B-2
MODEL EQ2200IDC SERIES INITIATING DEVICE CIRCUIT AND
MODEL EQ2200IDCGF SERIES INITIATING DEVICE CIRCUIT GROUND FAULT
• Explosion-proof for Class I, Division 1, Groups B, C, and D Hazardous Locations per CSA C22.2 #30.
• Dust ignition-proof for Class II, Division 1, Groups E, F, and G, Class III Hazardous Locations per CSA C22.2 #25.
• Non-incendive for Class I, Div. 2, Groups A, B, C, and D; Class II, Div. 2, Groups F and G; Class III; Temperature
Code T4A Hazardous Locations per CSA C22.2 #213.
• EQ22EMIDC AND EQ22EMIDCGF non-incendive for Class I, Div. 2, Groups A, B, C, and D; Temperature Code
T4A Hazardous Locations per CSA C22.2 #213.
• Enclosure Rating Type 4X per CSA C22.2 #94.
• Operating Temperature Limits –40°C to +75°C.
• Storage Temperature Limits –55°C to +85°C.
• Relative Humidity Range: 5 to 95% RH.
• The Model EQ2200IDC Series must be used in conjunction with any CSA certified device providing relay contact
closure.
MODEL EQ2200UV SERIES UV FLAME DETECTOR:
• Explosion-proof for Class I, Division 1, Groups B, C and D Hazardous Locations per CSA C22.2 #30.
• Dust-ignitionproof for Class II, Division 1, Groups E, F, and G, Class III Hazardous Locations per CSA C22.2 #25.
• Non-incendive for Class I, Div. 2, Groups A, B, C, and D; Class II, Div. 2, Groups F and G; Class III; Temperature
Code T4A Hazardous Locations per CSA C22.2 #213.
• Enclosure Rating Type 4X per CSA C22.2 #94.
• Operating Temperature Limits –40°C to +75°C.
• Storage Temperature Limits –55°C to +85°C.
• Relative Humidity Range: 5 to 95% RH.
• Optional Q9001L Swivel Mount.
MODEL EQ2200UVHT SERIES HIGH TEMPERATURE UV FLAME DETECTOR
• Explosion-proof for Class I, Division 1, Groups B, C and D Hazardous Locations per CSA C22.2 #30.
• Dust-ignitionproof for Class II, Division 1, Groups E, F, and G, Class III Hazardous Locations per CSA C22.2 #25.
• Non-incendive for Class I, Div. 2, Groups A, B, C, and D; Class II, Div. 2, Groups F and G; Class III; Temperature
Code T4A Hazardous Locations per CSA C22.2 #213.
• Enclosure Rating Type 4X per CSA C22.2 #94.
• Operating Temperature Limits –40°C to +75°C for electronic module, –40°C to +125°C for UV detector.
• Storage Temperature Limits –55°C to +85°C.
• Relative Humidity Range: 5 to 95% RH.
• Optional Q9001B Swivel Mount for UV detector.