EDR-3000
IM02602003E
Setting Group Parameters of the BF
In order to prevent a faulty activation of the BF Module, the pickup (alarm) time
must be greater than the sum of:
Operating time of the protective relay
+The close-open time of the breaker (please refer to the technical data of
the manufacturer of the breaker);
+Drop off time (current- or position indicators)
+Security margin.
Parameter
Description
Setting range
Default
Menu path
Function
Permanent activation or deactivation of module/element. Inactive,
Active
Inactive
[Protection Para
/<1..4>
/Supervision
/BF]
ExBlo Fc
Activate (allow) or inactivate (disallow) blocking of the
module/element. This parameter is only effective if a
signal is assigned to the corresponding global protection
parameter. If the signal becomes true, those
modules/elements are blocked that are parameterized
"ExBlo Fc=active".
Inactive,
Active
Inactive
[Protection Para
/<1..4>
/Supervision
/BF]
I-BF >
Current level that needs to exist after Trip Command has
been given.
Only available if: Scheme50BF = Or Scheme = 50BF and
CB Pos
0.02 - 4.00In
0.02In
[Protection Para
/<1..4>
/Supervision
/BF]
t-BF
If the delay time is expired, an BF alarm is given out.
0.00 - 10.00s
0.20s
[Protection Para
/<1..4>
/Supervision
/BF]
www.eaton.com
554
Содержание EDR 3000
Страница 2: ......
Страница 4: ......
Страница 6: ......
Страница 7: ...Medium Voltage Switchgear Assembly...
Страница 8: ......
Страница 10: ......
Страница 11: ...Component Data...
Страница 12: ......
Страница 64: ...EDR 3000 IM02602003E Ethernet RJ45 Terminal Marking www eaton com 52 1 8 TxD TxD RxD N C N C RxD N C N C...
Страница 659: ...EDR 3000 IM02602003E Real Time Clock Running Reserve of the Real Time Clock 1 year min www eaton com 647...