dormakaba ED250 IG Installation Instructions
Chapter 21
21.3 Verify driving parameters for low energy operation
WARNING
Parameters for ED250 In-ground must be
configured for low energy operation!
21.2.2
Verify driving parameter factory settings for
low energy operation.
Step 1
Press
Press and hold right button greater
than 3 sec. to enter parameter mode;
AS parameter displayed.
Step 2
Press
Scroll to
So
parameter. Opening speed,
automatic mode.
Step 3
Press
Displays "25" , factory setting.
Maximum parameter value in low
energy mode is 27
Step 4
Press
Returns to So parameter.
Step 5
Press
Scroll to
Sc
parameter. Closing speed,
automatic mode.
Step 6
Press
Displays "25" , factory setting.
Maximum parameter value in low
energy mode is 27
Step 7
Press
Returns to Sc parameter.
Step 8
Press
Scroll to
Fo
parameter. Static force in
opening direction.
Step 9
Press
Displays "06" , factory setting.
Maximum parameter value in low
energy mode is 6 Newtons (15 lbf)
Step 10
Press
Returns to So parameter.
Step 11
Press
Scroll to
Fc
parameter. Static force in
closing direction.
Step 12
Press
Displays "06" , factory setting.
Maximum parameter value in low
energy mode is 6 Newtons (15 lbf)
Step 13
Press
Returns to Fc parameter.
Step 14
Press
Exits parameter mode. Display
indicates "ready for learning cycle".
TIPS AND RECOMMENDATIONS
Adjustments to these and other driving
parameters can be made once door learning
cycle has been completed.