Device Para IEC61850 VirtualOutput22 Virtual Output This signal can be assigned or visualize...

Страница 295: ...assigned or visualized via the SCD file to other devices within the IEC61850 substation 1 n Assignment List Device Para IEC61850 VirtualOutput30 Virtual Output This signal can be assigned or visualize...

Страница 296: ...Out8 I Module input state Binary state of the Virtual Output GGIO Device Para IEC61850 VirtOut9 I Module input state Binary state of the Virtual Output GGIO Device Para IEC61850 VirtOut10 I Module inp...

Страница 297: ...nput state Binary state of the Virtual Output GGIO Device Para IEC61850 VirtOut25 I Module input state Binary state of the Virtual Output GGIO Device Para IEC61850 VirtOut26 I Module input state Binar...

Страница 298: ...ual Input IEC61850 GGIO Ind VirtInp15 Signal Virtual Input IEC61850 GGIO Ind VirtInp16 Signal Virtual Input IEC61850 GGIO Ind VirtInp17 Signal Virtual Input IEC61850 GGIO Ind VirtInp18 Signal Virtual...

Страница 299: ...and RevData IEC61850 NoOfGooseTxAll Total Number of GOOSE messages that have been published by this device 0 0 9999999999 Operation Count and RevData IEC61850 NoOfGooseTxNew Total Number of new GOOSE...

Страница 300: ...al Number of correctly written values by this device 0 0 9999999999 Operation Count and RevData IEC61850 NoOfDataChangeNot ification Number of detected changes within the datasets that are published w...

Страница 301: ...of the GOOSE Publisher on or off Off Off On Error Operation Status display IEC61850 GooseSubscriberStat e State of the GOOSE Subscriber on or off Off Off On Error Operation Status display IEC61850 Mm...

Страница 302: ...e part of the Device Parameter tree By modifying the Device Parameters the User may depending on the type of device Configure digital inputs Assign LEDs Configure Relay Outputs Assign acknowledgment s...

Страница 303: ...lity for any personal or material damage as a result of incorrect planning Contact your Eaton Customer Service representative for more information The protection parameters include the following prote...

Страница 304: ...ey will be executed directly e g Resetting of a Counter State of the Module Inputs Module Inputs are part of the Device Parameter tree The State of the Module Input is context dependent By means of th...

Страница 305: ...0 s Active Inactive Active Inactive 0 In 1 n 0 s 0 05 n 1 n 0 s Active Inactive Active Inactive 0 In 1 n 0 s 0 05 n 1 n 0 s Active Inactive Active Inactive 0 In 1 n 0 s 0 05 n 1 n 0 s Active Inactive...

Страница 306: ...so be used to realize various special protective functions or to expand the existing function modules in a simple way without costly redesign the existing hardware or software platform The Adaptive Pa...

Страница 307: ...DI 8P X1 DI 2 Signal Digital Input DI 8P X1 DI 3 Signal Digital Input DI 8P X1 DI 4 Signal Digital Input DI 8P X1 DI 5 Signal Digital Input DI 8P X1 DI 6 Signal Digital Input DI 8P X1 DI 7 Signal Digi...

Страница 308: ...ut Signal Output of the logic gate Logic LE8 Timer Out Signal Timer Output Logic LE8 Out Signal Latched Output Q Logic LE8 Out inverted Signal Negated Latched Output Q NOT Logic LE9 Gate Out Signal Ou...

Страница 309: ...LE17 Timer Out Signal Timer Output Logic LE17 Out Signal Latched Output Q Logic LE17 Out inverted Signal Negated Latched Output Q NOT Logic LE18 Gate Out Signal Output of the logic gate Logic LE18 Tim...

Страница 310: ...LE26 Out Signal Latched Output Q Logic LE26 Out inverted Signal Negated Latched Output Q NOT Logic LE27 Gate Out Signal Output of the logic gate Logic LE27 Timer Out Signal Timer Output Logic LE27 Ou...

Страница 311: ...nverted Signal Negated Latched Output Q NOT Logic LE36 Gate Out Signal Output of the logic gate Logic LE36 Timer Out Signal Timer Output Logic LE36 Out Signal Latched Output Q Logic LE36 Out inverted...

Страница 312: ...ate Out Signal Output of the logic gate Logic LE45 Timer Out Signal Timer Output Logic LE45 Out Signal Latched Output Q Logic LE45 Out inverted Signal Negated Latched Output Q NOT Logic LE46 Gate Out...

Страница 313: ...LE54 Timer Out Signal Timer Output Logic LE54 Out Signal Latched Output Q Logic LE54 Out inverted Signal Negated Latched Output Q NOT Logic LE55 Gate Out Signal Output of the logic gate Logic LE55 Tim...

Страница 314: ...LE63 Out Signal Latched Output Q Logic LE63 Out inverted Signal Negated Latched Output Q NOT Logic LE64 Gate Out Signal Output of the logic gate Logic LE64 Timer Out Signal Timer Output Logic LE64 Ou...

Страница 315: ...nverted Signal Negated Latched Output Q NOT Logic LE73 Gate Out Signal Output of the logic gate Logic LE73 Timer Out Signal Timer Output Logic LE73 Out Signal Latched Output Q Logic LE73 Out inverted...

Страница 316: ...c LE79 Timer Out Signal Timer Output Logic LE79 Out Signal Latched Output Q Logic LE79 Out inverted Signal Negated Latched Output Q NOT Logic LE80 Gate Out Signal Output of the logic gate Logic LE80 T...

Страница 317: ...2 This password provides access to the reset and acknowledge options In addition to that it permits changing of protection settings and the configuration of the trip manager Control Lv1 This password...

Страница 318: ...e passwords have to be kept as a secret and to be known only by the authorized persons A lock symbol indicates in the upper right corner of the display if there are any access authorizations active at...

Страница 319: ...en the upper right corner of the display shows this symbol The passwords are part of the device fixed assignments That means passwords will not be overwritten if a parameter file is transmitted into a...

Страница 320: ...arameters and settings www eaton com 308 Supervisor Lv3 Device Configuration Read Only Lv0 Read Only Prot Lv1 Reset Ack Control Lv1 Control Prot Lv2 Protection Settings Control Lv2 Control Settings Ac...

Страница 321: ...s authorizations are currently unlocked As soon as there is an unlocked access area authorization above Read Only Lv0 this will be indicated by an unlocked lock symbol within the upper right corner of...

Страница 322: ...to deactivate passwords during commissioning It is not allowed to use this feature for other purposes than commissioning In order to deactivate the password protection replace the existing password w...

Страница 323: ...he corresponding Adaptive Set 5 Set the modified parameter for the selected Adaptive Set Application Example The tripping time t for the 50 1 element of Parameter Set 1 should be desensitized reduced...

Страница 324: ...on can easily be realized using the Adaptive Parameter features mentioned previously The standard time overcurrent protection element e g 51P should trip instantaneously in case of SOTF condition If t...

Страница 325: ...that desensitizes the overcurrent protection By means of Adaptive Parameter Sets an Adaptive Auto Reclosure can be realized After a reclosure attempt the tripping thresholds or tripping curves of the...

Страница 326: ...2 This password provides access to the reset and acknowledge options In addition to that it permits changing of protection settings and the configuration of the trip manager Control Lv1 This password...

Страница 327: ...s not active within the parameter setting mode for a longer time can be set between 20 3600 seconds it changes into Read Only Lv0 mode automatically This parameter t max Edit can be modified within me...

Страница 328: ...symbol will be shown in the upper right corner of the display As soon as there are any access authorizations active above the Read Only Lv0 level the upper right corner of the display will show an unl...

Страница 329: ...n if a parameter file is transmitted into a device Existing passwords are persistent assined to a device If an offline created parameter file is transmitted into a device or if a parameter file is tra...

Страница 330: ...urrently unlocked As soon as there is an unlocked access area authorization above Read Only Lv0 this will be indicated by an unlocked lock symbol within the upper right corner of the device display ww...

Страница 331: ...Passwords during Commissioning It is possible optionally to deactivate passwords during commissioning It is not allowed to use this feature for other purposes than commissioning In order to deactivat...

Страница 332: ...d the new password twice Confirm the changes by a cklick on OK Password Entry at the Panel Passwords can be entered by way of the Softkeys 1 2 3 4 Example For password 3244 press successively Softkey...

Страница 333: ...ed access authorization is available Confirm the Softkey Wrench in order to edit the parameter Change the parameter Now you can save the change you made and have them adopted by the system or change a...

Страница 334: ...ameter changes If the device detects an implausibility this is indicated by a question mark in front of the respective parameter In order to make things easier to follow up especially where complex pa...

Страница 335: ...hanges by pressing the Yes Softkey or dismiss by pressing No To change additional parameters and save afterwards move to other parameters and change them A star symbol in front of the changed paramete...

Страница 336: ...by the question mark plausibility trace This makes it possible to control or follow from the main menu level at any time where implausibilities are intended to be saved In addition to the question mar...

Страница 337: ...red The User will be asked for the Supervisor Lv3 password Example3 A Prot Lv1 parameter and a Prot Lv2 parameter as well as a Ctrl Lv2 parameter have been changed and should be transferred The User w...

Страница 338: ...ettings the software monitors constantly all temporary saved parameter changes If it detects an implausibility this is indicated by a question mark in front of the respective parameter In order to mak...

Страница 339: ...ameters in the popup window Confirm the inquiry Shall The Data Be Saved Locally with Yes recommended Select a suitable storing location on your hard disk Confirm the chosen storing location by clickin...

Страница 340: ...That means if there is more or less than one request signal active no switch over will be executed Example DI3 is assigned onto Parameter set 1 DI3 is active 1 DI4 is assigned onto Parameter set 2 DI...

Страница 341: ...ed Output Q NOT Logic LE2 Gate Out Signal Output of the logic gate Logic LE2 Timer Out Signal Timer Output Logic LE2 Out Signal Latched Output Q Logic LE2 Out inverted Signal Negated Latched Output Q...

Страница 342: ...ut Signal Latched Output Q Logic LE10 Out inverted Signal Negated Latched Output Q NOT Logic LE11 Gate Out Signal Output of the logic gate Logic LE11 Timer Out Signal Timer Output Logic LE11 Out Signa...

Страница 343: ...nverted Signal Negated Latched Output Q NOT Logic LE20 Gate Out Signal Output of the logic gate Logic LE20 Timer Out Signal Timer Output Logic LE20 Out Signal Latched Output Q Logic LE20 Out inverted...

Страница 344: ...ate Out Signal Output of the logic gate Logic LE29 Timer Out Signal Timer Output Logic LE29 Out Signal Latched Output Q Logic LE29 Out inverted Signal Negated Latched Output Q NOT Logic LE30 Gate Out...

Страница 345: ...LE38 Timer Out Signal Timer Output Logic LE38 Out Signal Latched Output Q Logic LE38 Out inverted Signal Negated Latched Output Q NOT Logic LE39 Gate Out Signal Output of the logic gate Logic LE39 Tim...

Страница 346: ...LE47 Out Signal Latched Output Q Logic LE47 Out inverted Signal Negated Latched Output Q NOT Logic LE48 Gate Out Signal Output of the logic gate Logic LE48 Timer Out Signal Timer Output Logic LE48 Ou...

Страница 347: ...nverted Signal Negated Latched Output Q NOT Logic LE57 Gate Out Signal Output of the logic gate Logic LE57 Timer Out Signal Timer Output Logic LE57 Out Signal Latched Output Q Logic LE57 Out inverted...

Страница 348: ...ate Out Signal Output of the logic gate Logic LE66 Timer Out Signal Timer Output Logic LE66 Out Signal Latched Output Q Logic LE66 Out inverted Signal Negated Latched Output Q NOT Logic LE67 Gate Out...

Страница 349: ...LE75 Timer Out Signal Timer Output Logic LE75 Out Signal Latched Output Q Logic LE75 Out inverted Signal Negated Latched Output Q NOT Logic LE76 Gate Out Signal Output of the logic gate Logic LE76 Tim...

Страница 350: ...0 Out Signal Latched Output Q Logic LE80 Out inverted Signal Negated Latched Output Q NOT Sys Maint Mode Active Signal Arc Flash Reduction Maintenance Active Sys Maint Mode Inactive Signal Arc Flash R...

Страница 351: ...ick Receive Data From The Device in the Device menu Double click the Protection Para icon in the navigation tree Double click the P Set Switch within the protection parameters To configure the Setting...

Страница 352: ...ce parameters by selecting File Save as Select Copy Parameter Sets out of the Edit menu Then define both source and destination of the parameter sets to be copied source copy from destination copy to...

Страница 353: ...r device file against a file on the hard disk The precondition is that the versions and type of devices match To compare the parameter files please proceed as follows Click on Compare with a Parameter...

Страница 354: ...In order to convert a parameter file please proceed as follows If PowerPort E is not in operation please start the application Open a parameter file or load the parameters from a device that should b...

Страница 355: ...he Program Mode is used for Motor Protection devices the user has the following options Motor Stop Lock parameter changes if the motor is not in the STOP state This ensures that parameter changes can...

Страница 356: ...and the mains operational method like frequency primary and secondary values and the star point treatment General System Parameters Parameter Description Setting range Default Menu path Phase Sequenc...

Страница 357: ...s parameter defines the primary nominal current of the connected ground current transformer If the ground current is measured via the Residual connection the primary value of the phase current transfo...

Страница 358: ...Modules On or Off Each of the modules can be switched On or Off permanently This is achieved when the Function parameter is set to Active or Inactive in the respective module Activating or Deactivatin...

Страница 359: ...modules can be blocked from an external signal In this case external does not only mean from outside the device but also from outside the module Not only real external signals are permitted to be use...

