Table 5–7 RF35 Disk Drive Removal Procedure
Step
Action
1
Ask the operator or system manager to shut down the zone using the procedure
in Section 5.3.2.
2
Open the front door of the cabinet.
3
Turn off the RF35 disk drive.
4
Loosen the four screws that secure the DSSI disk drive rack in the CPU
cabinet.
5
Pull the DSSI disk drive rack out until it locks in place.
6
Swing the LDC bracket out until you can see the disk drives. See Figure 5–7.
7
Label the DSSI, power, and disk signal cables, and disconnect them from the
RF35 drive you are removing.
8
Loosen the captive screws at the bottom of the drive.
9
Remove the drive and bracket.
10
Remove the six Phillips screws that secure the bracket on the drive.
Error Handling and Analysis 5–13