dormakaba ED250 IG Installation Instructions
Chapter 16
16.20 Final anchoring cement pour
16.21 Remove cement case cover for ED250 commissioning
16.21.1 Remove cement case cover.
Fig. 16.20.1 ED250 cement case end view,
final anchoring cement pour
16.20.1 Final anchoring cement pour.
Center hung door shown as reference.
1. Door must be hung and in its final
position.
2. Pour anchoring cement into blockout to
a minimum depth of four inches from
bottom of cement case.
CAUTION
Allow cement to set for time
period referenced in
manufacturer's instructions.
16.19 Reinstall cement case cover
Fig. 16.19.1 ED250 cement case with cover installed.
CAUTION
Cover must be installed on cement
case before final anchoring
cement poured in concrete
blockout.
1
(21) 8-32 x 3/4" PFHMS
(Phillips flat head
machine screws)
16.19.1 Install cover.
1. Insure gasket is clean, then place cover
over gasket.
2. Install the twenty one 8-32 x 3/4"PFHMS
securing the cover to the cement case.
Hand tighten with No. 2 Phillips
screwdriver.
CAUTION
Do not over tighten screws!
4” min.
Top of anchoring
cement
4 7/8”
Bottom of cement case
1