Страница 360: ...of a Protection Module www eaton com 348 Inactive Active Name Blo TripCmd Inactive Active Name ExBlo TripCmd Fc 1 n Assignment List Name ExBlo TripCmd Name ExBlo TripCmd Trip Blockings Name All Module...

Страница 361: ...ked Name ExBlo1 I 1 n Assignment List Name ExBlo 2 Name ExBlo2 I Name A ll Modules That A re Blockable 1 2 Please Refer to Diagram Prot OR AND All protective elements will be blocked that are using fu...

Страница 362: ...t Name ExBlo 1 1 n Assignment List Name Rvs Blo Name ExBlo Name Rvs Blo B lockings Th e G en eral Protection module is no t deact ivate d or blocke d Name I 1 n IG 1 n Name ExBlo1 I Name Rvs Blo I 1 n...

Страница 363: ...In such a case the protective function is Inactive Protection Active If the master Protection module was activated and a blockade for this module was not activated respectively the assigned blocking s...

Страница 364: ...1 Prot ExBlo Prot Active 1 n Assignment List Prot ExBlo 2 Prot ExBlo1 I Prot ExBlo2 I AND Prot Available Measured Values OK At the moment no parameter is being changed except parameter set parameters...

Страница 365: ...signal OR ed from all protection elements Prot Trip is the collective Trip signal OR ed from all protection elements and etc The Tripping commands of the protection elements have to be fed to the Bkr...

Страница 366: ...EDR 3000 IM02602003E www eaton com 354 Prot Trip Name Trip Name Each trip of an active trip authorized protection module will lead to a general trip Name Trip Prot Trip Name n Trip 15 15 15 OR...

Страница 367: ...3E www eaton com 355 Prot Pickup Prot Pickup Name Pickup Name Pickup Name Pickup Name Each pickup of a module except from supervision modules but including BF will lead to a general pickup collective...

Страница 368: ...e will lead to a phase selective general trip 19c 19d 23 OR Prot Trip Phase A 50P 1 n Trip Phase A 51P 1 n Trip Phase A V n Trip Phase A 16a 16b 20 OR Prot Trip Phase B 50P 1 n Trip Phase B 51P 1 n Tr...

Страница 369: ...o a phase selective general pickup collective pickup 27c 27d 31 OR Prot Pickup Phase B 50P 1 n Pickup IB V n Pickup Phase B 25a 29 OR 51P 1 n Pickup IB 25b Prot Pickup Phase C 50P 1 n Pickup IC V n Pi...

Страница 370: ...l protection functionality of the device Inactive Active Inactive Protection Para Global Prot Para Prot ExBlo1 If external blocking of this module is activated allowed the global protection functional...

Страница 371: ...ive Signal Active ExBlo Signal External Blocking Pickup Phase A Signal General Pickup Phase A Pickup Phase B Signal General Pickup Phase B Pickup Phase C Signal General Pickup Phase C Pickup IX or IR...

Страница 372: ...FaultNo Waveform No No of grid faults Number of grid faults A grid fault e g a short circuit might cause several faults with trip and autoreclosing each fault being identified by an increased fault nu...

Страница 373: ...isplay in order to verify and analyze each of the steps NOTICE The Syn check function is not available on EMR XXXX devices The User has to establish the wiring of the Position Indicators of the Breake...

Страница 374: ...g general settings are possible None No switching authority switching not allowed Local Switching only via push buttons at the panel Remote Switching only via SCADA digital inputs or internal signals...

Страница 375: ...ons e g QA1 QA2 instead of SG x will be taken from the single line diagram configuration file The configuration file includes the single line diagram and the switchgear properties Switchgear propertie...

Страница 376: ...lidation functions As a result the breaker position will be detected by the following signals Pos CLOSE Pos OPEN Pos Indeterm Pos Disturb and Pos State 0 1 2 or 3 CLOSE initiated Supervision When a CL...

Страница 377: ...Indeterm Pos Disturb Breaker State 0 0 0 0 1 while a Moving timer is running 0 while a Moving timer is running 0 Intermediate 1 1 0 0 1 while a Moving timer is running 0 while a Moving timer is runni...

Страница 378: ...start the moving time the position indication indicates an INTERMEDIATE position during this time interval When the switchgear reaches the end position indicated by the Pos CLOSE signal the moving ti...

Страница 379: ...ts the moving time Because the device does not receive a close signal by the breaker it assumes that the breaker is in close position after the moving time has elapsed The following table shows how br...

Страница 380: ...ipable Elements Name Description No assignment 50P 1 TripCmd Signal Trip Command 50P 2 TripCmd Signal Trip Command 50P 3 TripCmd Signal Trip Command 51P 1 TripCmd Signal Trip Command 51P 2 TripCmd Sig...

Страница 381: ...e a k e r Breaker OPEN Command Breaker CLOSE Command Protection Trip Command Position Indication OPEN CLOSE Indeterminated Disturbed Trip Command 50P x Trip Command 51P x Trip Command XX x I P r o te...

Страница 382: ...ctive Bkr Latched R TripCmd Cr Bkr Res TripCmdCr Name TripCmd Name TripCmd Name TripCmd Name TripCmd Acknowledge HMI Acknowledge 1 n Assignment List Acknowledge Comm Name Each trip of an active trip a...

Страница 383: ...corresponding switching direction can be inhibited via these inputs Please note The Protection Trip commands and the reclosure command of the auto reclosure module will be issued without interlocking...

Страница 384: ...Manual Switch Command Auto reclosure issues the following commands Automatic Switch Command Protection issues Trip Command e g 50P Interlockings AND Trip command assigned and configured within the Tr...

Страница 385: ...d will be overwritten by an upcoming OPEN command An applied OPEN command will not be overwritten by an upcoming CLOSE command that means the OPEN command is dominant Synchronous Switching If a signal...

Страница 386: ...Breaker Parameter Description Setting range Default Menu path Res Bwear Sl Breaker Resetting the slow breaker alarm Inactive Active Inactive Operation Reset Ack TripCmd Acknowledge Trip Command Inact...

Страница 387: ...closure AR e g as a trigger signal 1 n Dig Inputs Control Bkr Pos Indicatrs Wirng Interl CLOSE1 Interlocking of the CLOSE command 1 n Assignment List Wired Inputs Bkr Trouble I Control Bkr Interlockin...

Страница 388: ...ager Trigger2 Open Command to the Breaker if the state of the assigned signal becomes true 1 n Trip Cmds 50P 2 TripCmd Control Bkr Trip Manager Trigger3 Open Command to the Breaker if the state of the...

Страница 389: ...ate of the assigned signal becomes true 1 n Trip Cmds Control Bkr Trip Manager Trigger13 Open Command to the Breaker if the state of the assigned signal becomes true 1 n Trip Cmds Control Bkr Trip Man...

Страница 390: ...Cmds Control Bkr Trip Manager Synchronism Synchronism 1 n In SyncList Control Bkr Synchron Switchg t MaxSyncSuperv Synchron Run timer Max time allowed for synchronizing process after a close initiate...

Страница 391: ...he module input Acknowledgment Signal only for automatic acknowledgment Module input signal Control Bkr Trip Manager Interl CLOSE1 I State of the module input Interlocking of the CLOSE command Control...

Страница 392: ...inputs are active Interl OPEN Signal One or more IL_Open inputs are active CES succesf Signal Command Execution Supervision Switching command executed successfully CES Disturbed Signal Command Executi...

Страница 393: ...Cmd Signal CLOSE command issued to the switchgear Depending on the setting the signal may include the CLOSE command of the Prot module OPEN Cmd Signal OPEN command issued to the switchgear Depending...

Страница 394: ...softkeys and press the right arrow softkey button 3 Select the Control menu by using the up or down softkeys and press the right arrow softkey button 4 A symbol for the switchgear and its status ON O...

Страница 395: ...Authority Remote SG Indeterm Minimum one Switchgear is moving Position cannot be determined SG Disturb Minimum one Switchgear is disturbed Counters of the Switching Authority Parameter Description CES...

Страница 396: ...nance is mandatory now Breaker Wear Curve Monitoring of total CLOSE OPEN cycles and alarm for max allowed CLOSE OPEN cycles per hour Slow Breaker Alarm An increase of the closing or opening time of th...

Страница 397: ...ear Each point has two settings the interrupt current in kilo amperes and the allowed operation counts The first point is always the number of allowed operations if no current is flowing zero current...

Страница 398: ...an alarm will be issued The breaker maintenance curve is to be taken from the technical data sheet of the breaker manufactor By means of the available points this curve is to be replicated Inactive Ac...

Страница 399: ...Only available if Bwear Curve Fc Active 1 32000 1900 Control Bkr Bwear Current5 Interrupted Current Level 5 Only available if Bwear Curve Fc Active 0 00 2000 00kA 5 00kA Control Bkr Bwear Count5 Open...

Страница 400: ...Control Bkr Bwear Current9 Interrupted Current Level 9 Only available if Bwear Curve Fc Active 0 00 2000 00kA 20 00kA Control Bkr Bwear Count9 Open Counts Allowed 9 Only available if Bwear Curve Fc A...

Страница 401: ...Intr trip Signal Maximum permissible Summation of the interrupting tripping currents exceeded in at least one phase Res TripCmdCr Signal Resetting of the Counter total number of trip commands Res Isum...

Страница 402: ...ase 0 00A 0 00 1000 00A Operation Count and RevData Control Bkr Isum trip IB Summation of the tripping currents phase 0 00A 0 00 1000 00A Operation Count and RevData Control Bkr Isum trip IC Summation...

Страница 403: ...y Resetting of the CB OPEN capacity 100 means that the breaker is to be maintenanced Inactive Active Inactive Operation Reset Trigger signals for Sync check NOTICE The Syn check function is not availa...

Страница 404: ...Signal Timer Output Logic LE4 Out Signal Latched Output Q Logic LE4 Out inverted Signal Negated Latched Output Q NOT Logic LE5 Gate Out Signal Output of the logic gate Logic LE5 Timer Out Signal Timer...

Страница 405: ...LE13 Out Signal Latched Output Q Logic LE13 Out inverted Signal Negated Latched Output Q NOT Logic LE14 Gate Out Signal Output of the logic gate Logic LE14 Timer Out Signal Timer Output Logic LE14 Out...

Страница 406: ...nverted Signal Negated Latched Output Q NOT Logic LE23 Gate Out Signal Output of the logic gate Logic LE23 Timer Out Signal Timer Output Logic LE23 Out Signal Latched Output Q Logic LE23 Out inverted...

Страница 407: ...ate Out Signal Output of the logic gate Logic LE32 Timer Out Signal Timer Output Logic LE32 Out Signal Latched Output Q Logic LE32 Out inverted Signal Negated Latched Output Q NOT Logic LE33 Gate Out...

Страница 408: ...LE41 Timer Out Signal Timer Output Logic LE41 Out Signal Latched Output Q Logic LE41 Out inverted Signal Negated Latched Output Q NOT Logic LE42 Gate Out Signal Output of the logic gate Logic LE42 Tim...

Страница 409: ...LE50 Out Signal Latched Output Q Logic LE50 Out inverted Signal Negated Latched Output Q NOT Logic LE51 Gate Out Signal Output of the logic gate Logic LE51 Timer Out Signal Timer Output Logic LE51 Ou...

Страница 410: ...nverted Signal Negated Latched Output Q NOT Logic LE60 Gate Out Signal Output of the logic gate Logic LE60 Timer Out Signal Timer Output Logic LE60 Out Signal Latched Output Q Logic LE60 Out inverted...

Страница 411: ...ate Out Signal Output of the logic gate Logic LE69 Timer Out Signal Timer Output Logic LE69 Out Signal Latched Output Q Logic LE69 Out inverted Signal Negated Latched Output Q NOT Logic LE70 Gate Out...

Страница 412: ...ate Out Signal Output of the logic gate Logic LE77 Timer Out Signal Timer Output Logic LE77 Out Signal Latched Output Q Logic LE77 Out inverted Signal Negated Latched Output Q NOT Logic LE78 Gate Out...

Страница 413: ...itching authority and interlockings can be set By means of the softkey SG it can be switched to the menu SG In this menu specific settings for the switch gear can be done This page can be directly cal...

Страница 414: ...l or Local and Remote Now it is possible to execute switching commands at the HMI Push the right arrow softkey to get to the control page The breaker is opened therefore it can be closed only After pu...

Страница 415: ...chgear It will be shown on the display when the switchgear reaches the new end position Further possible switching operations OPEN will be displayed by softkeys Notice For the case the switchgear does...

Страница 416: ...ion All overcurrent protective elements are identically structured For each element the following characteristic is available DEFT definite time Explanation This element offers a criterion setting The...

Страница 417: ...ickup Please Refer to Diagram Trip Blockings Inactive Active Name IH2 Blo Element is not deactivated and no active blocking signals AND AND AND Name IH2 Blo Tripping com mand deactivated or blocked 5...

Страница 418: ...llowed within a parameter set and if the state of the assigned signal is true 1 n Assignment List Protection Para Global Prot Para I Prot 50P 1 ExBlo TripCmd External blocking of the Trip Command of t...

Страница 419: ...etting range Default Menu path AdaptSet 3 Assignment Adaptive Parameter 3 AdaptSet Protection Para Global Prot Para I Prot 50P 1 AdaptSet 4 Assignment Adaptive Parameter 4 AdaptSet Protection Para Glo...

Страница 420: ...rameterized Rvs Blo Fc active Inactive Active Inactive Protection Para 1 4 I Prot 50P 1 Blo TripCmd Permanent blocking of the Trip Command of the module element Inactive Active Inactive Protection Par...

