XI-2
BATTERIES
Batteries must be replaced every 48 months, or sooner
if required by local codes. Only sealed batteries are to
be used.
TROUBLESHOOTING
Table XI-1 is intended to serve as an aid in locating the
cause of a system malfunction. If the problem cannot
be corrected, contact the factory for assistance.
REPLACEMENT PARTS
Eagle devices are not designed to be repaired in the
field. If a problem should develop, first carefully check
for proper wiring, programming and calibration. If it is
determined that the problem is caused by an electronic
defect, the device must be returned to the factory for
repair.
NOTE
When replacing a device, be sure that the rocker
switches on the replacement are set the same as
the original. Remove power before removing or
plugging in the replacement unit. When a DCU,
IDC or flame detector is replaced, the point must
be re-configured. If the auto-configure feature is
enabled, configuration is done automatically.
T0025B
Symptom
Possible Cause
Gateway Green Power LED is off.
Power wiring is wrong.
Gateway Fault LED is on and F30 is displayed.
An open in the LON wiring. This can also be caused by
a device that has isolated a short on the LON. Press
the Gateway reset switch after the LON is repaired to
clear the fault.
Gateway Fault LED is on and F40 is displayed.
The external or faceplate reset switch is held closed.
Gateway Fault LED is on and F50 or F51 is displayed.
A fault was detected on one of the LON communication
boards. Replace the gateway.
Gateway Fault LED is on and F60 is displayed.
The gateway was not configured using the OIS
software.
No communication with the host computer.
Wrong communication parameters (check the gateway
DIP switches), or communication wiring.
Logic Controller Fault LED is on.
See Logic Controller table (Table II-3).
Logic Controller Power Fault LED is on.
Power related fault.
Logic Controller Supervisory LED is on.
A field device programmed as a supervisory input is
active.
The Gateway displays F10 for a field device.
This is caused by a problem with the field device input.
Check for wiring or sensor faults.
The Gateway displays F20 for a field device.
The field device is not reporting or communication fault.
Check power and LON wiring. Check that the device
address is set properly.
The Gateway displays F60 for a field device.
The device configuration needs to be downloaded
using the OIS software.
UV Detector LEDs not blinking.
Dirty viewing window.
oi
ring dirty, misaligned or missing.
Input voltage too low.
Internal high voltage out of tolerance.
Open, shorted or incorrect wiring.
Device not configured.
UV Detector does not respond to fire stimuli or to manual
oi
test.
Dirty viewing window.
Insufficient supply voltage.
Open, shorted or incorrect wiring.
Defect in UV module.
Defect in electronic module.
Table XI-1—Troubleshooting Guide