4.
Set the node address for the device. Refer to
“Device Address Switch Setting” in the “Switch
Setting” section (Section VIII) of this manual for
complete information regarding the switch setting
procedure.
5.
Install the communication module inside the
junction box. Be sure that the keyed ribbon cable is
properly connected.
6.
Inspect the junction box O-ring to be sure that it is
in good condition and properly installed. Lubricate
the O-ring and the threads of the junction box cover
with a thin coat of an appropriate grease to ease
installation and ensure a watertight enclosure. The
recommended lubricant is a silicone free grease,
available from Det-Tronics. Place the cover on the
junction box. Tighten only until snug. Do not over
tighten.
EQ2200UV UV FLAME DETECTOR
1.
Remove the sensor housing from the bulkhead (turn
counterclockwise). Install the sensor module and
replace the sensor housing. See Figure VII-20.
NOTE
If the detector is equipped with a cover locking
device, it must be loosened using a 5/32
hexagonal (Allen) wrench (see Figure VII-21).
2.
Mount the swivel mounting bracket using 1/4 inch
(M6) screws with a length of at least 1 inch (25
mm). The mounting surface should be free of
vibration. Allow adequate space around the swivel
to facilitate aiming and wiring of the detector.
Armored flexible conduit should be used for the
final 3 feet (one meter) of the cable run to allow for
aiming and alignment of the detector.
3.
Attach the detector to the swivel mounting bracket.
4.
Remove the rear housing from the bulkhead.
5.
Connect the wires to the appropriate screw
terminals on the terminal block. See Figure VII-22.
Connect the cable shields to the terminals
provided.
6.
Set the rocker switches on the DIP switch assembly
on the electronic module for the desired address.
Refer to “Device Address Switch Setting” in the
“Switch Setting” section of this manual for complete
information regarding the switch setting procedure.
7.
Install the electronic module, ensuring that the
connector is aligned correctly. Tighten the three
captive screws that hold the electronic module in
place. See Figures VII-20 and VII-23.
8.
Replace the rear housing and hand tighten to ensure
proper sealing. See Figures VII-20 and VII-21.
9.
Aim the detector at the potential hazard and tighten
the nut.
10. Check the viewing window surface (Figure VII-24)
and ensure that:
A) the
oi
source (UV test lamp opening) is located
on top
B) the split in the
oi
reflective ring is not aligned
with the UV test lamp opening on the detector
module
C) the split in the
oi
ring is directed downward to
prevent a buildup of contaminants between the
oi
ring and the viewing window.
95-8470
VII-15
1
2
3
4
5
6
7
8
9
10
IDCSC
MANUAL PULL STATION
OR OTHER CONTACT DEVICE
14
13
12
11
–
–
+
+
24 VDC
+
–
+
–
A
B
A
B
CIRCUIT 1
CIRCUIT 2
COM 2
COM SHIELDS
COM 1
A2076
EOL (10K)
EOL (10K)
3.3 K
3.3 K
3.3 K
Figure VII-19B—Terminal Identification for EQ2200IDCSC