Страница 421: ...602003E Parameter Description Setting range Default Menu path t Tripping delay Only available if Characteristic DEFT 0 00 300 00s 50P 1 0s 50P 2 0 25s 50P 3 0 25s Protection Para 1 4 I Prot 50P 1 www...

Страница 422: ...ection Para Global Prot Para I Prot 50P 1 Rvs Blo I Module Input State Reverse Blocking Protection Para Global Prot Para I Prot 50P 1 AdaptSet1 I Module Input State Adaptive Parameter1 Protection Para...

Страница 423: ...B Signal Pickup IB Pickup IC Signal Pickup IC Pickup Signal Pickup Trip Phase A Signal General Trip Phase A Trip Phase B Signal General Trip Phase B Trip Phase C Signal General Trip Phase C Trip Signa...

Страница 424: ...e relevant documentation provided by the breaker manufacturer Necessary means Current source Current meters and Timer Procedures Testing the threshold values 3 x single phase and 1 x three phase For e...

Страница 425: ...to devices which are equipped with Inrush protection All overcurrent protective elements are identically structured For each element the following characteristics are available NINV IEC XInv VINV IEC...

Страница 426: ...ive Name IH2 Blo Element is not deactivated and no active blocking signals AND AND AND Name IH2 Blo Imax Tripping command deactivated or blocked 5 6 7 4 3 Please Refer to Diagram IH2 Please Refer to D...

Страница 427: ...ted allowed within a parameter set and if the state of the assigned signal is true 1 n Assignment List Protection Para Global Prot Para I Prot 51P 1 ExBlo TripCmd External blocking of the Trip Command...

Страница 428: ...etting range Default Menu path AdaptSet 3 Assignment Adaptive Parameter 3 AdaptSet Protection Para Global Prot Para I Prot 51P 1 AdaptSet 4 Assignment Adaptive Parameter 4 AdaptSet Protection Para Glo...

Страница 429: ...hose modules element are blocked that are parameterized Rvs Blo Fc active Inactive Active Inactive Protection Para 1 4 I Prot 51P 1 Blo TripCmd Permanent blocking of the Trip Command of the module ele...

Страница 430: ...Time multiplier tripping characteristic factor The setting range depends on the selected tripping curve 0 02 20 00 51P 1 1 51P 2 2 51P 3 3 Protection Para 1 4 I Prot 51P 1 Reset Mode Reset Mode Insta...

Страница 431: ...ection Para Global Prot Para I Prot 51P 1 Rvs Blo I Module Input State Reverse Blocking Protection Para Global Prot Para I Prot 51P 1 AdaptSet1 I Module Input State Adaptive Parameter1 Protection Para...

Страница 432: ...B Signal Pickup IB Pickup IC Signal Pickup IC Pickup Signal Pickup Trip Phase A Signal General Trip Phase A Trip Phase B Signal General Trip Phase B Trip Phase C Signal General Trip Phase C Trip Signa...

Страница 433: ...relevant documentation provided by the breaker manufacturer Necessary means Current source Current meters and Timer Procedure Testing the threshold values 3 x single phase and 1 x three phase For eac...

Страница 434: ...uctured For each element the following characteristics are available DEFT definite time For tripping curves please refer to the Appendix Instantaneous Current Curves Ground Current Measured section Th...

Страница 435: ...tive blocking signals Tripping command deactivated or blocked IH2 Blo IG Inactive Active Name IGH2 Blo AND Name Pickup Name IGH2 Blo 8 4 3 Please Refer to Diagram IH2 14 27a 19a AND AND AND DEFT Name...

Страница 436: ...a parameter set and if the state of the assigned signal is true 1 n Assignment List Protection Para Global Prot Para I Prot 50X 1 ExBlo TripCmd External blocking of the Trip Command of the module the...

Страница 437: ...etting range Default Menu path AdaptSet 3 Assignment Adaptive Parameter 3 AdaptSet Protection Para Global Prot Para I Prot 50X 1 AdaptSet 4 Assignment Adaptive Parameter 4 AdaptSet Protection Para Glo...

Страница 438: ...on parameter If the signal becomes true those modules element are blocked that are parameterized Rvs Blo Fc active Inactive Active Inactive Protection Para 1 4 I Prot 50X 1 Blo TripCmd Permanent block...

Страница 439: ...u path Pickup sensitive If the pickup value is exceeded the module element will be started 0 002 2 000In 0 02In Protection Para 1 4 I Prot 50X 1 t Tripping delay Only available if Characteristic DEFT...

Страница 440: ...mand Protection Para Global Prot Para I Prot 50X 1 Rvs Blo I Module Input State Reverse Blocking Protection Para Global Prot Para I Prot 50X 1 AdaptSet1 I Module Input State Adaptive Parameter1 Protec...

Страница 441: ...and blocked ExBlo TripCmd Signal External Blocking of the Trip Command Pickup Signal Pickup IX or IR Trip Signal Trip TripCmd Signal Trip Command Active AdaptSet Active Adaptive Parameter DefaultSet S...

Страница 442: ...00 IM02602003E Commissioning Ground Fault Protection Non directional ANSI 50X Please test the non directional ground overcurrent analog to the non directional phase overcurrent protection www eaton co...

Страница 443: ...MINV ANSI XInv VINV ANSI XInv EINV ANSI XInv Thermal Flat IT I2T and I4T For tripping curves please refer to the Appendix Time Current Curves Ground Current section The ground current can be measured...

Страница 444: ...activated or blocked IH2 Blo IG Inactive Active Name IGH2 Blo AND Name Pickup Name IGH2 Blo 8 4 3 Please Refer to Diagram IH2 14 27b 19b AND AND AND IX Measured Fund RMS Name Criterion 51X 1 n Name 51...

Страница 445: ...ated allowed within a parameter set and if the state of the assigned signal is true 1 n Assignment List Protection Para Global Prot Para I Prot 51X 1 ExBlo TripCmd External blocking of the Trip Comman...

Страница 446: ...etting range Default Menu path AdaptSet 3 Assignment Adaptive Parameter 3 AdaptSet Protection Para Global Prot Para I Prot 51X 1 AdaptSet 4 Assignment Adaptive Parameter 4 AdaptSet Protection Para Glo...

Страница 447: ...rotection parameter If the signal becomes true those modules element are blocked that are parameterized Rvs Blo Fc active Inactive Active Inactive Protection Para 1 4 I Prot 51X 1 Blo TripCmd Permanen...

Страница 448: ...at IT I2T I4T ANSI MINV Protection Para 1 4 I Prot 51X 1 t multiplier Time multiplier tripping characteristic factor The setting range depends on the selected tripping curve 0 02 20 00 51X 1 1 51X 2 2...

Страница 449: ...mand Protection Para Global Prot Para I Prot 51X 1 Rvs Blo I Module Input State Reverse Blocking Protection Para Global Prot Para I Prot 51X 1 AdaptSet1 I Module Input State Adaptive Parameter1 Protec...

Страница 450: ...and blocked ExBlo TripCmd Signal External Blocking of the Trip Command Pickup Signal Pickup IX or IR Trip Signal Trip TripCmd Signal Trip Command Active AdaptSet Active Adaptive Parameter DefaultSet S...

Страница 451: ...00 IM02602003E Commissioning Ground Fault Protection Non directional ANSI 51X Please test the non directional ground overcurrent analog to the non directional phase overcurrent protection www eaton co...

Страница 452: ...structured For each element the following characteristics are available DEFT definite time For tripping curves please refer to the Appendix Instantaneous Current Curves Ground Current Calculated sect...

Страница 453: ...ipping command deactivated or blocked IH2 Blo IG Inactive Active Name IGH2 Blo AND Name Pickup Name IGH2 Blo 8 4 3 Please Refer to Diagram IH2 14 27c 19c AND AND AND Fund RMS Name Criterion 50R 1 n Na...

Страница 454: ...a parameter set and if the state of the assigned signal is true 1 n Assignment List Protection Para Global Prot Para I Prot 50R 1 ExBlo TripCmd External blocking of the Trip Command of the module the...

Страница 455: ...etting range Default Menu path AdaptSet 3 Assignment Adaptive Parameter 3 AdaptSet Protection Para Global Prot Para I Prot 50R 1 AdaptSet 4 Assignment Adaptive Parameter 4 AdaptSet Protection Para Glo...

Страница 456: ...on parameter If the signal becomes true those modules element are blocked that are parameterized Rvs Blo Fc active Inactive Active Inactive Protection Para 1 4 I Prot 50R 1 Blo TripCmd Permanent block...

Страница 457: ...EDR 3000 IM02602003E Parameter Description Setting range Default Menu path t Tripping delay Only available if Characteristic DEFT 0 00 300 00s 0 5s Protection Para 1 4 I Prot 50R 1 www eaton com 445...

Страница 458: ...mand Protection Para Global Prot Para I Prot 50R 1 Rvs Blo I Module Input State Reverse Blocking Protection Para Global Prot Para I Prot 50R 1 AdaptSet1 I Module Input State Adaptive Parameter1 Protec...

Страница 459: ...and blocked ExBlo TripCmd Signal External Blocking of the Trip Command Pickup Signal Pickup IX or IR Trip Signal Trip TripCmd Signal Trip Command Active AdaptSet Active Adaptive Parameter DefaultSet S...

Страница 460: ...02602003E Commissioning Ground Fault Protection Non directional ANSI 50R Please test the non directional ground overcurrent using the procedure for non directional phase overcurrent protection www eat...

Страница 461: ...v MINV ANSI XInv VINV ANSI XInv EINV ANSI XInv Thermal Flat IT I2T and I4T For tripping curves please refer to the Appendix Time Current Curves Ground Current section The ground current can be measure...

Страница 462: ...ctivated or blocked IH2 Blo IG Inactive Active Name IGH2 Blo AND Name Pickup Name IGH2 Blo 8 4 3 Please Refer to Diagram IH2 14 27d 19d AND AND AND Fund RMS Name Criterion INV Name t reset Name t mult...

Страница 463: ...ated allowed within a parameter set and if the state of the assigned signal is true 1 n Assignment List Protection Para Global Prot Para I Prot 51R 1 ExBlo TripCmd External blocking of the Trip Comman...

Страница 464: ...etting range Default Menu path AdaptSet 3 Assignment Adaptive Parameter 3 AdaptSet Protection Para Global Prot Para I Prot 51R 1 AdaptSet 4 Assignment Adaptive Parameter 4 AdaptSet Protection Para Glo...

Страница 465: ...parameter If the signal becomes true those modules element are blocked that are parameterized Rvs Blo Fc active Inactive Active Inactive Protection Para 1 4 I Prot 51R 1 Blo TripCmd Permanent blockin...

Страница 466: ...Time multiplier tripping characteristic factor The setting range depends on the selected tripping curve 0 02 20 00 51R 1 1 51R 2 2 Protection Para 1 4 I Prot 51R 1 Reset Mode Reset Mode Instantaneous...

Страница 467: ...mand Protection Para Global Prot Para I Prot 51R 1 Rvs Blo I Module Input State Reverse Blocking Protection Para Global Prot Para I Prot 51R 1 AdaptSet1 I Module Input State Adaptive Parameter1 Protec...

Страница 468: ...and blocked ExBlo TripCmd Signal External Blocking of the Trip Command Pickup Signal Pickup IX or IR Trip Signal Trip TripCmd Signal Trip Command Active AdaptSet Active Adaptive Parameter DefaultSet S...

Страница 469: ...00 IM02602003E Commissioning Ground Fault Protection Non directional ANSI 51R Please test the non directional ground overcurrent analog to the non directional phase overcurrent protection www eaton co...

Страница 470: ...ductors between the upstream and downstream breakers it is ideal for the upstream breaker to trip with no time delay This is the feature provided by Zone Selective Interlocking The zone interlocking i...

Страница 471: ...ignal only possible by absence of zone interlocking INPUT signals Configurable zone interlocking trip functions protective functions serve as zone interlocking trip functions Zone interlocking trip fu...

Страница 472: ...EDR 3000 IM02602003E Device Planning Parameters of the Zone Interlocking Parameter Description Options Default Menu path Mode Mode Use Use Device Planning www eaton com 460...

Страница 473: ...sent to the upstream device if a breaker failure on downstream device is detected Parameter Description Setting range Default Menu path ExBlo1 External blocking of the module if blocking is activated...

Страница 474: ...ocking application is applied to an upstream device main breaker or Zone 1 the settings in the TRIP group should be programmed accordingly If the zone interlocking application is only used for a downs...

Страница 475: ...tings ExBlo TripCmd Fc Activate allow or inactivate disallow blocking of the module element This parameter is only effective if a signal is assigned to the corresponding global protection parameter If...

Страница 476: ...rent protective function elements serve as the Phase Zone Interlock OUTPUT start functions 51P 1 50P 1 and 50P 2 The following current protective function serves as the Ground Zone Interlock OUTPUT st...

Страница 477: ...2602003E www eaton com 465 ZI OUT Zone Interlocking OUTPUT Logic Timing STARTED STANDBY TRIPPED RESET STANDBY STATE TRANSFER 51P 1 Trip 51P 1 Pickup ZI Bkr Blo t t 0 1 0 1 t 0 1 t 0 1 t 0 1 Reset Time...

Страница 478: ...ripCmd 50X 1 Pickup 51X 1 Pickup 50X 2 Pickup 50R 1 Pickup 51R 1 Pickup 50R 2 Pickup 50X 1 TripCmd 51X 1 TripCmd 50X 2 TripCmd 50R 1 TripCmd 51R 1 TripCmd 50R 2 TripCmd Active ZI OUT Fc Inactive BF Tr...

