EQ2110PS, EQ2130PS AND EQ2175PS
Refer to Table VI-6 for Power Supply ratings.
BACKUP BATTERY
Refer to Table VI-7 or VI-8 to calculate the minimum size
of the backup battery (in amp hours). Select a sealed
lead-acid battery with an adequate amp hour rating.
NOTE
Connect two batteries in series for 24 volts. Be
sure that the battery enclosure is adequately
ventilated.
VI-4
Table VI-6—EQ21xxPS Power Supply Specifications
Device Type
Number of Devices
Alarm Current
Total Current for Device Type
LCU
1
X
0.340
=
0.340
Release Module
X
0.165
=
Signal Audible
X
0.120
=
Relay Module
X
0.090
=
P. S. Monitor
X
0.060
=
IDC/IDCGF/IDCSC
X
0.090
=
UV Detector
X
0.120
=
UV/IR Detector
X
0.120
=
DCUEX
X
0.160
=
DCU with H2S
X
0.075
=
DCU with PointWatch
X
0.320
=
ARM
X
0.120
=
SAM
X
0.120
=
Network Extender
X
0.090
=
Power Supply
X
0.300
=
Other
X
=
Total Solenoid Load
+
Total Signaling Load
+
TOTAL
ALARM
CURRENT FOR SYSTEM (IN AMPERES)
=
T0013B
Table VI–5—
Alarm
Current Requirements at 24 vdc
Characteristic
Power Supply
EQ2110PS
EQ2130PS
EQ2175PS
Input Voltage
120 vac
120/208/240 vac
120/208/240 vac
Input Current
4 Amps
11/6/6 Amps
24/15/12 Amps
Input Frequency
60 Hz
60 or 50 Hz
60 or 50 Hz
Supply Rating
10 Amps
30 Amps
75 Amps
Maximum Alarm Current
10 Amps
30 Amps
75 Amps
Maximum Standby Current
3.33 Amps
10 Amps
25 Amps
Recharge Current
6.67 Amps
20 Amps
50 Amps
Maximum Battery Capacity
100 AmpHours
300 AmpHours
750 AmpHours
Maximum Deluge Standby Current
1 Amp
3 Amps
7.5 Amps
Содержание Eagle Quantum 95-8470-05
Страница 116: ...Figure A1 A 10...
Страница 122: ...Figure B1 B 6...
Страница 125: ...APPENDIX D D 1 95 8470...
Страница 128: ...LON is a registered trademark of Echelon Corporation Modbus is a registered trademark of Modicon Inc...