Terminals 11 to 14 —
24 vdc power input
Connect the module power
supply to terminals 12 and 13.
If an auxiliary output supply is
used for powering solenoids, it
should be connected to
terminals 11 and 14.
Jumpers
Terminals 13 and 14 are connected by jumper JP2 and
terminals 11 and 12 are connected by jumper JP3.
These two jumpers (JP2 and JP3) must be cut if an
auxiliary output power supply is being used. See Figure
VII-41 for the locations of jumpers on the circuit board.
When an explosive initiator is being used, jumper JP1
must be cut. If a solenoid is used, the jumper must
remain in.
Address Switch Setting
Each device on the LON/SLC must be assigned a
unique address. This is accomplished by setting DIP
switches on the release module circuit board. The valid
address range is from 5 to 250. For complete
information on address switch setting, refer to
“LON/SLC Device Address Switch Setting” in Section
VIII. For convenience in determining the correct
positions for address switches, refer to the table
“Address Switch Settings” at the back of this manual.
VII-28
9 10
7 8
5 6
3 4
1 2
1314
1112
JP1
JP2
JP3
A1902
Figure VII–41—Agent Release Module Wiring Terminals and Jumpers
1
2
3
4
5
6
7
8
9
10
1
2
3
4
EXPLOSIVE INITIATOR OPTION
DUAL
SOLENOIDS
14
13
12
11
–
–
+
+
24 VDC
+
–
+
–
A
B
A
B
SINGLE
SOLENOID
COM 2
COM SHIELD
COM 1
NOTE:
TERMINALS 12 AND 13 ARE FOR MODULE POWER SUPPLY.
TERMINALS 11 AND 14 ARE FOR AUXILIARY OUTPUT POWER SUPPLY.
JUMPERS JP2 AND JP3 MUST BE REMOVED IF AN AUXILIARY POWER SUPPLY IS USED.
NOTES:
1. JUMPER JP1 MUST BE REMOVED IF EXPLOSIVE INITIATOR IS USED.
2. RESISTOR IS USED TO COMPENSATE FOR 10 OHMS CIRCUIT RESISTANCE.
RESISTOR MUST BE RATED 1 WATT MINIMUM (WIRE-WOUND RESISTOR PREFERRED).
WHEN MEASURING THE TOTAL RELEASE CIRCUIT RESISTANCE,
USE AN OHM METER WITH A CURRENT OUTPUT OF 10 MA MAXIMUM.
3. MAXIMUM NUMBER OF EXPLOSIVE INITIATORS PER CIRCUIT IS 12.
EACH CIRCUIT MUST NOT EXCEED 10 OHMS INCLUDING CABLE RESISTANCE.
B1900
SEE NOTE 2.
Figure VII–40—Wiring Configuration for Agent Release Module