Страница 479: ...llowing overcurrent protection elements trigger Phase Zone Interlock trip functions 1 5 51P 1 50P 1 and 50P 2 The following overcurrent protection elements trigger Ground Zone Interlock trip functions...

Страница 480: ...03E www eaton com 468 Zone Interlocking TRIP Logic Timing STARTED STANDBY TRIPPED STANDBY INTERLOCKED STANDBY ZI Trip STATE TRANSFER 51P 1 Pickup ZI Pickup t t 0 1 0 1 t 0 1 t 0 1 t 0 1 Trip Delay Tim...

Страница 481: ...kup 50R 1 Pickup 51R 1 Pickup 50R 2 Pickup Active Trip Inactive ZI Ground Pickup ZI Phase Pickup ZI Phase Trip ZI Ground Trip ZI Trip ZI IN ZI Zone Trip Please Refer to Diagram Blockings 2 Element is...

Страница 482: ...o1 I Module Input State External Blocking1 Protection Para Global Prot Para ZI ExBlo2 I Module Input State External Blocking2 Protection Para Global Prot Para ZI ExBlo TripCmd I Module Input State Ext...

Страница 483: ...up Signal Zone Interlocking Phase Pickup Phase Trip Signal Zone Interlocking Phase Trip Ground Pickup Signal Zone Interlocking Ground Pickup Ground Trip Signal Zone Interlocking Ground Trip Pickup Sig...

Страница 484: ...onic inputs only The zone interlocking connection between relays is done by means of a twisted shielded cable Downstream zone interlock outputs may be paralleled from up to ten devices FP 5000 or DT 3...

Страница 485: ...4 2 Out In Com X2 13 14 15 Shield Out Com Zone 2 16 17 18 Shield In Com EDR X000 Zone 3 J3 FP X000 1 4 2 Out In Com DT 3000 13 14 15 Out In Out 16 18 In Com Ground Phase J3 FP X000 1 4 2 Out In Com X...

Страница 486: ...such as an FP5000 DT3000 etc As an upstream device the terminals Phase Ground IN should be connected to the OUT terminals of up to ten downstream device s by means of a dedicated cable wired in paral...

Страница 487: ...2 for Device EDR 4000 EDR 5000 EMR 4000 EMR 5000 EGR 4000 and EGR 5000 www eaton com 475 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 RO3 X Do not use Do not use COM OUT IN COM RO4 RO1 RO2 1 2 3 4 5 6...

Страница 488: ...rip pickup setting It is defined by the ratio of negative sequence current to positive sequence current I2 I1 for ABC rotation and I1 I2 for ACB rotation The device will automatically select the corre...

Страница 489: ...agram Blockings IA Name Pickup Please Refer to Diagram Trip Blockings 46 1 n Element is not deactivated and no active blocking signals Tripping command deactivated or blocked IC IB Name 46 1 n 2 3 15a...

Страница 490: ...ate of the assigned signal is true 1 n Assignment List Protection Para Global Prot Para Unbalance Prot 46 1 ExBlo2 External blocking of the module if blocking is activated allowed within a parameter s...

Страница 491: ...ctive if a signal is assigned to the corresponding global protection parameter If the signal becomes true those modules elements are blocked that are parameterized ExBlo TripCmd Fc active Inactive Act...

Страница 492: ...ra Unbalance Prot 46 1 ExBlo TripCmd I Module Input State External Blocking of the Trip Command Protection Para Global Prot Para Unbalance Prot 46 1 Current Unbalance Module Signals Output States Sign...

Страница 493: ...nd is the same as that for the balanced nominal currents fed to the relay it implies that the phase sequence of the currents seen by the relay is reversed Now turn off phase A Again check the measurin...

Страница 494: ...current system nominal currents Switch off IA the threshold value Threshold for I2 Fund must be below 33 Measure the tripping time The present current unbalance I2 Fund corresponds with 1 3 of the ex...

Страница 495: ...hreshold value Testing I2 I1 Configure minimum threshold value Threshold I2 Fund 0 01 x In and set I2 I1 greater or equal to 10 Apply a balanced three phase current system nominal currents The measuri...

Страница 496: ...load condition is finished a cold to warm load condition is detected due to for example breaker closing or load current injection a load inrush detector will be initiated that supervises the coming a...

Страница 497: ...ually the CLPU enabled signal will be issued for this time That means for the duration of this time the tripping thresholds of the overcurrent protection can be desensitized by means of adaptive param...

Страница 498: ...EDR 3000 IM02602003E Example Mode Breaker Position www eaton com 486 Name CLPU CLPU CinBkr 52a 0 1 0 1 CLPU detected t Load Off t Max Block Cold Load 0 1...

Страница 499: ...A IB IC CLPU I AR Running CLPU AND AND AND I Bkr State And I CLPU Mode Bkr State Bkr State Or I OR OR Bkr x Pos OPEN Applies only for devices with Auto Reclosure AND CLPU Load Inrush CLPU Settle Time...

Страница 500: ...l blocking of the module if blocking is activated allowed within a parameter set and if the state of the assigned signal is true 1 n Assignment List Protection Para Global Prot Para CLPU ExBlo2 Extern...

Страница 501: ...the corresponding global protection parameter If the signal becomes true those modules element are blocked that are parameterized Rvs Blo Fc active Inactive Active Inactive Protection Para 1 4 CLPU t...

Страница 502: ...t Para CLPU Rvs Blo I Module Input State Reverse Blocking Protection Para Global Prot Para CLPU Signals of the Cold Load Pickup Module States of the Outputs Signal Description Active Signal Active ExB...

Страница 503: ...is distinctly above the I threshold Mode I and Bkr state Combine the abruptly changing current switching the current ON and OFF with the manual switching ON and OFF of the breaker Mode I or Bkr state...

Страница 504: ...te down the measured time Successful test result The measured total tripping delays or individual tripping delays threshold values and drop out ratios correspond with those values specified in the adj...

Страница 505: ...ually and or An external trigger This protection module can initiate a high speed trip of the overcurrent protection modules The module can be started via a digital input that indicates that the break...

Страница 506: ...no active blocking signals Name SOTF 2 SOTF enabled SOTF I IA IB IC SOTF I SOTF AR Blo AR Running S OTF t en able t T Ext SOTF SOTF AND AND AND I Bkr State And I SOTF Mode Bkr State Bkr manual CLOSE...

Страница 507: ...EDR 3000 IM02602003E Device Planning Parameters of the Switch Onto Fault Module Parameter Description Options Default Menu path Mode Mode Do not use Use Use Device Planning www eaton com 495...

Страница 508: ...e 1 n Assignment List Protection Para Global Prot Para SOTF ExBlo2 External blocking of the module if blocking is activated allowed within a parameter set and if the state of the assigned signal is tr...

Страница 509: ...active Inactive Active Inactive Protection Para 1 4 SOTF Rvs Blo Fc Activate allow or inactivate disallow reverse blocking of the module element This parameter is only effective if a signal is assigne...

Страница 510: ...everse Blocking Protection Para Global Prot Para SOTF Ext SOTF I Module Input State External Switch Onto Fault Alarm Protection Para Global Prot Para SOTF Signals of the Switch Onto Fault Module Outpu...

Страница 511: ...stinctly greater than the I threshold to the measuring inputs of the relay Mode I and Bkr state Simultaneously manually switch on the breaker and feed with an abrupt change current that is distinctly...

Страница 512: ...sured total tripping delays or individual tripping delays threshold values and drop out ratios correspond with those values specified in the adjustment list Permissible deviations tolerances can be fo...

Страница 513: ...e available features of the autoreclose function can be summarized as follows Flexible assignment of initiate functions for individual shots Maximum of six autoreclose shots Dynamic adjustment of prot...

Страница 514: ...EDR 3000 IM02602003E Automatic autoreclose result evaluation successful unsuccessful Separate counters to register total successful unsuccessful reclosing numbers www eaton com 502...

Страница 515: ...to the line and all circuits connected on the line will still be energized 80 90 of the faults are not permanent After a period from 0 5 up to 1 sec the line is probably no longer faulty and the compl...

Страница 516: ...he pre shot the trigger start events can be assigned For each shot a maximum of four initiate functions protective functions which are dedicated to start this shot can be selected from a list of avail...

Страница 517: ...te transitions between the various states of the autoreclosure function This diagram visualizes the run time logic and timing sequence according to the state transition direction and the events which...

Страница 518: ...AR Cycle Start t dead t Run2Ready 4 Lock True Initiate AR InitiateFc True successful Bkr Pos CLOSE Lock True Bkr Pos CLOSE t ManualCloseBlock timer elapsed Reset Lockout True t Reset Lockout timer el...

Страница 519: ...art functions and No external or internal AR blocking signals are present No autoreclose shot operation is possible if the autoreclose function is within Standby state 2 t manual close block Suppose t...

Страница 520: ...in Ready state 4 Run Cycle The RUN state can only be reached if the following conditions are fulfilled The autoreclose was in READY state before The breaker was in closed position before No external o...

Страница 521: ...n activated autoreclose function goes into the BLOCKED state when one of the assigned blocking functions is true The autoreclose function exits the BLOCKED state if the assigned blocking signal is no...

Страница 522: ...e Autoreclose rate per hour exceeds the limit Breaker failure during AR starting Manual breaker close operation during autoreclose process At least one protective function is still tripping before the...

Страница 523: ...False Shot Shot 1 tCI start Shot Shot 1 tCI start CB_CLOSE True t Run2Ready 16 t dead 14 Waiting Bkr Open 13 Ready 11 Ready 11 AR Lock True AR Blo True AR Lock True AR Lock True AR Blo True AR Blo Tr...

Страница 524: ...ion is not initiated from any initiate start functions and No external or internal AR blocking signals are present 13 Waiting Bkr Open While in the WAITING BKR OPEN state the autoreclosure supervises...

Страница 525: ...The breaker is in open position The breaker is ready for next reclosing operation if the CB Ready logic input is used No pickup from current assigned AR initiate function s No trip from current assign...

Страница 526: ...more faults detected within the t Run2Ready timer the autoreclosure logic will leave the RUN state and goes back to the READY state The flag successful is set Unsuccessful Autoreclose If a fault is de...

Страница 527: ...w eaton com 515 Pre Shot Shot AR Running Shot 1 Shot 2 AR Module states t 0 1 Ready Running Lockout Reclosing t 0 1 Bkr State t 0 1 Protection t 0 1 Protection t 0 1 Fault t 0 1 t D1 t D2 t Run2Ready...

Страница 528: ...ww eaton com 516 Pre Shot Shot AR Running Shot 1 Shot 2 AR Module states t 0 1 Ready Running Ready Reclosing t 0 1 Bkr State t 0 1 Protection t 0 1 Protection t 0 1 Fault t 0 1 t D1 t D2 t Run2Ready P...

Страница 529: ...mer does not care about that and timing continues until it times out After it times out the AR module looks at the breaker status again and sees that the breaker is open The AR goes to the STANDBY sta...

Страница 530: ...w eaton com 518 Lockout Reset AR Module states t 0 1 Lockout t Man Close Blo Ready Manual Breaker Close t 0 1 t 0 1 Lockout Reset Time t ManualCloseBlock t Reset Lockout Standby Bkr State Pos OPEN Pos...

Страница 531: ...s Zone Coordination activated The zone coordination function is part of the autoreclosure element and it can be enabled by setting the parameter Zone coordination as active within the Protection Para...

Страница 532: ...w the protective settings of downstream recloser shot by shot For a transient fault the autoreclose with zone coordination will not be initiated again because of absence of the fault current and will...

Страница 533: ...EDR 3000 IM02602003E www eaton com 521 Protective Device Recloser Shot 1 triggered by I 1 Tripping Curve of the Fuse Shot 2 triggered by I 2 Shot 1 triggered by I 1 Shot 2 triggered by I 2 I t I t I t...

Страница 534: ...t Res ServiceCr Reset the Service Counters Inactive Active Inactive Operation Reset Reset Lock via HMI Reset the AR Lockout via the panel Inactive Active Inactive Operation Reset Res Max Shots h Cr Re...

Страница 535: ...state of the assigned signal is true 1 n Assignment List Protection Para Global Prot Para AR General Settings Ex Shot Inc The AR Shot counter will be incremented by this external Signal This can be u...

Страница 536: ...Comm Cmd 1 Modbus Comm Cmd 2 Modbus Comm Cmd 3 Modbus Comm Cmd 4 Modbus Comm Cmd 5 Modbus Comm Cmd 6 Modbus Comm Cmd 7 Modbus Comm Cmd 8 Modbus Comm Cmd 9 Modbus Comm Cmd 10 Modbus Comm Cmd 11 Modbus...

Страница 537: ...t and delay curve operation thus avoiding overtripping Inactive Active Inactive Protection Para 1 4 AR General Settings Ex Shot Inc Fc The AR Shot counter will be incremented by this external Signal T...

Страница 538: ...Para 1 4 AR Shot Manager Shot 3 t D4 Dead time between trip and reclosure attempt Can be initiated either by a phase or a ground fault Only available if Shots 4 6 0 1 9999 00s 1s Protection Para 1 4...

Страница 539: ...signal anymore 0 01 9999 00s 10 0s Protection Para 1 4 AR General Settings t AR Supervision AR Overall supervision time sum of all the timers used by AR 1 00 9999 00s 100 0s Protection Para 1 4 AR Ge...

Страница 540: ...ot Manager Initiate AR Shot 1 InitiateFc1 Automatic Reclosure Attempt Initiate Function Only available if Shots 1 6 Start fct Protection Para 1 4 AR Shot Manager Shot 1 Shot 1 InitiateFc2 Automatic Re...

