EDR-3000
IM02602003E
Global Protection Parameters of the Trip Circuit Monitoring Module
Parameter
Description
Setting range
Default
Menu path
Mode
Select if trip circuit is going to be monitored when the
breaker is closed or when the breaker is either open or
close.
Closed,
Either
Closed
[Protection Para
/Global Prot Para
/Supervision
/TCM]
Input 1
Select the input configured to monitor the trip coil when
the breaker is closed.
1..n, Dig Inputs
-.-
[Protection Para
/Global Prot Para
/Supervision
/TCM]
Input 2
Select the input configured to monitor the trip coil when
the breaker is open. Only available if Mode set to
“Either”.
Only available if: Mode = Either
1..n, Dig Inputs
-.-
[Protection Para
/Global Prot Para
/Supervision
/TCM]
ExBlo1
External blocking of the module, if blocking is activated
(allowed) within a parameter set and if the state of the
assigned signal is true.
1..n, Assignment
List
-.-
[Protection Para
/Global Prot Para
/Supervision
/TCM]
ExBlo2
External blocking of the module, if blocking is activated
(allowed) within a parameter set and if the state of the
assigned signal is true.
1..n, Assignment
List
-.-
[Protection Para
/Global Prot Para
/Supervision
/TCM]
www.eaton.com
580
Содержание EDR 3000
Страница 2: ......
Страница 4: ......
Страница 6: ......
Страница 7: ...Medium Voltage Switchgear Assembly...
Страница 8: ......
Страница 10: ......
Страница 11: ...Component Data...
Страница 12: ......
Страница 64: ...EDR 3000 IM02602003E Ethernet RJ45 Terminal Marking www eaton com 52 1 8 TxD TxD RxD N C N C RxD N C N C...
Страница 659: ...EDR 3000 IM02602003E Real Time Clock Running Reserve of the Real Time Clock 1 year min www eaton com 647...