EDR-3000
IM02602003E
Parameter
Description
Setting range
Default
Menu path
Inverting 5
Inverting of the state of the assigned signal.
Inactive,
Active
Inactive
[Device Para
/Relay Outputs
/RO-5 X2
/RO 5]
Assignment 6
Assignment
1..n, Assignment
List
-.-
[Device Para
/Relay Outputs
/RO-5 X2
/RO 5]
Inverting 6
Inverting of the state of the assigned signal.
Inactive,
Active
Inactive
[Device Para
/Relay Outputs
/RO-5 X2
/RO 5]
Assignment 7
Assignment
1..n, Assignment
List
-.-
[Device Para
/Relay Outputs
/RO-5 X2
/RO 5]
Inverting 7
Inverting of the state of the assigned signal.
Inactive,
Active
Inactive
[Device Para
/Relay Outputs
/RO-5 X2
/RO 5]
DISARMED Ctrl
Enables and disables the disarming of the relay outputs.
This is the first step of a two step process, to inhibit the
operation or the relay outputs. Please refer to
"DISARMED" for the second step.
Inactive,
Active
Inactive
[Service
/Test Mode (Prot
inhibit)
/WARNING! Cont?
/DISARMED
/RO-5 X2]
Disarm Mode
CAUTION! RELAYS DISARMED in order to safely
perform maintenance while eliminating the risk of taking
an entire process off-line. (Note: Zone Interlocking and
Supervision Contact cannot be disarmed). YOU MUST
ENSURE that the relays are ARMED AGAIN after
maintenance.
Permanent,
Timeout
Permanent
[Service
/Test Mode (Prot
inhibit)
/WARNING! Cont?
/DISARMED
/RO-5 X2]
www.eaton.com
103
Содержание EDR 3000
Страница 2: ......
Страница 4: ......
Страница 6: ......
Страница 7: ...Medium Voltage Switchgear Assembly...
Страница 8: ......
Страница 10: ......
Страница 11: ...Component Data...
Страница 12: ......
Страница 64: ...EDR 3000 IM02602003E Ethernet RJ45 Terminal Marking www eaton com 52 1 8 TxD TxD RxD N C N C RxD N C N C...
Страница 659: ...EDR 3000 IM02602003E Real Time Clock Running Reserve of the Real Time Clock 1 year min www eaton com 647...