Страница 541: ...6 Start fct Protection Para 1 4 AR Shot Manager Shot 2 Shot 2 InitiateFc4 Automatic Reclosure Attempt Initiate Function Only available if Shots 2 6 Start fct Protection Para 1 4 AR Shot Manager Shot...

Страница 542: ...6 Start fct Protection Para 1 4 AR Shot Manager Shot 4 Shot 4 InitiateFc3 Automatic Reclosure Attempt Initiate Function Only available if Shots 4 6 Start fct Protection Para 1 4 AR Shot Manager Shot...

Страница 543: ...teFc1 Automatic Reclosure Attempt Initiate Function Only available if Shots 6 Start fct Protection Para 1 4 AR Shot Manager Shot 6 Shot 6 InitiateFc2 Automatic Reclosure Attempt Initiate Function Only...

Страница 544: ...m Auto Reclosure devices Note This parameter enables the functionallity only The assignment has to be set within the global parameters Protection Para Global Prot Para AR General Settings Ex Lock I Mo...

Страница 545: ...been detected Blo Signal Auto Reclosure is blocked t Blo Reset Signal Delay Timer for resetting the AR blocking The release de blocking of the AR will be delayed for this time if there is no blocking...

Страница 546: ...y executed Automatic Reclosures 0 0 65536 Operation Count and RevData AR Cr failed Total number of unsuccessfully executed automatic reclosure attempts 0 0 65536 Operation Count and RevData AR Cr Serv...

Страница 547: ...te of the assigned signal is true If the state of this function is true the AR will be aborted 1 n Assignment List Protection Para Global Prot Para AR BlockFct Abort 4 Abort the AR cycle if the state...

Страница 548: ...of the assigned signal is true If the state of this function is true the AR will be aborted Protection Para Global Prot Para AR BlockFct Abort 4 Abort the AR cycle if the state of the assigned signal...

Страница 549: ...ipCmd Signal Trip Command 50X 2 TripCmd Signal Trip Command 51X 1 TripCmd Signal Trip Command 51X 2 TripCmd Signal Trip Command 50R 1 TripCmd Signal Trip Command 50R 2 TripCmd Signal Trip Command 51R...

Страница 550: ...ructured By means of these elements the protective device can detect and execute pickups and trips that are issued by other external devices This can be helpful for logging purposes if the other devic...

Страница 551: ...AND AND Name Trip Name Alarm Please Refer to Diagram Blockings Please Refer to Diagram Trip Blockings Element is not deactivated and no active blocking signals Tripping command deactivated or blocked...

Страница 552: ...ExBlo2 External blocking of the module if blocking is activated allowed within a parameter set and if the state of the assigned signal is true 1 n Assignment List Protection Para Global Prot Para ExP...

Страница 553: ...nal becomes true those modules elements are blocked that are parameterized ExBlo Fc active Inactive Active Inactive Protection Para 1 4 ExP ExP 1 Blo TripCmd Permanent blocking of the Trip Command of...

Страница 554: ...cking of the Trip Command Protection Para Global Prot Para ExP ExP 1 Alarm I Module Input State Alarm Protection Para Global Prot Para ExP ExP 1 Trip I Module Input State Trip Protection Para Global P...

Страница 555: ...sary means Dependent on the application Procedure Simulate the functionality of the External Protection pickup trip and blockings by de energizing the digital inputs Successful test result All externa...

Страница 556: ...his trip signal is to be used to trip the upstream breaker backup Stopping the BF The timer will be stopped if the opening of the breaker is detected Depending on the supervision scheme the timer will...

Страница 557: ...dged at the HMI Note on devices that offer Wide Frequency Range measurement The supervision scheme 50BF will be blocked as soon as the frequency differs more than 5 from the nominal frequency As long...

Страница 558: ...as the BF module is triggered by a trip signal A Breaker Failure will be de tected and a signal will be issued if the measured current does not fall below a set threshold and if simultaneously the eva...

Страница 559: ...e BFmodule even if they are not assigned onto the breaker within the corresponding breaker manager Select the winding side Breaker Winding from which the measured currents should be taken in case this...

Страница 560: ...the BF module is within the stand by state Who stopps the BF Timer Once the timer has been stopped the BF module will switch into the state Rejected The module will switch back into the state Stand b...

Страница 561: ...r the threshold the longer the time that is needed to detect that the breaker is in the open position especially if there are transients harmonics Note Tripping delay of the BF module Minimum delay ti...

Страница 562: ...ger3 1 n Assignment List BF Trigger2 1 n Assignment List BF Trigger1 BF Name BF Please Refer to Diagram Blockings Element is not deactivated and no active blocking signals 2 11 15 15 IA IB IC BF Locko...

Страница 563: ...n Assignment List BF Trigger2 1 n Assignment List BF Trigger1 BF Name BF Please Refer to Diagram Blockings Element is not deactivated and no active blocking signals 2 11 15 BF Lockout Res Lockout BF P...

Страница 564: ...signal is true 1 n Assignment List Protection Para Global Prot Para Supervision BF ExBlo2 External blocking of the module if blocking is activated allowed within a parameter set and if the state of t...

Страница 565: ...u path Trigger3 Trigger that will start the BF Trigger Protection Para Global Prot Para Supervision BF Direct Commands of the BF Parameter Description Setting range Default Menu path Res Lockout Reset...

Страница 566: ...ve Inactive Protection Para 1 4 Supervision BF ExBlo Fc Activate allow or inactivate disallow blocking of the module element This parameter is only effective if a signal is assigned to the correspondi...

Страница 567: ...Para Global Prot Para Supervision BF Trigger2 I Module Input Trigger that will start the BF Protection Para Global Prot Para Supervision BF Trigger3 I Module Input Trigger that will start the BF Prote...

Страница 568: ...al Trip Command 51R 1 TripCmd Signal Trip Command 51R 2 TripCmd Signal Trip Command 46 1 TripCmd Signal Trip Command 46 2 TripCmd Signal Trip Command ZI TripCmd Signal Zone Interlocking Trip Command E...

Страница 569: ...Gate Out Signal Output of the logic gate Logic LE5 Timer Out Signal Timer Output Logic LE5 Out Signal Latched Output Q Logic LE5 Out inverted Signal Negated Latched Output Q NOT Logic LE6 Gate Out Sig...

Страница 570: ...LE14 Timer Out Signal Timer Output Logic LE14 Out Signal Latched Output Q Logic LE14 Out inverted Signal Negated Latched Output Q NOT Logic LE15 Gate Out Signal Output of the logic gate Logic LE15 Tim...

Страница 571: ...LE23 Out Signal Latched Output Q Logic LE23 Out inverted Signal Negated Latched Output Q NOT Logic LE24 Gate Out Signal Output of the logic gate Logic LE24 Timer Out Signal Timer Output Logic LE24 Ou...

Страница 572: ...nverted Signal Negated Latched Output Q NOT Logic LE33 Gate Out Signal Output of the logic gate Logic LE33 Timer Out Signal Timer Output Logic LE33 Out Signal Latched Output Q Logic LE33 Out inverted...

Страница 573: ...ate Out Signal Output of the logic gate Logic LE42 Timer Out Signal Timer Output Logic LE42 Out Signal Latched Output Q Logic LE42 Out inverted Signal Negated Latched Output Q NOT Logic LE43 Gate Out...

Страница 574: ...LE51 Timer Out Signal Timer Output Logic LE51 Out Signal Latched Output Q Logic LE51 Out inverted Signal Negated Latched Output Q NOT Logic LE52 Gate Out Signal Output of the logic gate Logic LE52 Tim...

Страница 575: ...LE60 Out Signal Latched Output Q Logic LE60 Out inverted Signal Negated Latched Output Q NOT Logic LE61 Gate Out Signal Output of the logic gate Logic LE61 Timer Out Signal Timer Output Logic LE61 Ou...

Страница 576: ...nverted Signal Negated Latched Output Q NOT Logic LE70 Gate Out Signal Output of the logic gate Logic LE70 Timer Out Signal Timer Output Logic LE70 Out Signal Latched Output Q Logic LE70 Out inverted...

Страница 577: ...LE78 Timer Out Signal Timer Output Logic LE78 Out Signal Latched Output Q Logic LE78 Out inverted Signal Negated Latched Output Q NOT Logic LE79 Gate Out Signal Output of the logic gate Logic LE79 Tim...

Страница 578: ...ignal Trip Command 51X 2 TripCmd Signal Trip Command 50R 1 TripCmd Signal Trip Command 50R 2 TripCmd Signal Trip Command 51R 1 TripCmd Signal Trip Command 51R 2 TripCmd Signal Trip Command 46 1 TripCm...

Страница 579: ...module if External trips have been selected as the trigger event Name Description No assignment ExP 1 TripCmd Signal Trip Command ExP 2 TripCmd Signal Trip Command ExP 3 TripCmd Signal Trip Command E...

Страница 580: ...protection a test current has to be higher than the threshold value of one of the current protection modules that are assigned to trigger the BF protection The BF trip delay can be measured from the t...

Страница 581: ...ent circuit calibration errors and other is the dynamic error that is proportional to the measured maximum current due to CT transformation characteristics The CTs are assumed to be used in the wye gr...

Страница 582: ...If the current is measured in two phases only for example only IA IB or if there is no separate ground current measuring e g normally via a zero sequence CT the supervision function should be deactiva...

Страница 583: ...ww eaton com 571 Please Refer to Diagram Blockings IX Calculated IA CTS Pickup CTS Element is not deactivated and no active blocking signals IC IB IX Kd CTS I 2 AND 40 CTS t t 0 Phase or Ground Curren...

Страница 584: ...Setting range Default Menu path ExBlo1 External blocking of the module if blocking is activated allowed within a parameter set and if the state of the assigned signal is true 1 n Assignment List Prot...

Страница 585: ...n CTS I In order to prevent faulty tripping of phase selective protection functions that use the current as tripping criterion If the difference of the measured ground current and the calculated value...

Страница 586: ...ion Para Global Prot Para Supervision CTS ExBlo2 I Module Input State External Blocking2 Protection Para Global Prot Para Supervision CTS Current Transformer Supervision Signals Outputs States Signal...

Страница 587: ...hree phase symmetrical current system approx nominal current to the secondary side Disconnect the current of one phase from one of the measuring inputs the symmetrical feeding at the secondary side ha...

Страница 588: ...t be monitored through the other digital inputs Note that the digital inputs used for this purpose must be configured properly based on the trip circuit control voltage and also that the de bouncing t...

Страница 589: ...52a and 52b in trip circuit www eaton com 577 Breaker 1 Bkr 1 Control Voltage 1 2 3 4 5 6 7 8 PE 9 10 11 12 COM1 13 14 15 16 17 18 V DI1 COM2 DI2 V X1 TC W1 52a W1 52b DC DC 52a 52b Trip Relay Control...

Страница 590: ...a Only in Trip Circuit www eaton com 578 Breaker 1 Bkr 1 Control Voltage 1 2 3 4 5 6 7 8 PE 9 10 11 12 COM1 13 14 15 16 17 18 V DI1 V X1 TC W1 52a W1 52b DC DC 52a 52b Trip Relay Control Voltage AND B...

Страница 591: ...EDR 3000 IM02602003E Device Planning Parameters of the Trip Circuit Monitoring Module Parameter Description Options Default Menu path Mode Mode Do not use Use Use Device Planning www eaton com 579...

Страница 592: ...upervision TCM Input 2 Select the input configured to monitor the trip coil when the breaker is open Only available if Mode set to Either Only available if Mode Either 1 n Dig Inputs Protection Para G...

Страница 593: ...Fc Activate allow or inactivate disallow blocking of the module element This parameter is only effective if a signal is assigned to the corresponding global protection parameter If the signal becomes...

Страница 594: ...Global Prot Para Supervision TCM ExBlo1 I Module Input State External Blocking1 Protection Para Global Prot Para Supervision TCM ExBlo2 I Module Input State External Blocking2 Protection Para Global P...

Страница 595: ...st of the trip circuit monitoring with 52a and 52b contact Procedure Part 1 Simulate failure of the control voltage in the power circuits Successful Test Result Part 1 After expiration of t TCM the tr...

Страница 596: ...recorders of the device should be left untouched to ensure an easy diagnosis and proper repair at the factory Besides the records and visible indications to the customer there is internal information...

Страница 597: ...ow a certain threshold a restart of the device is initiated If the voltage staggers around the threshold the device also starts again after several seconds Additionally the level of all internal suppl...

Страница 598: ...internally for system analysis purposes 5 Restart because of configuration changes 6 General failure Reboot without definite reason 7 Reboot by SW system abort HOST side Summary of several reboot rea...

Страница 599: ...ctive function pickups protective function states breaker states system alarms and module inputs The User can use the output signals of a logic equation as inputs in higher equations e g the output si...

Страница 600: ...are 0 then the output of the gate will be set as follows 0 for an AND gate 1 for a NAND gate 0 for an OR gate 1 for a NOR gate If at least one input signal is assigned to a gate all not assigned input...

Страница 601: ...nment List LE x IN1 Active Inactive Inverting1 XOR 1 n Assignment List LE x IN2 Active Inactive Inverting2 XOR 1 n Assignment List LE x IN3 Active Inactive Inverting3 XOR 1 n Assignment List LE x IN4...

Страница 602: ...e output of the gate can be delayed The User has the option to set an On and an Off delay Latching The timer issues two signals an unlatched and a latched signal The latched output can optionally be i...

Страница 603: ...utilizes the output signal of Logic Equation n as input of Logic Equation n 1 If the state of Logic Equation n changes the state of the output of Logic Equation n 1 will be updated within the same cyc...

