Copyright 2022Baker Hughes Company.
English–DPI610E Instruction Manual | 217
HART Dashboard
12.3.3 Measure Variables
Figure 12-3: Measure Variables screen
This screen shows the following variables:
•
HART PV (Primary variable)
•
Loop Current (Measured by HART device)
•
% Range (Percentage - the current PV reading of the PV range)
•
CH1 Primary (Primary reading on CH1)
•
CH2 MA (Loop current measured by the DPI 610E).
12.3.4 Signal Condition
Figure 12-4: Signal Condition screen
This screen shows the following variables (variables with a pen
icon can be edited):
•
PV Units (Measurement units the primary variable is displayed)
•
PV LRV (Primary variable Lower Range Value)
•
PV URV (Primary variable Upper Range Value)
•
PV Damping (Primary variable damping value in seconds)
•
PV Transfer Function (Primary function transfer function selection code)
•
Write Protect (Write protect code).