EDR-3000
IM02602003E
Zone Interlocking Trip Logic [X2]
The following overcurrent protection elements trigger Phase Zone-Interlock trip functions:
1.5 * 51P[1];
50P[1]; and
50P[2].
The following overcurrent protection elements trigger Ground Zone Interlock trip functions:
51X[1];
50X[1];
50X[2];
51R[1];
50R[1], and
50R[2].
www.eaton.com
467
Содержание EDR 3000
Страница 2: ......
Страница 4: ......
Страница 6: ......
Страница 7: ...Medium Voltage Switchgear Assembly...
Страница 8: ......
Страница 10: ......
Страница 11: ...Component Data...
Страница 12: ......
Страница 64: ...EDR 3000 IM02602003E Ethernet RJ45 Terminal Marking www eaton com 52 1 8 TxD TxD RxD N C N C RxD N C N C...
Страница 659: ...EDR 3000 IM02602003E Real Time Clock Running Reserve of the Real Time Clock 1 year min www eaton com 647...