Страница 604: ...elay Logic Equation2 LE2 IN2 LE2 IN3 LE2 IN4 Output of Logic Equation 2 Logic Equation1 LE1 IN2 LE1 IN3 LE1 IN4 Output of Logic Equation 1 Logic Equation3 LE3 IN1 LE3 IN2 LE3 IN3 LE3 IN4 Logic Equatio...

Страница 605: ...used assign a reset signal to the reset input Within the status display the User can check the status of the logical inputs and outputs of the logic equation In case the logic equations should be cas...

Страница 606: ...he User can check the status of the logical inputs and outputs of the logic equation In case the logic equations should be cascaded the User has to be aware of timing delays cycles in case of descendi...

Страница 607: ...pCmd Signal Command Execution Supervision Command execution failed because trip command is pending Bkr CES SwitchgDir Signal Command Execution Supervision respectivly Switching Direction Control This...

Страница 608: ...rip 50P 3 TripCmd Signal Trip Command 51P 1 Pickup Signal Pickup 51P 1 Trip Signal Trip 51P 1 TripCmd Signal Trip Command 51P 2 Pickup Signal Pickup 51P 2 Trip Signal Trip 51P 2 TripCmd Signal Trip Co...

Страница 609: ...d Trip Signal Zone Interlocking Ground Trip ZI IN Signal Zone Interlocking IN ZI OUT Signal Zone Interlocking OUT ZI Phase OUT Signal Zone Interlocking Phase OUT ZI Phase Pickup Signal Zone Interlocki...

Страница 610: ...d AR failed Signal Auto Reclosing Failure AR Lock Signal Auto Reclosure is locked out AR Pre Shot Pre Shot Control AR Ready Signal Ready to shoot AR Running Signal Auto Reclosing Running AR Standby Si...

Страница 611: ...Digital Input DI 4P X1 DI 2 Signal Digital Input DI 4P X1 DI 3 Signal Digital Input DI 4P X1 DI 4 Signal Digital Input DI 8P X1 DI 1 Signal Digital Input DI 8P X1 DI 2 Signal Digital Input DI 8P X1 D...

Страница 612: ...Out19 I Module input state Binary state of the Virtual Output GGIO IEC61850 VirtOut20 I Module input state Binary state of the Virtual Output GGIO IEC61850 VirtOut21 I Module input state Binary state...

Страница 613: ...rtual Input IEC61850 GGIO Ind IEC61850 VirtInp24 Signal Virtual Input IEC61850 GGIO Ind IEC61850 VirtInp25 Signal Virtual Input IEC61850 GGIO Ind IEC61850 VirtInp26 Signal Virtual Input IEC61850 GGIO...

Страница 614: ...ut Signal Output of the logic gate Logic LE8 Timer Out Signal Timer Output Logic LE8 Out Signal Latched Output Q Logic LE8 Out inverted Signal Negated Latched Output Q NOT Logic LE9 Gate Out Signal Ou...

Страница 615: ...LE17 Timer Out Signal Timer Output Logic LE17 Out Signal Latched Output Q Logic LE17 Out inverted Signal Negated Latched Output Q NOT Logic LE18 Gate Out Signal Output of the logic gate Logic LE18 Tim...

Страница 616: ...LE26 Out Signal Latched Output Q Logic LE26 Out inverted Signal Negated Latched Output Q NOT Logic LE27 Gate Out Signal Output of the logic gate Logic LE27 Timer Out Signal Timer Output Logic LE27 Ou...

Страница 617: ...nverted Signal Negated Latched Output Q NOT Logic LE36 Gate Out Signal Output of the logic gate Logic LE36 Timer Out Signal Timer Output Logic LE36 Out Signal Latched Output Q Logic LE36 Out inverted...

Страница 618: ...ate Out Signal Output of the logic gate Logic LE45 Timer Out Signal Timer Output Logic LE45 Out Signal Latched Output Q Logic LE45 Out inverted Signal Negated Latched Output Q NOT Logic LE46 Gate Out...

Страница 619: ...LE54 Timer Out Signal Timer Output Logic LE54 Out Signal Latched Output Q Logic LE54 Out inverted Signal Negated Latched Output Q NOT Logic LE55 Gate Out Signal Output of the logic gate Logic LE55 Tim...

Страница 620: ...LE63 Out Signal Latched Output Q Logic LE63 Out inverted Signal Negated Latched Output Q NOT Logic LE64 Gate Out Signal Output of the logic gate Logic LE64 Timer Out Signal Timer Output Logic LE64 Ou...

Страница 621: ...nverted Signal Negated Latched Output Q NOT Logic LE73 Gate Out Signal Output of the logic gate Logic LE73 Timer Out Signal Timer Output Logic LE73 Out Signal Latched Output Q Logic LE73 Out inverted...

Страница 622: ...rc Flash Reduction Maintenance Manual Mode Sys Maint Mode I Module Input State Arc Flash Reduction Maintenance Switch Sys Min 1 param changed Signal At least one parameter has been changed Sys PS 1 Si...

Страница 623: ...gicList Logic LE 1 LE1 Inverting2 Inverting the input signals Only available if an input signal has been assigned Inactive Active Inactive Logic LE 1 LE1 IN3 Assignment of the Input Signal 1 n LogicLi...

Страница 624: ...36000 00s 0 00s Logic LE 1 LE1 Reset Latched Reset Signal for the Latching 1 n LogicList Logic LE 1 LE1 Inverting Reset Inverting Reset Signal for the Latching Inactive Active Inactive Logic LE 1 LE1...

Страница 625: ...LE 1 LE1 Gate In2 I State of the module input Assignment of the Input Signal Logic LE 1 LE1 Gate In3 I State of the module input Assignment of the Input Signal Logic LE 1 LE1 Gate In4 I State of the m...

Страница 626: ...grammable Logic Outputs Signal Description LE1 Gate Out Signal Output of the logic gate LE1 Timer Out Signal Timer Output LE1 Out Signal Latched Output Q LE1 Out inverted Signal Negated Latched Output...

Страница 627: ...omponent connections All locally applicable national and international installation and safety regulations for working at electrical power installations MUST always to be followed Prior to the initial...

Страница 628: ...LEDs and relay functions these have to be provided with the relevant pickup alarm and tripping functions of the respective protection functions elements This MUST be tested in practical operation Chec...

Страница 629: ...nd that there are no voltages that could lead to injury of personnel Disconnect the terminals at the rear side of the device DO NOT pull any cable pull on the plug If it is stuck use a screw driver Fa...

Страница 630: ...ce and Commissioning Support Within the service menu various functions support maintenance and commissioning of the device General Within the Service General menu the User can initiate a reboot of the...

Страница 631: ...lt clearing time and lower incident energy levels at energized panels The Maintenance Mode allows the User to switch to more sensitive settings via the HMI panel Communication or via a Digital Input w...

Страница 632: ...ensitivity settings either into a setting group or into Adaptive Parameters The Maintenance Mode offers two output signals Maint Mode activated and Maint Mode not activated The Maint Mode ACTIVATED si...

Страница 633: ...ctive Sys Maint Mode Mode Activation Manually Activation via Comm Activation via DI Inactive Sys MaintMode Manually Active Comm Cmd Sys Maint Mode Active Sys Maint Mode Inactive Sys MaintMode Manually...

Страница 634: ...with a timeout they will keep their Force Position only as long as this timer runs If the timer expires the relay will operate normally If they are set as Permanent they will keep the Force Position c...

Страница 635: ...tective device WILL NOT provide protection Zone Interlocking Output and the Supervision Contact cannot be disarmed Within this mode Service Test Mode Prot inhibit WARNING Cont DISARMED entire groups o...

Страница 636: ...t contact WILL be disarmed if it is not latched and If there is no running t OFF delay timer hold time of a relay output contact and If the DISARM Control is set to active and If the Direct Command Di...

Страница 637: ...t inhibit WARNING Cont URTD RTD temperatures can be set by force Permanent or Via timeout If they are set with a timeout they will keep their Forced Temperature only as long as this timer runs If the...

Страница 638: ...ARNING Cont Analog Outputs Analog Outputs can be set by force Permanent or Via timeout If they are set with a timeout they will keep their Forced Value only as long as this timer runs If the timer exp...

Страница 639: ...s can be set by force Permanent or Via timeout If they are set with a timeout they will keep their Forced Value only as long as this timer runs If the timer expires the Analog Input will operate norma...

Страница 640: ...Prot inhibit WARNING Cont Sine wave gen Configuration sub menu the duration of each phase can be set In addition the measuring quantities to be simulated can be determined e g voltages currents and th...

Страница 641: ...EDR 3000 IM02602003E The simulation voltages are always phase to neutral voltages irrespectively of the mains voltage transformers connection method Phase to phase Wey Open Delta www eaton com 629...

Страница 642: ...wave gen Process Trip Cmd Mode No Trip Simulation is authorized to trip the breaker How To Call up Service Test Mode Prot inhibit WARNING Cont Sine wave gen Process Trip Cmd Mode Trip Stop by external...

Страница 643: ...Fault Duration 0 00 300 00s 0 0s Service Test Mode Prot inhibit WARNING Cont Sgen Configuration Times FaultSimulation Duration of Fault Simulation 0 00 10800 00s 0 0s Service Test Mode Prot inhibit W...

Страница 644: ...d if the state of the assigned signal is true 1 n Assignment List Bkr Pos CLOSE Service Test Mode Prot inhibit WARNING Cont Sgen Process Ex ForcePost Force Post state Abort simulation 1 n Assignment L...

Страница 645: ...Pre State Phase C 0 00 40 00In 0 0In Service Test Mode Prot inhibit WARNING Cont Sgen Configuration PreFault CT IX meas Fund Current Fundamental Magnitude in Pre State IX 0 00 25 00In 0 0In Service Te...

Страница 646: ...rt Angle of the Current Phasor during Pre Phase Phase C 360 360 120 Service Test Mode Prot inhibit WARNING Cont Sgen Configuration PreFault CT Angle IX meas Fund Start Position respectively Start Angl...

Страница 647: ...te Phase C 0 00 40 00In 0 0In Service Test Mode Prot inhibit WARNING Cont Sgen Configuration FaultSimulation CT IX meas Fund Current Fundamental Magnitude in Fault State IX 0 00 25 00In 0 0In Service...

Страница 648: ...Angle of the Current Phasor during Fault Phase Phase C 360 360 120 Service Test Mode Prot inhibit WARNING Cont Sgen Configuration FaultSimulation CT Angle IX meas Fund Start Position respectively Star...

Страница 649: ...Post phase Phase C 0 00 40 00In 0 0In Service Test Mode Prot inhibit WARNING Cont Sgen Configuration PostFault CT IX meas Fund Current Fundamental Magnitude during Post phase IX 0 00 25 00In 0 0In Ser...

Страница 650: ...nt Sgen Configuration PostFault CT Angle IC Fund Start Position respectively Start Angle of the Current Phasor during Post phase Phase C 360 360 120 Service Test Mode Prot inhibit WARNING Cont Sgen Co...

Страница 651: ...of the module input Force Post state Abort simulation Service Test Mode Prot inhibit WARNING Cont Sgen Process Signals of the Failure Simulator States of the Outputs Signal Description Running Signal...

Страница 652: ...ve Active Inactive Service Test Mode Prot inhibit WARNING Cont Sgen Process Failure Simulator Values Value Description Default Size Menu path State Wave generation states 0 Off 1 PreFault 2 Fault 3 Po...

Страница 653: ...ove sea level If 4 000 m 13 123 35 ft altitude applies a changed classification of the operating and test voltages may be necessary Degree of Protection EN 60529 HMI Front Panel with Seal IP54 Rear Si...

Страница 654: ...in 141 5 mm 5 571 in Housing Depth Incl Terminals 208 mm 8 189 in Material Housing Aluminum extruded section Material Front Panel Aluminum foil front Mounting Position Horizontal 45 around the X axis...

Страница 655: ...lf wave Power Consumption Phase current inputs At In 1 A S 25 mVA At In 5 A S 90 mVA Ground current input At In 1 A S 25 mVA At In 5 A S 90 mVA Sensitive Ground Current Inputs Nominal Currents 1 A 5 A...

Страница 656: ...5 mm 2 x AWG 14 with wire end ferrule 1 x or 2 x 4 0 mm 2 x AWG 12 with ring cable sleeve or cable sleeve 1 x or 2 x 6 mm 2 x AWG 10 with ring cable sleeve or cable sleeve The current measuring board...

Страница 657: ...ak value for 1 ms The voltage supply must be protected by a fuse of 2 5 A time lag miniature fuse 5 x 20 mm approx 1 5 x 0 8 in according to IEC 60127 3 5 A time lag miniature fuse 6 3 x 32 mm approx...

Страница 658: ...th LED background illumination Resolution Graphics Display 128 x 64 pixel LED Type Two colored red green Number of LEDs Housing B2 8 Front Interface RS232 Baud Rates 115 200 Baud Handshake RTS and CTS...

Страница 659: ...EDR 3000 IM02602003E Real Time Clock Running Reserve of the Real Time Clock 1 year min www eaton com 647...

Страница 660: ...Threshold 1 ON Switching Threshold 1 OFF Min 19 2 Vdc Max 9 6 Vdc Un 48 V 60Vdc Switching Threshold 2 ON Switching Threshold 2 OFF Min 42 6 Vdc Max 21 3 Vdc Un 110 120 Vac dc Switching Threshold 3 ON...

Страница 661: ...05 30 A 250Vdc according to ANSI IEEE Std C37 90 2005 Max Breaking Current 5 A ac up to 240 V ac 4 A ac at 230V and cos 0 4 5 A dc up to 30 V resistive 0 3 A dc at 250 V resistive 0 1 A dc at 220 V an...

Страница 662: ...EDR 3000 IM02602003E Time Synchronization IRIG B00X Nominal input voltage 5 V Connection Screw type terminals twisted pair www eaton com 650...

Страница 663: ...ctronic inputs only Zone Out Output voltage High 4 75 to 5 25 Vdc Output voltage Low 0 0 to 0 5 Vdc Zone In Nominal input voltage 5 Vdc Max input voltage 5 5 Vdc Switching threshold ON min 4 0 Vdc Swi...

Страница 664: ...The RS485 interface is realized via terminals The communication cable has to be shielded The shielding has to be fixed at the screw that is marked with the ground symbol rear side of the device Fiber...

Страница 665: ...Boot Phase After switching on the power supply the protection will be available in approximately 15 seconds After approximately 70 seconds the boot phase is completed HMI and Communication initialize...

Страница 666: ...EC 60255 22 1 IEEE C37 90 1 IEC 61000 4 18 class 3 Within one circuit Circuit to ground Circuit to circuit 1 kV 2 s 2 5 kV 2 s 2 5 kV 2 s Insulation Voltage Test IEC 60255 27 10 5 3 2 IEC 60255 5 EN 5...

Страница 667: ...4 ANSI C37 90 1 class 4 Power supply mains inputs Other in and outputs 4 kV 2 5 kHz 2 kV 5 kHz coupling network 4 kV 2 5 kHz coupling clamp Surge Immunity Test Surge IEC 60255 22 5 IEC 61000 4 5 clas...

Страница 668: ...V m 35 V m 10 V m Immunity to Conducted Disturbances Induced by Radio Frequency Fields IEC 61000 4 6 class 3 150kHz 80MHz 10 V Power Frequency Magnetic Field Immunity Test IEC 61000 4 8 class 4 contin...

Страница 669: ...of ambient conditions Stationary use at weather protected locations 3K6 3B1 3C1 3S1 3M2 but min 20 C 4 F max 60 C 140 F Test Ad Cold IEC 60068 2 1 Temperature Test duration 20 C 4 F 16 h Test Bd Dry H...

Страница 670: ...14 Temperature cycle test duration 60 C 20 C 5 1 C 5min Test BD Dry Heat Transport and storage test IEC 60255 6 12 3 3 IEC 60068 2 2 Temperature test duration 70 C 16 h Test AB Cold Transport and sto...

Страница 671: ...Test IEC 60068 2 27 IEC 60255 21 2 class 1 Shock response test 5 gn 11 ms 3 impulses in each direction Shock resistance test 15 gn 11 ms 3 impulses in each direction Test Eb Shock Endurance Test IEC...

Страница 672: ...ary in their accuracy Used Protocol Time drift over one month Deviation to time generator Without time synchronization 1 min 20 C Time drifts IRIG B Dependent on the time drift of the time generator 1...

Страница 673: ...d current 3 Amplitude Error if I 2 In 1 0 of the measured current 3 Harmonics Up to 20 3rd harmonic 2 Up to 20 5th harmonic 2 Frequency Influence 2 Hz in the range of 5 Hz of the configured nominal fr...

Страница 674: ...p value 35 ms Disengaging Time 45 ms t Multiplier 5 according to selected curve Reset Mode 5 according to selected curve t reset Reset Mode t delay 1 or 10 ms Ground Current Elements 50X x 50R x Accur...

Страница 675: ...closing AR Accuracy t all timers 1 or 20 ms Switch onto Fault SOTF Accuracy Operating time 35 ms I 1 5 of the setting value or1 In t enable 1 or 10 ms Cold Load Pickup CLPU Accuracy Threshold 1 5 of t...

Страница 676: ...EDR 3000 IM02602003E Current Transformer Supervision CTS Accuracy I 2 of the setting value or 1 5 In Dropout Ratio 94 Pickup delay 1 or 10 ms www eaton com 664...

Страница 677: ...ate The output becomes true if all Input signals are true ANG Angle ANSI American National Standards Institute AR Automatic reclosure AUX Auxiliary AVG avg Average AWG American wire gauge BF Breaker f...

Страница 678: ...nt DEFT Definite time characteristic Tripping time does not depend on the height of the current DFLT Default DGNST Diagnostics DI Digital Input Diagn Diagnosis Diagn Cr Diagnosis counter s DIFF Differ...

Страница 679: ...cceleration of the earth in vertical direction 9 81 m s2 GND Ground GPS Global positioning system h Hour HARM Harmonic harmonics HMI Human machine interface Front of the protective relay HTL Manufactu...

Страница 680: ...armonic IINV Inverse in Inch incl Include including Info Information Interl Interlocking INV Inverse characteristic The tripping time will be calculated depending on the height of the current I O Inpu...

Страница 681: ...pping characteristic LV Low voltage m Meter M Machine mA Milliampere s Milliamp s MAG Magnitude MAN man Manual manually MAX max Maximum meas Measured MIN min Minimum min Minute MINV Moderately Inverse...

Страница 682: ...W A Megawatt s phase A MW B Megawatt s phase B MW C Megawatt s phase C MWH Megawatt Hour s N Neutral N A n a Not applicable N C Not connected NEG Negative NINV Normal inverse tripping characteristic N...

Страница 683: ...S1 Parameter set 1 PS2 Parameter set 2 PS3 Parameter set 3 PS4 Parameter set 4 PSet Parameter set PSS Parameter set switch Switching from one parameter set to another pu Per unit PWM Pulse width modul...

Страница 684: ...EQ Sequence Sig Signal SNTP Simple network time protocol SRC Source StartFct Start function STATS Statistics Sum Summation SUPERV Supervision SW Software SYNC Sync check Synchrocheck SYNCHCHK Sync che...

Страница 685: ...ce voltage V2 Negative sequence voltage VA Phase A voltage VAB Phase A to B voltage Vac V ac Volts alternating current VAG Phase A to ground voltage VARH Var hour voltage VB Phase B voltage VBA Phase...

Страница 686: ...er supervision W Watt s WDC Watch dog contact supervision contact WDG Winding WH Watthour www World wide web X Reactance XCT 4th current measuring input ground or neutral current XInv Inverse characte...

Страница 687: ...anation www eaton com 675 t Tripping delay I Fault current Pickup If the pickup value is exceeded the module element starts to time out to trip t s Pickup I 1 10 0 01 0 1 1 10 100 1 10 0 01 0 1 1 10 1...

Страница 688: ...nv VINV ANSI XInv EINV ANSI XInv Thermal Flat Therm Flat IT Therm Flat I2T and Therm Flat I4T Explanation www eaton com 676 t Tripping delay t multiplier Time multiplier tripping characteristic factor...

Страница 689: ...7 t multiplier x Pickup Multiples of Pickup Trip Reset t 0 14 t multiplier s Pickup 1 I 2 t 0 14 t multiplier s Pickup 1 I 0 02 t s Notice Various Reset Modes are available Resetting via characteristi...

Страница 690: ...678 t s t multiplier t 13 5 t multiplier s Pickup 1 I t 13 5 t multiplier s Pickup 1 I 2 Trip Reset x Pickup Multiples of Pickup Notice Various Reset Modes are available Resetting via characteristic...

Страница 691: ...m 679 t s t multiplier t 120 t multiplier s Pickup 1 I 2 t 120 t multiplier s Pickup 1 I Trip Reset x Pickup Multiples of Pickup Notice Various Reset Modes are available Resetting via characteristic d...

Страница 692: ...m 680 t s t multiplier t 80 t multiplier s Pickup 1 I 2 t 80 t multiplier s Pickup 1 I 2 Trip Reset x Pickup Multiples of Pickup Notice Various Reset Modes are available Resetting via characteristic d...

Страница 693: ...t multiplier t 4 85 t multiplier s Pickup 1 I 2 t 0 0515 t multiplier s Pickup 1 I 0 02 0 1140 Trip Reset x Pickup Multiples of Pickup Notice Various Reset Modes are available Resetting via character...

Страница 694: ...t s t multiplier Trip Reset x Pickup Multiples of Pickup t 19 61 t multiplier s Pickup 1 I 2 0 491 t 21 6 t multiplier s Pickup 1 I 2 Notice Various Reset Modes are available Resetting via characteris...

Страница 695: ...t s t multiplier t 29 1 t multiplier s Pickup 1 I 2 Trip Reset x Pickup Multiples of Pickup t 28 2 t multiplier s Pickup 1 I 2 0 1217 Notice Various Reset Modes are available Resetting via characteris...

Страница 696: ...al Current Trip Reset t 5 3 t multiplier s 2 In I 0 t 5 1 t multiplier s In I 0 2 Notice Various Reset Modes are available Resetting via characteristic delayed and instantaneous Therm Flat t 45 t mult...

Страница 697: ...s of the Nominal Current Trip Reset t 5 3 t multiplier s 2 In I 0 Notice Various Reset Modes are available Resetting via characteristic delayed and instantaneous IT t 5 3 t multiplier s 1 In I 1 0 01...

Страница 698: ...100 1 10 3 1 10 4 TM s 10 5 2 1 0 0 5 0 05 t s t multiplier x In Multiples of the Nominal Current Trip Reset t 5 3 t multiplier s 2 In I 0 Notice Various Reset Modes are available Resetting via chara...

Страница 699: ...of the Nominal Current Trip Reset t 5 3 t multiplier s 2 In I 0 Notice Various Reset Modes are available Resetting via characteristic delayed and instantaneous I4T t 5 3 t multiplier s In I 4 4 0 01...

Страница 700: ...easured either directly via a zero sequence transformer or detected by a residual connection The ground current can alternatively be calculated from the phase currents but this is only possible if the...

Страница 701: ...EDR 3000 IM02602003E www eaton com 689 t s 1 10 0 01 0 1 1 10 100 1 10 0 01 0 1 1 10 100 I I t t 40 20 300 s 300 s 0 0 s 0 0 s 0 01 0 01 Pickup IR calc Pickup IR calc DEFT...

Страница 702: ...asured either directly via a zero sequence transformer or detected by a residual connection The ground current can alternatively be calculated from the phase currents but this is only possible if the...

Страница 703: ...EDR 3000 IM02602003E www eaton com 691 t s 1 10 0 01 0 1 1 10 100 1 10 0 01 0 1 1 10 100 I I t t 40 20 300 s 300 s 0 0 s 0 0 s 0 01 0 01 Pickup IX Pickup IX DEFT...

Страница 704: ...be measured either directly via a zero sequence transformer or detected by a residual connection The ground current can alternatively be calculated from the phase currents but this is only possible if...

Страница 705: ...t multiplier t 0 14 t multiplier s Pickup 1 IG 0 02 Trip Reset t 0 14 t multiplier s Pickup 1 IG 2 x Pickup Multiples of Pickup t s Notice Various Reset Modes are available Resetting via characterist...

Страница 706: ...694 t s t multiplier Trip Reset x Pickup Multiples of Pickup t 13 5 t multiplier s Pickup 1 IG 2 t 13 5 t multiplier s Pickup 1 IG Notice Various Reset Modes are available Resetting via characteristic...

Страница 707: ...695 t s t multiplier x Pickup Multiples of Pickup Trip Reset t 120 t multiplier s Pickup 1 IG t 120 t multiplier s 1 IG 2 Pickup Notice Various Reset Modes are available Resetting via characteristic...

Страница 708: ...696 t s t multiplier x Pickup Multiples of Pickup Trip Reset t 80 t multiplier s Pickup 1 IG 2 t 80 t multiplier s Pickup 1 IG 2 Notice Various Reset Modes are available Resetting via characteristic...

Страница 709: ...t multiplier x Pickup Multiples of Pickup t 0 0515 t multiplier s Pickup 1 IG 0 02 0 1140 t 4 85 t multiplier s 1 IG 2 Pickup Trip Reset Notice Various Reset Modes are available Resetting via characte...

Страница 710: ...s t multiplier x Pickup Multiples of Pickup Trip Reset t 21 6 t multiplier s 1 IG 2 Pickup t 19 61 t multiplier s Pickup 1 IG 2 0 491 Notice Various Reset Modes are available Resetting via characteri...

Страница 711: ...s t multiplier x Pickup Multiples of Pickup Trip Reset t 28 2 t multiplier s Pickup 1 IG 2 0 1217 t 29 1 t multiplier s 1 IG 2 Pickup Notice Various Reset Modes are available Resetting via characteri...

Страница 712: ...s 2 IG 0 IGnom x In Multiples of the Nominal Current Notice Various Reset Modes are available Resetting via characteristic delayed and instantaneous Therm Flat t 5 t multiplier s IGnom IG 0 t 5 t mul...

Страница 713: ...tiples of the Nominal Current t 5 1 t multiplier s 2 IG 0 IGnom Notice Various Reset Modes are available Resetting via characteristic delayed and instantaneous IT t 5 1 t multiplier s IGnom IG 1 1 0 0...

Страница 714: ...ltiples of the Nominal Current t 5 1 t multiplier s 2 IG 0 IGnom Notice Various Reset Modes are available Resetting via characteristic delayed and instantaneous I2T t 5 1 t multiplier s IGnom IG 2 2 0...

Страница 715: ...ltiples of the Nominal Current t Notice Various Reset Modes are available Resetting via characteristic delayed and instantaneous I4T t 5 1 t multiplier s IGnom IG 4 4 5 1 t multiplier s 2 IGnom IG 0 0...

Страница 716: ...uthority Local Ctrl Remote Switching Authority Remote Ctrl SG Indeterm Minimum one Switchgear is moving Position cannot be determined Ctrl SG Disturb Minimum one Switchgear is disturbed Bkr SI SingleC...

Страница 717: ...y include the CLOSE command of the Prot module Bkr OPEN Cmd Signal OPEN command issued to the switchgear Depending on the setting the signal may include the OPEN command of the Prot module Bkr CLOSE C...

Страница 718: ...Sum Limit of interrupting currents has been exceeded 50P 1 Active Signal Active 50P 1 ExBlo Signal External Blocking 50P 1 Rvs Blo Signal Reverse Blocking 50P 1 Blo TripCmd Signal Trip Command blocked...

Страница 719: ...nal Adaptive Parameter 1 50P 2 AdaptSet 2 Signal Adaptive Parameter 2 50P 2 AdaptSet 3 Signal Adaptive Parameter 3 50P 2 AdaptSet 4 Signal Adaptive Parameter 4 50P 2 ExBlo1 I Module Input State Extern...

Страница 720: ...odule Input State Adaptive Parameter1 50P 3 AdaptSet2 I Module Input State Adaptive Parameter2 50P 3 AdaptSet3 I Module Input State Adaptive Parameter3 50P 3 AdaptSet4 I Module Input State Adaptive Pa...

Страница 721: ...Signal Pickup IB 51P 2 Pickup IC Signal Pickup IC 51P 2 Pickup Signal Pickup 51P 2 Trip Phase A Signal General Trip Phase A 51P 2 Trip Phase B Signal General Trip Phase B 51P 2 Trip Phase C Signal Gen...

Страница 722: ...nal Adaptive Parameter 4 51P 3 ExBlo1 I Module Input State External Blocking1 51P 3 ExBlo2 I Module Input State External Blocking2 51P 3 ExBlo TripCmd I Module Input State External Blocking of the Tri...

Страница 723: ...ckup IX or IR 50X 2 Trip Signal Trip 50X 2 TripCmd Signal Trip Command 50X 2 DefaultSet Signal Default Parameter Set 50X 2 AdaptSet 1 Signal Adaptive Parameter 1 50X 2 AdaptSet 2 Signal Adaptive Param...

Страница 724: ...1X 2 ExBlo Signal External Blocking 51X 2 Rvs Blo Signal Reverse Blocking 51X 2 Blo TripCmd Signal Trip Command blocked 51X 2 ExBlo TripCmd Signal External Blocking of the Trip Command 51X 2 Pickup Si...

Страница 725: ...Module Input State Adaptive Parameter1 50R 1 AdaptSet2 I Module Input State Adaptive Parameter2 50R 1 AdaptSet3 I Module Input State Adaptive Parameter3 50R 1 AdaptSet4 I Module Input State Adaptive...

Страница 726: ...e Parameter 4 51R 1 ExBlo1 I Module Input State External Blocking1 51R 1 ExBlo2 I Module Input State External Blocking2 51R 1 ExBlo TripCmd I Module Input State External Blocking of the Trip Command 5...

Страница 727: ...6 1 ExBlo1 I Module Input State External Blocking1 46 1 ExBlo2 I Module Input State External Blocking2 46 1 ExBlo TripCmd I Module Input State External Blocking of the Trip Command 46 2 Active Signal...

Страница 728: ...ection Settings SOTF AR Blo Signal Blocked by AR SOTF I Signal No Load Current SOTF ExBlo1 I Module Input State External Blocking SOTF ExBlo2 I Module Input State External Blocking SOTF Rvs Blo I Modu...

Страница 729: ...t State External Blocking2 ExP 2 ExBlo TripCmd I Module Input State External Blocking of the Trip Command ExP 2 Alarm I Module Input State Alarm ExP 2 Trip I Module Input State Trip ExP 3 Active Signa...

Страница 730: ...Trigger3 I Module Input Trigger that will start the BF TCM Active Signal Active TCM ExBlo Signal External Blocking TCM Pickup Signal Pickup Trip Circuit Supervision TCM Not Possible Not possible beca...

Страница 731: ...e Alarm 1 Signal AR Service Alarm 1 too many switching operations AR Service Alarm 2 Signal AR Service Alarm 2 too many switching operations AR Max Shots h exceeded Signal The maximum allowed number o...

Страница 732: ...1 I State of the module input Main 1 Breaker Closed Wired Inputs 52b M1 I State of the module input Main 1 Breaker Open Wired Inputs TOCa M1 I State of the module input Main 1 Breaker Connected Wired...

Страница 733: ...risk of taking an entire process off line Note Zone Interlocking and Supervision Contact cannot be disarmed YOU MUST ENSURE that the relays are ARMED AGAIN after maintenance RO 3 X2 Outs forced Signal...

Страница 734: ...munication Command Modbus Comm Cmd 3 Communication Command Modbus Comm Cmd 4 Communication Command Modbus Comm Cmd 5 Communication Command Modbus Comm Cmd 6 Communication Command Modbus Comm Cmd 7 Com...

Страница 735: ...irtInp29 Signal Virtual Input IEC61850 GGIO Ind IEC61850 VirtInp30 Signal Virtual Input IEC61850 GGIO Ind IEC61850 VirtInp31 Signal Virtual Input IEC61850 GGIO Ind IEC61850 VirtInp32 Signal Virtual In...

Страница 736: ...te of the Virtual Output GGIO IEC61850 VirtOut29 I Module input state Binary state of the Virtual Output GGIO IEC61850 VirtOut30 I Module input state Binary state of the Virtual Output GGIO IEC61850 V...

Страница 737: ...Gate Out Signal Output of the logic gate Logic LE2 Timer Out Signal Timer Output Logic LE2 Out Signal Latched Output Q Logic LE2 Out inverted Signal Negated Latched Output Q NOT Logic LE2 Gate In1 I S...

Страница 738: ...ed Output Q Logic LE6 Out inverted Signal Negated Latched Output Q NOT Logic LE6 Gate In1 I State of the module input Assignment of the Input Signal Logic LE6 Gate In2 I State of the module input Assi...

Страница 739: ...In1 I State of the module input Assignment of the Input Signal Logic LE10 Gate In2 I State of the module input Assignment of the Input Signal Logic LE10 Gate In3 I State of the module input Assignmen...

Страница 740: ...14 Gate In2 I State of the module input Assignment of the Input Signal Logic LE14 Gate In3 I State of the module input Assignment of the Input Signal Logic LE14 Gate In4 I State of the module input As...

Страница 741: ...18 Gate In3 I State of the module input Assignment of the Input Signal Logic LE18 Gate In4 I State of the module input Assignment of the Input Signal Logic LE18 Reset Latch I State of the module input...

Страница 742: ...2 Gate In4 I State of the module input Assignment of the Input Signal Logic LE22 Reset Latch I State of the module input Reset Signal for the Latching Logic LE23 Gate Out Signal Output of the logic ga...

Страница 743: ...al Logic LE26 Reset Latch I State of the module input Reset Signal for the Latching Logic LE27 Gate Out Signal Output of the logic gate Logic LE27 Timer Out Signal Timer Output Logic LE27 Out Signal L...

Страница 744: ...e input Reset Signal for the Latching Logic LE31 Gate Out Signal Output of the logic gate Logic LE31 Timer Out Signal Timer Output Logic LE31 Out Signal Latched Output Q Logic LE31 Out inverted Signal...

Страница 745: ...gic LE35 Gate Out Signal Output of the logic gate Logic LE35 Timer Out Signal Timer Output Logic LE35 Out Signal Latched Output Q Logic LE35 Out inverted Signal Negated Latched Output Q NOT Logic LE35...

Страница 746: ...Logic LE39 Timer Out Signal Timer Output Logic LE39 Out Signal Latched Output Q Logic LE39 Out inverted Signal Negated Latched Output Q NOT Logic LE39 Gate In1 I State of the module input Assignment o...

Страница 747: ...d Output Q Logic LE43 Out inverted Signal Negated Latched Output Q NOT Logic LE43 Gate In1 I State of the module input Assignment of the Input Signal Logic LE43 Gate In2 I State of the module input As...

Страница 748: ...47 Gate In1 I State of the module input Assignment of the Input Signal Logic LE47 Gate In2 I State of the module input Assignment of the Input Signal Logic LE47 Gate In3 I State of the module input As...

Страница 749: ...51 Gate In2 I State of the module input Assignment of the Input Signal Logic LE51 Gate In3 I State of the module input Assignment of the Input Signal Logic LE51 Gate In4 I State of the module input As...

Страница 750: ...55 Gate In3 I State of the module input Assignment of the Input Signal Logic LE55 Gate In4 I State of the module input Assignment of the Input Signal Logic LE55 Reset Latch I State of the module input...

Страница 751: ...9 Gate In4 I State of the module input Assignment of the Input Signal Logic LE59 Reset Latch I State of the module input Reset Signal for the Latching Logic LE60 Gate Out Signal Output of the logic ga...

Страница 752: ...al Logic LE63 Reset Latch I State of the module input Reset Signal for the Latching Logic LE64 Gate Out Signal Output of the logic gate Logic LE64 Timer Out Signal Timer Output Logic LE64 Out Signal L...

Страница 753: ...e input Reset Signal for the Latching Logic LE68 Gate Out Signal Output of the logic gate Logic LE68 Timer Out Signal Timer Output Logic LE68 Out Signal Latched Output Q Logic LE68 Out inverted Signal...

Страница 754: ...gic LE72 Gate Out Signal Output of the logic gate Logic LE72 Timer Out Signal Timer Output Logic LE72 Out Signal Latched Output Q Logic LE72 Out inverted Signal Negated Latched Output Q NOT Logic LE72...

Страница 755: ...Logic LE76 Timer Out Signal Timer Output Logic LE76 Out Signal Latched Output Q Logic LE76 Out inverted Signal Negated Latched Output Q NOT Logic LE76 Gate In1 I State of the module input Assignment o...

Страница 756: ...ut Signal Latched Output Q Logic LE80 Out inverted Signal Negated Latched Output Q NOT Logic LE80 Gate In1 I State of the module input Assignment of the Input Signal Logic LE80 Gate In2 I State of the...

Страница 757: ...Communication Sys Ack Counter Comm Signal Reset of all Counters Communication Sys Ack Comm Comm Signal Acknowledge Communication Communication Sys Ack TripCmd Comm Signal Reset Trip Command Communicat...

Страница 758: ...d Signal Negated Latched Output Q NOT Logic LE2 Gate Out Signal Output of the logic gate Logic LE2 Timer Out Signal Timer Output Logic LE2 Out Signal Latched Output Q Logic LE2 Out inverted Signal Neg...

Страница 759: ...ut Signal Latched Output Q Logic LE10 Out inverted Signal Negated Latched Output Q NOT Logic LE11 Gate Out Signal Output of the logic gate Logic LE11 Timer Out Signal Timer Output Logic LE11 Out Signa...

Страница 760: ...nverted Signal Negated Latched Output Q NOT Logic LE20 Gate Out Signal Output of the logic gate Logic LE20 Timer Out Signal Timer Output Logic LE20 Out Signal Latched Output Q Logic LE20 Out inverted...

Страница 761: ...ate Out Signal Output of the logic gate Logic LE29 Timer Out Signal Timer Output Logic LE29 Out Signal Latched Output Q Logic LE29 Out inverted Signal Negated Latched Output Q NOT Logic LE30 Gate Out...

Страница 762: ...LE38 Timer Out Signal Timer Output Logic LE38 Out Signal Latched Output Q Logic LE38 Out inverted Signal Negated Latched Output Q NOT Logic LE39 Gate Out Signal Output of the logic gate Logic LE39 Tim...

Страница 763: ...LE47 Out Signal Latched Output Q Logic LE47 Out inverted Signal Negated Latched Output Q NOT Logic LE48 Gate Out Signal Output of the logic gate Logic LE48 Timer Out Signal Timer Output Logic LE48 Ou...

Страница 764: ...nverted Signal Negated Latched Output Q NOT Logic LE57 Gate Out Signal Output of the logic gate Logic LE57 Timer Out Signal Timer Output Logic LE57 Out Signal Latched Output Q Logic LE57 Out inverted...

Страница 765: ...ate Out Signal Output of the logic gate Logic LE66 Timer Out Signal Timer Output Logic LE66 Out Signal Latched Output Q Logic LE66 Out inverted Signal Negated Latched Output Q NOT Logic LE67 Gate Out...

Страница 766: ...LE75 Timer Out Signal Timer Output Logic LE75 Out Signal Latched Output Q Logic LE75 Out inverted Signal Negated Latched Output Q NOT Logic LE76 Gate Out Signal Output of the logic gate Logic LE76 Tim...

Страница 767: ...ntries depends on the type of device Name Description No assignment DI 4P X1 DI 1 Signal Digital Input DI 4P X1 DI 2 Signal Digital Input DI 4P X1 DI 3 Signal Digital Input DI 4P X1 DI 4 Signal Digita...

Страница 768: ...Voltage Protection 48 Incomplete Sequence Start up time Supervison 49 Thermal Protection 49M Thermal Motor Protection 49R Thermal Rotor Protection 49S Thermal Stator Protection 50BF Breaker Failure 5...

Страница 769: ...ure 81 Frequency Protection 81U Underfrequency Protection 81O Overfrequency Protection 81R ROCOF df dt 86 Lock Out 87 Differential Protection Generator Transformer Busbar 87GD Ground Differential Prot...

Страница 770: ...ING FROM COURSE OF DEALING OR USAGE OF TRADE ARE MADE REGARDING THE INFORMATION RECOMMENDATIONS AND DESCRIPTIONS CONTAINED HEREIN In no event will Eaton be responsible to the purchaser or user in cont...

Отзывы: